DPM-200 Digital Panel Meter
Instruction Manual
14
Thermocouple and RTD
Connections
The following figures show examples for
thermocouple and RTD connections.
The RTD/TC selector switch must be set to the proper
position for the meter to accept the selected
temperature input.
The input type is selected using the
Setup
menu.
The selected thermocouple input must correspond to
the thermocouple sensor and wire type used.
Figure 26. Thermocouple Input Connections
Figure 27. Three-Wire RTD Input Connections
The meter accepts two, three, or four-wire RTDs. The
three-wire RTD connection has built-in lead wire
compensation.
Figure 28. Two-Wire RTD Input Connections
Lead wire compensation for two-wire RTDs can be
applied using the
Adjust
menu. See
Figure 29. Four-Wire RTD Input Connections
The four-wire RTD connection is similar to the three-
wire. One of the leads of a four-wire RTD is not
connected and may be clipped off.
The three-wire connection provides sufficient lead
wire compensation to provide accurate readings even
with long leads.