Before installing the unit, carry out the following checks:
•  Make sure that the fan impeller rotates freely.
•  Make sure there is no condensate on the motor.
•  Check the electrical resistance of insulation between the motor windings and between each winding and the motor casing.
The fan can be mounted in any position – vertically, horizontally or tilted at any angle.

FAN INSTALLATION RECOMMENDATIONS

Fan mounting in the ductworks

To ensure smooth airflow at the fan inlet it is recommended to install 
a straight air duct segment with a cross section equal to the fan cross 
section. The air duct segment must be 3 ÷ 4 D (D is the inner fan diameter). 
The length of the straight duct section downstream of the fan must be 
1.5 ÷ 2 D. Installation of shorter air ducts may result in insufficient air 
pressure and air flow. The flexible joints EVAF-AF are recommended for 
vibration damping and noise attenuation.

4D

2D

D

Changing diameter installation

When changing from a smaller diameter to a larger one use a connector 
diffuser with the maximum opening angle of 12°.

max 12°

MOUNTING AND SET-UP

WHILE INSTALLING THE UNIT ENSURE CONVENIENT ACCESS FOR SUBSEQUENT 

MAINTENANCE AND REPAIR. 

ALL OPERATIONS DESCRIBED IN THIS USER’S MANUAL MUST BE PERFORMED BY 

QUALIFIED PERSONNEL ONLY, PROPERLY TRAINED AND QUALIFIED TO INSTALL AND 

MAINTAIN VENTILATION EQUIPMENT.

DO NOT ATTEMPT TO INSTALL THE PRODUCT YOURSELF.

IT IS UNSAFE AND IMPOSSIBLE WITHOUT SPECIAL KNOWLEDGE.

www.blaubergventilatoren.de

Axis-p

9

Summary of Contents for AXIS-P Series

Page 1: ...Axial pressurisation fan USER S MANUAL EN Axis P...

Page 2: ...ny reserves the right to modify the technical characteristics design or configuration of its products at any time in order to incorporate the latest technological developments No part of this publicat...

Page 3: ...ing the unit control the user s manual must be turned over to the receiving operator UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS Disconnect the unit from power mains prior to any installation o...

Page 4: ...power mains prior to any technical maintenance Do not store any explosive or highly flammable substances in close proximity to the unit When the unit generates unusual sounds odour or emits smoke disc...

Page 5: ...stems with high air flow rates THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL MENTAL OR SENSORY CAPACITIES OR THOSE WITHOUT THE APPROPRIATE TRAINING THE UNIT MUST BE INST...

Page 6: ...60 40 C T tropical climate 10 50 C M maritime moderately cold climate 40 40 C O general climatic modification except maritime climate 60 50 C OM general maritime climatic modification 40 40 C V unive...

Page 7: ...al box Casing modification with a terminal box d n holes d n holes MODEL DIMENSIONS MM L D D1 D2 d n B Axis P400 350 450 400 450 490 8 12 480 Axis P450 350 450 550 450 500 540 8 12 525 Axis P500 350 4...

Page 8: ...quare cage rotor installed inside the casing The fan casing modifications depend on the electrical cable connection options The cable is connected to the electric motor terminal box via a cable gland...

Page 9: ...The length of the straight duct section downstream of the fan must be 1 5 2 D Installation of shorter air ducts may result in insufficient air pressure and air flow The flexible joints EVAF AF are re...

Page 10: ...crement Installation of a downstream contractor is not recommended Installation near bends To install the fan directly downstream of a bend elbow use a curved section with a large bending radius or an...

Page 11: ...on The fan must be integrated into a ventilation or smoke extraction system with an automatic control system The fan motor is rated for connection to 400 V 50 60 Hz three phase alternating current Con...

Page 12: ...smooth out the inrush the high startup torque has no adverse effects on the operation of the driven mechanism Soft start SS starting A soft starter gradually increases the voltage supplied to the moto...

Page 13: ...ces of success The use of an FC in this case helps solve the problem fundamentally Standard switching equipment automatic circuit breakers contactors and motor starters is not designed to withstand pr...

Page 14: ...rt No power supply Check the mains switch Check the electrical connections against the wiring diagram Jammed motor Carefully check the fan impeller for possible seizure and eliminate it if necessary I...

Page 15: ...place the fan with a unit of proper standard size The fan supplies less air than expected Wrong calculation of the ventilation network and wrong selection of the fan Re calculate the network parameter...

Page 16: ...handling requirements applicable for the particular type of cargo The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mecha...

Page 17: ...nded use by the user within the guaranteed period of operation The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component The warranty...

Page 18: ...www blaubergventilatoren de Axis P 18...

Page 19: ...______ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Sig...

Page 20: ...www blaubergventilatoren de B118EN 05...

Reviews: