Ventless Hood System
Installation
14
3. If required, connect the provided fire extinguishing system contacts for remote signaling. Refer to
the electrical diagram included in this manual (see page 26).
4. Adjust the position of the two ADP appliance nozzles as depicted below.
5. Install two UL Listed; type “A”, 165
°
F. fusible links (load rating 3-45 lbs.) in the two appliance
detector positions (one in front of the grease baffle, one behind the grease baffle).
FUSIBLE
LINKS