12
RACK MOUNT POWER STRIPS AND SURGE SUPPRESSORS
SP216A (48" Vertical Surge Suppressor Strip), SP217A (70" Vertical Surge
Suppressor Strip), and SP218A (77" Vertical Surge Suppressor Strip)
Compliance —
FCC Class A, DOC Class/MDC classe A, UL listed, CSA certified
Power —
120 VAC
Rated Current —
20 amps (has front-mounted resettable breaker)
Protection —
Surge suppression:
Type: Single-stage;
UL 1449 clamping category: 330 volts peak transient voltage;
Actual clamp voltage: 312 volts peak;
Maximum surge-energy resistance: 13,000 amps;
EMI/RFI resistance: Up to 40 dB
Indicator —
(1) Front-mounted Protection LED (goes dark when unit’s
protection circuitry has absorbed surge and been destroyed)
Input —
(1) 15-ft. (4.6-m) 14/3 (14-AWG, 3-conductor) cord with NEMA 5-15 male
plug
Outlets —
SP216A: (10) Front-mounted NEMA 5-15Rs;
SP217A: (11) Front-mounted NEMA 5-15Rs;
SP218A: (12) Front-mounted NEMA 5-15Rs
Size —
SP216A: 48"L x 1.5"W x 1.2"D (121.9 x 3.8 x 3.1 cm);
SP217A: 70"L x 1.5"W x 1.2"D (177.8 x 3.8 x 3.1 cm);
SP218A: 77"L x 1.5"W x 1.2"D (195.6 x 3.8 x 3.1 cm)
Weight —
SP216A: 5.22 lb. (2.37 kg);
SP217A: 6.3 lb. (2.86 kg);
SP218A: 6.66 lb. (3.02 kg)