ASYNCHRONOUS ELECTRIC MOTOR STARTING METHODS

There are several methods for starting asynchronous squirrel-cage electric motors.
The most common methods are: direct-on-line (DOL), with a soft starter (SS) or with a frequency converter (FC).

Direct-on-line starting

In case of direct-on-line starting (i.e. by connecting the motor to the electric mains with a simple line contactor), the motor starting 
time significantly increases due to high inertia of the impeller, which, in turn, results in high in-rush starting currents in the circuit. These 
currents of long duration may cause voltage slumps (especially if the feed line section falls short of the requirements), which may affect 
load operation.
The in-rush current consumed by an electric motor in case of DOL starting is 5-8 times larger than the rated value (or even 10-14 times 
larger in some rare instances). It should be noted that the torque developed by the motor also significantly exceeds the rated value.
Upon energisation the motor operates as a transformer with a squirrel-cage secondary winding formed by the rotor cage with a very low 
resistance.
The rotor develops high induced current causing a rush of current in the feed line.
The startup torque during starting averages 0.5-1.5 of the rated torque value.

Despite such advantages as simple construction, high startup current, quick start and low cost, direct-on-line systems are suitable only 
in the following cases:
•  the motor power is low compared to the mains power which limits the adverse effect of the rush of current
•  the driven mechanism does not require gradual speed build-up or is equipped with a damping device to smooth out the inrush
•  the high startup torque has no adverse effects on the operation of the driven mechanism

Soft start. SS starting.

A soft starter gradually increases the voltage supplied to the motor – from the initial to the rated value.
This starting system can be used to meet the following goals:
•  limit the motor current
•  regulate the torque

Regulation by limiting the current sets the maximum in-rush current equal to 300-400 % (or  250 % in some rare instances) of the rated 
current and reduces torque characteristics. This type of regulation is especially suited for turbomachinery such as centrifugal pumps and 
fans.
Regulation by variation of torque optimizes the torque during startup and reduces in-rush current in the circuit. These conditions are 
suitable for mechanisms with constant load resistance.
This type of soft starting may differ in the implementation pattern:
•  motor start
•  motor start and stop
•  device bridging at the end of start sequence
•  start and stop of several motors in stage circuits

Soft start. FC starting.

During the starting the FC raises the frequency from 0 Hz to the electrical mains frequency (50 or 60 Hz). As the frequency is increased 
gradually, the motor can be assumed to operate at its rated speed for a given frequency value. Furthermore, on the assumption that the 
motor runs at its rated speed the nominal torque should be immediately available whereas the current will be approximately equal to 
the rated value.
This starting system is used for speed control and regulation and can be used in the following cases:
•  start with high-inertia load
•  start with high load and limited-capacity power supply source
•  optimization of electric power consumption depending on turbomachinery speed
The aforementioned starting system can be used for all types of mechanisms.

www.blaubergventilatoren.de

Axis-p

12

Summary of Contents for AXIS-P Series

Page 1: ...Axial pressurisation fan USER S MANUAL EN Axis P...

Page 2: ...ny reserves the right to modify the technical characteristics design or configuration of its products at any time in order to incorporate the latest technological developments No part of this publicat...

Page 3: ...ing the unit control the user s manual must be turned over to the receiving operator UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS Disconnect the unit from power mains prior to any installation o...

Page 4: ...power mains prior to any technical maintenance Do not store any explosive or highly flammable substances in close proximity to the unit When the unit generates unusual sounds odour or emits smoke disc...

Page 5: ...stems with high air flow rates THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL MENTAL OR SENSORY CAPACITIES OR THOSE WITHOUT THE APPROPRIATE TRAINING THE UNIT MUST BE INST...

Page 6: ...60 40 C T tropical climate 10 50 C M maritime moderately cold climate 40 40 C O general climatic modification except maritime climate 60 50 C OM general maritime climatic modification 40 40 C V unive...

Page 7: ...al box Casing modification with a terminal box d n holes d n holes MODEL DIMENSIONS MM L D D1 D2 d n B Axis P400 350 450 400 450 490 8 12 480 Axis P450 350 450 550 450 500 540 8 12 525 Axis P500 350 4...

Page 8: ...quare cage rotor installed inside the casing The fan casing modifications depend on the electrical cable connection options The cable is connected to the electric motor terminal box via a cable gland...

Page 9: ...The length of the straight duct section downstream of the fan must be 1 5 2 D Installation of shorter air ducts may result in insufficient air pressure and air flow The flexible joints EVAF AF are re...

Page 10: ...crement Installation of a downstream contractor is not recommended Installation near bends To install the fan directly downstream of a bend elbow use a curved section with a large bending radius or an...

Page 11: ...on The fan must be integrated into a ventilation or smoke extraction system with an automatic control system The fan motor is rated for connection to 400 V 50 60 Hz three phase alternating current Con...

Page 12: ...smooth out the inrush the high startup torque has no adverse effects on the operation of the driven mechanism Soft start SS starting A soft starter gradually increases the voltage supplied to the moto...

Page 13: ...ces of success The use of an FC in this case helps solve the problem fundamentally Standard switching equipment automatic circuit breakers contactors and motor starters is not designed to withstand pr...

Page 14: ...rt No power supply Check the mains switch Check the electrical connections against the wiring diagram Jammed motor Carefully check the fan impeller for possible seizure and eliminate it if necessary I...

Page 15: ...place the fan with a unit of proper standard size The fan supplies less air than expected Wrong calculation of the ventilation network and wrong selection of the fan Re calculate the network parameter...

Page 16: ...handling requirements applicable for the particular type of cargo The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mecha...

Page 17: ...nded use by the user within the guaranteed period of operation The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component The warranty...

Page 18: ...www blaubergventilatoren de Axis P 18...

Page 19: ...______ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Sig...

Page 20: ...www blaubergventilatoren de B118EN 05...

Reviews: