KB 23 / KB 23-UL (E3.1) 02/2019
page 20/87
Normal Display / Fixed value operation
5 seconds
Fixed value entry mode
Program editor
Program start level
5 seconds
Week program editor
Menu visible only if week program
timer is activated in the user level
5 seconds
User level
If no button is touched within more than 120 sec. the controller returns from the current level to Normal
Display.
6.
Fixed value entry mode
If you do not want to use the week program timer, deactivate it (factory setting, setting in the
user level, chap. 10) before entering any set-points. Any setting of the operation lines in Fixed
value entry mode is ineffective with an active week program timer.
Basic entry principle:
Access the individual parameters with button X/W one after the other. Enter the
values with the arrow keys. A value flashing once after 2 seconds indicates that it has been applied by the
controller.
Normal Display
Display 1 shows e.g. 19.8
(actual temperature value)
Display 2 shows e.g. 15.05.06 13:52 - -
(actual date and time)
(actual switching state of week program timer channel 1: Off,
channel 2: Off; visible only if week program timer is activated
in the user level, chap. 10)
Press key
Display 1 shows e.g. 10.0
(actual temperature set-point 1)
Display 2 shows SP1 TEMPERATURE
(variable: temperature in °C)
Enter temperature set-point in °C using
arrow keys
Value is shown in display 1.
Summary of Contents for KB 23
Page 75: ...KB 23 KB 23 UL E3 1 02 2019 page 75 87 20 7 KB KB UL 23 dimensions...
Page 77: ...KB 23 KB 23 UL E3 1 02 2019 page 77 87...
Page 78: ...KB 23 KB 23 UL E3 1 02 2019 page 78 87...
Page 80: ...KB 23 KB 23 UL E3 1 02 2019 page 80 87...
Page 81: ...KB 23 KB 23 UL E3 1 02 2019 page 81 87 22 Product registration...