background image

6 of 24 

  

Table 3.3.1 – Controller Card Front PC Board Jumper W1 and W2 Settings 
 

Jumper 

W1 

W2 

Gang-In Pin 3 

Connected to TXD * 
Connected to V+ through 1K 

 
Pin 1 to Pin 2 
Pin 2 to Pin 3 

 

Gang-In Pin 4 

Connected to RXD * 
Connected to V- through 1K 

 

 
Pin 1 to Pin 2 
Pin 2 to Pin 3 

 
* Factory Default Setting 
 
The jumpers W1 and W2 function as a pair to configure the gang-in port.  Refer to table 3.2.3 for the GANG-IN port 
pin assignment.  Connect to TXD and RXD to support RS-232 serial communications, or connect to V+ and V- 
through 1 K ohm resistors to control the system control input with a remote toggle switch.  Note that the serial port 
is required for setup of the network parameters. 
 
 
Table 3.3.2 – Controller Card Front PC Board Jumper W4 and W5 Settings 
 

Jumper 

W4 

W5 

Input Port Source 

no Ethernet capabilities 
Ethernet version * 

 
Pin 1 to Pin 2 
Pin 2 to Pin 3 

 

Input Port Source 

no Ethernet capabilities 
Ethernet version * 

 

 
Pin 1 to Pin 2 
Pin 2 to Pin 3 

 
* Factory Default Setting 
 
Jumpers W4 and W5 function as a pair to configure the input port source.  It should not be necessary to change these 
jumpers from their factory set positions.  These jumpers configure the source for communications to the internal 
processor on the Controller Card. 
 
The 8-position dipswitch SW2 on the Controller Card is used to define the Controller Card’s address.  Switch 
position 1 is the least significant bit, and position 8 is the most significant bit.  Set each switch position ON (as 
marked) for a '0', and OFF for a '1'.  Address 1 for example, would be DIP position 1 OFF, and positions 2-8 ON. 
Controller Card addresses may be repeated within the Auto Bypass Switch chassis since each controller card has it’s 
own set of interface connectors and unique IP address. However, the user may find that setting each controller card 
to a unique value helps to eliminate confusion. Address “00” is reserved and must not be used.   
 
 

3.4 TCP/IP and Auto Bypass Configuration 

 
Once the user configurable jumpers and DIP switch settings inside the 2U Auto Bypass Switch are configured, there 
are several parameters related to TCP/IP operations and the auto bypass and auto recovery functions that must be 
initially configured in order to operate the 2U Auto Bypass Switch. These parameters are accessible using either the 
serial RS232 remote control interface or the Ethernet remote control interface. These parameters include: 
 

 

 

IP address, subnet mask, and gateway address for the Ethernet remote control interface on the 2U Auto 
Bypass Switch (this interface also functions as the internal Ethernet node that acts as the “PING source” 
used by the auto bypass and auto recovery switching functions). Note that the default values for these 
parameters are 192.168.1.30, 255.255.255.0, and 192.168.1.1 respectively. 

Summary of Contents for SW1021A

Page 1: ...ber upgrade kit 1 additional path SW1026A SC Fiber upgrade kit 1 additional path 2U AUTO BYPASS SWITCH CUSTOMER SUPPORT INFORMATION Order toll free in the U S 877 877 BBOX outside U S call 724 746 550...

Page 2: ...ecifications Connectors CAT6 RJ45 A B SWITCH CARD 3 CAT6 RJ45 connectors FIBER OPTIC A B SWITCH CARDS 3 Duplex fiber optic SC or 6 ST connectors CONTROLLER CARD 1 RJ45 2 RJ11 POWER CARD 2 two position...

Page 3: ...t in the normal path the auto recovery function can be disabled to allow the intermittent problem to be corrected while the system continues to use the backup path Once the intermittent problem is fix...

Page 4: ...ch is to set the card addresses in each group to 01 and 02 from left to right within the group The Controller Card communicates with the individual switch cards using a multi drop scheme If two A B ca...

Page 5: ...connections to V and V are through 1 K ohm resistors The System Control signal can be used as an input or an output If used an Input this pin should normally be open This input is driven to V to swit...

