2.7 EXTERNAL OVERRIDE
This feature can be used to prohibit measurements during a vessel filling cycle. The IMS
software will notify the user that a measurement cannot be taken while a filling operation
is in progress. Located on the SmartBob circuit board (just below the RS-485 terminals),
is the terminal block labeled
OVERRIDE
. A connection must exist across these termi-
nals for normal operation of the remote unit, see Figure 6. A contact on an external relay
can be used to disable the remote unit during a fill cycle to prevent burying the Bob. The
use of this feature is optional, if not used, leave the factory installed jumper in the termi-
nal block.
FIGURE 6
2.8 PROTO JUMPER SETTING
The TS1 is capable of operating in two different modes as selected by the PROTO
jumper located on the TS1 circuit board. The desired mode is dependent upon what type
of controlling device the TS1 is operating with and is normally set at the factory in accor-
dance with a particular customer order. PROTO A operates in a polling mode and
PROTO B in a non-polling mode. The PROTO setting and corresponding controlling
devices are listed below.
PROTO A
e-Bob software
SBC-A console
QUCM
MUCM
PROTO B
IMS software
SBC console
RSU console
Coil
Located on PCB
External
Relay
NC
C
OVE
RRI
DE