
14
4.4 FLUE TERMINAL LOCATION - Figs. 4.3 and 4.4
Notes:
1. In addition, the terminal should not be nearer than 150 mm to the framework of an opening into the building, i.e. a
window surround or door surround.
2. This clearance may be reduced to 25 mm without effecting the performance of the boiler. However, to ensure the
condensate plume does not affect adjacent surfaces a clearance of 300 mm is preferable.
3. These clearances may be reduced to 25 mm without effecting the performance of the boiler. However, to ensure the
condensate plume does not affect adjacent surfaces the terminal can be extended beyond gutters, pipes, eaves,
balconies etc. by upto 500 mm. If the flue is extended more than 500 mm outside, it should be boxed and insulated.
4. To reduce the possibility of nuisance to neighbouring buildings etc. it is recommended the terminal should not be less
than 2500 mm from car parking spaces, building boundary walls, fences etc.
5. A terminal must not be sited under a car port roof.
6. In certain weather conditions the terminal will emit a plume of steam. If possible avoid positioning the terminal where
this may cause a nuisance, i.e. positions A, D, G, H, J or M.
7.
The flue terminal must be exposed to the external air and the position must allow the free passage of air across it at all times.
8. The flue terminal must be positioned where products of combustion will freely disperse and not cause a nuisance.
9. Where a terminal is sited below 2 m from the ground or floor level, the terminal must be protected by a terminal guard.
In these situations, consideration should also be given to prevent nuisance plume and fumes in areas such as access
routes, passageways, patios, balconies etc.
Alpha E-Tec S 20, 30 and 35 - General Boiler Information
A Directly below an opening, air brick, windows, etc.
B Below gutters, soil pipes or drain pipes
C Below eaves
D Below balconies
E From a vertical drain pipe or soil pipe
F From an internal or external corner
G Above ground, roof or balcony level
H From a surface or boundary facing the terminal
I
From a terminal facing the terminal
J Above an opening, air brick, window etc.
K Vertically from a terminal on the same wall
L Horizontally from a terminal on the same wall
M Horizontally from an opening, air brick, window etc.
N Minimum protrusion through a roof
O From a vertical obstruction
P From an openable window
Q From an adjacent vertical terminal
Min. distance (mm)
Terminal position
300
(See Note 1)
75
(See Note 3)
200
(See Note 3)
200
(See Note 3)
150
(See Note 3)
300
(See Note 2)
300
(See Note 9)
600
(See Note 4)
1200 mm
300
(See Note 1)
1500 mm
300 mm
300 mm
(See Note 1)
300 mm
300 mm
600 mm
600 mm
J
D
G
H I
Q
Boundary
O P
N
Fig. 4.3
Summary of Contents for BLADE TWIN PLUS TPWH60
Page 2: ......
Page 6: ...4 Blade 60 80 Twin Plus Water Heater Manual July 2020 3 0 BLADE WATER HEATER SCHEMATIC LAYOUT ...
Page 7: ...Blade 60 80 Twin Plus Water Heater Manual July 2020 5 3 1 SCHEMATIC LEGEND ...
Page 18: ...16 Blade 60 80 Twin Plus Water Heater Manual July 2020 10 0 INSTALLATION SCHEMATIC LAYOUT ...
Page 21: ...Blade 60 80 Twin Plus Water Heater Manual July 2020 19 13 0 WIRING DIAGRAM ...
Page 29: ...Blade 60 80 Twin Plus Water Heater Manual July 2020 27 Notes ...
Page 30: ...APPENDIX A ALPHA BOILER MANUAL ...
Page 89: ...59 Alpha E Tec S 20 30 and 35 Page intentionally Blank ...
Page 99: ...Blade 60 80 Twin Plus Water Heater Manual July 2020 29 APPENDIX B DAB PUMP MANUAL ...
Page 113: ...ENGLISH 41 It is dangerous to touch the circulator DANGER OF SCALDING ...
Page 123: ...ENGLISH 51 18 PERFORMANCE CURVES EVOSTA2 40 70 XXX ...
Page 124: ...ENGLISH 52 EVOSTA2 80 XXX ...
Page 125: ...ENGLISH 53 EVOSTA3 40 XXX ...
Page 126: ...ENGLISH 54 EVOSTA3 60 XXX ...
Page 127: ...ENGLISH 55 EVOSTA3 80 XXX ...