Page 6: ...ard is used to define the Controller Card s address Switch position 1 is the least significant bit and position 8 is the most significant bit Set each switch position ON as marked for a 0 and OFF for...

Page 7: ...disables the automatic bypass recovery functions Monitor ok count this is the number of successive PING attempts that must succeed before the 2U Auto Bypass Switch automatically switches back to the...

Page 8: ...le on the other side of the switch And since non latching relays are used in the 2U Auto Bypass Switch the A C connection state is typically used for the bypass or failover path connections and the B...

Page 9: ...Switch are in position B 4 5 Before you connect the 2U Auto Bypass Switch s Ethernet remote control port to your Ethernet network you must first configure the 2U Auto Bypass Switch TCP IP related para...

Page 10: ...tch to the failover network if it detects a problem thru the normal path to the device being monitored When the auto recovery switching function is enabled it will cause the 2U Auto Bypass Switch to a...

Page 11: ...ing commands over a serial communications line The parameters of the RS232 console port are fixed at 9600 baud no parity 8 data bits 1 stop and no flow control commonly abbreviated as 9600 N 8 1 NONE...

Page 12: ...for set port 2 a 5 3 Ethernet Switching In order to use the Ethernet NETWORK port you must set the IPADDRESS SUBNETMASK and GATEWAY address of the 2U Auto Bypass Switch before connecting to your netwo...

Page 13: ...te SNMP community names if using SNMP or a web password for browser access These parameters then need to be saved into non volatile memory and the system will then need to be reset to allow it to reco...

Page 14: ...b Password mctech Web Timeout 300 Web Port 80 Telnet Enable Enabled Telnet Password dataman Telnet Timeout 80 Telnet Port 23 Monitor IP Address 207 155 249 112 Monitor MAC Address 00 0C 41 3C 98 54 Mo...

Page 15: ...e current IP address of the network module Any change will not become permanent until a SAVE operation is performed SET SUBNETMASK X X X X GET SUBNETMASK Set or display the current subnet mask of the...

Page 16: ...rent telnet password Note that this is a case sensitive field Any change will not become permanent until a SAVE operation is performed SET TELNETTIMEOUT seconds GET TELNETTIMEOUT Set or display the cu...

Page 17: ...very functions Any change will not become permanent until a SAVE operation is performed SET MONITOROKCOUNT N GET MONITOROKCOUNT Set or display the number of successive PING attempts that must succeed...

Page 18: ...RACK display all ports GET SET PORT N A B control single port GET POWER N GET SET IPADDRESS X X X X GET SET SUBNETMASK X X X X GET SET GATEWAY X X X X GET SET READCOMMUNITYNAME string GET SET WRITECO...

Page 19: ...1 0 Copyright c 2007 All rights reserved ww Command console Enter new command Send Command Logoff Figure 8 2 Initial Command Screen IMPORTANT Do NOT click on the submit button or press the enter key o...

Page 20: ...168 1 150 Monitor MAC Address 00 07 62 71 BB 4D Monitor Interval 15 Monitor Fail Count 5 Monitor Ok Count 5 Read Community Name public Write Community Name private Authentication Trap Disabled 2 9 JU...

Page 21: ...2 abRackIndex 1 3 6 1 4 1 9477 1 4 2 1 1 RackIndex abRackGangPort 1 3 6 1 4 1 9477 1 4 2 1 2 RackIndex abRackKeyStat 1 3 6 1 4 1 9477 1 4 2 1 3 RackIndex abRackPowerStat 1 3 6 1 4 1 9477 1 4 2 1 4 Ra...

Page 22: ...the OFF position The A B Switches will still respond to switch control signals and commands from the GANG IN and GANG OUT ports abRackPowerStat 1 3 6 1 4 1 9477 1 4 2 1 4 RackIndex A B Switch Rack Po...

Page 23: ...n set to B the switch will connect port B to port C If the addressed A B Switch Card is not present you will not get a response abSwitchSoftwareVersion 1 3 6 1 4 1 9477 1 4 3 1 3 SwitchIndex A B Switc...

Page 24: ...24 of 24 Copyright 2007 Black Box Corporation All rights reserved 1000 Park Drive Lawrence PA 15055 1018 724 746 5500 Fax 724 746 0746...

Reviews: