background image

 

 

 

 

 

 

KB ECO / KB ECO-UL (E6.2) 12/2021 

Page 57/85 

 

20.  Defrosting at refrigerating operation 

BINDER cooling incubators are very diffusion-proof. In favor of the high temperature accuracy, no automatic 

cyclical defrosting device is used. At very low temperatures the moisture in the air can condense on the 

heat sinks leading to icing.  

 

Always close the door properly. 

Operation with temperature set-points above +5 °C / 

41 °F

 at an ambient temperature of 25 °C / 

77 °F

The air defrosts the ice cover automatically. Defrosting is continually performed. 

Operation with temperature set-points below +5 °C / 

41 °F

Icing on the heat sinks is possible. Defrost the chamber manually.  

 

With temperature set-points below +5 °C / 

41 °F

, regularly defrost the chamber manually: 

  Set the temperature to 40 °C / 

104 °F

  Let the chamber operate for about 30 minutes with the door closed. 

 

 

Too much ice on the heat sinks is noticeable by reduced refrigerating performance. 

 
 

21.  Anti-condensation protection 

Depending on the load, for example with a large number of Petri dishes, a lot of moisture can be released 

in the interior of the chamber. One of the Peltier modules ensures that the humidity is limited. With the “Anti-

condensation protection” function, you can adjust the degree of dehumidification in order to reduce con-

densation. 
Path:  

Normal display            Settings            Various       Anti-condensation

 

Press the 

OK button

 to enable the setting.

 

 

 

Setting the anti-condensation protection 
The current setting flashes. Enter the desired intensity of the anti-con-

densation protection with the 

arrow buttons

. Entry range: 0 % up to 

100 %. 
Confirm the entry with the 

OK button

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Anti-condensation

 

With the 

arrow-up button

 you can go back to the temperature tolerance range setting (chap. 13.2). 

With the 

Back button

 you can go back to the “

Various

” submenu and, repeatedly pressing it, to 

Normal 

display

 

Information on the setting 

Factory setting is 40% intensity. This setting is suitable for most applications. 
If a higher level of humidity in the interior leads to condensation, the intensity of the condensation protection 

can be increased, thereby preventing condensation on the door and in the interior. However, this also 

slightly increases the energy consumption. 
The intensity can be reduced for applications with low humidity introduction, which also lowers energy con-

sumption. The most energy-saving setting of 0% is suitable for applications without humidity introduction. 
 

 

Summary of Contents for 9020-0423

Page 1: ...0V 9020 0427 9120 0427 KB ECO 1020 KBECO1020 230V 9020 0425 9120 0425 KB ECO 1020 UL KBECO1020UL 120V 9020 0428 9120 0428 BINDER GmbH Address Post office box 102 78502 Tuttlingen Germany Phone 49 7462...

Page 2: ...Unpacking and checking equipment and completeness of delivery 19 3 2 Guidelines for safe lifting and transportation 19 3 3 Storage 20 3 4 Location of installation and ambient conditions 20 4 INSTALLAT...

Page 3: ...Start time program 44 15 2 Start week program 45 15 3 Stop program 45 16 ETHERNET NETWORK SETTINGS 45 16 1 Showing the network settings 45 16 1 1 Showing the chamber s MAC address 46 16 1 2 Showing th...

Page 4: ...t packing 65 25 2 Decommissioning 65 25 3 Disposal of the chamber in the Federal Republic of Germany 65 25 4 Disposal of the chamber in the member states of the EU except for the Federal Republic of G...

Page 5: ...o significant risks DANGER Dangers due to failure to observe the instructions and safety precautions Serious injuries and chamber damage Risk of death Observe the safety instructions in this Operating...

Page 6: ...and communities of states This includes word marks position marks word figurative marks design configurations figurative marks and design patents Patent Information BINDER products categories of produ...

Page 7: ...atmosphere Stability hazard Lifting hazard Risk of corrosion and or chemical burns Harmful substances Biohazard Pollution Hazard Mandatory action signs Mandatory regulation Read operating instructions...

Page 8: ...disruptions that could result in direct or indirect injury or property damage 1 5 Localization position of safety labels on the chamber The following labels are located on the chamber Pictograms warn...

Page 9: ...mber Project No Optional Special application acc to project no 1 40 kW Nominal power 5 8 A Nominal current 200 230 V 50 Hz Nominal voltage range 10 at the indicated power frequency 208 230 V 60 Hz 1 N...

Page 10: ...ev 2015 07 CAN CSA C22 2 No 61010 1 3rd Edition 2012 05 Rev 2015 07 1 7 General safety instructions on installing and operating the chambers With regard to operating the chambers and to the installati...

Page 11: ...t lie below the flash point or below the sublimation point of the charging material Familiarize yourself with the physical and chemical properties of the charging material as well as the con tained mo...

Page 12: ...or with alternating temperatures e g 37 C 98 6 F and 4 C 39 2 F Requirements for the chamber load Any solvent must not be explosive and flammable A mixture of any component of the charging material w...

Page 13: ...technical requirements e g electrical know how as well as knowledge of the service manual Installation site requirements The chambers are designed for setting up inside a building indoor use The requi...

Page 14: ...ble design features of a chamber as well as its proper field of application can also pose risks even during correct operation These residual risks include hazards which despite the inherently safe de...

Page 15: ...nnel Inappropriate repairs which do not meet the quality standard specified by BINDER Use of replacement parts other than BINDER original replacement parts Electrical safety analysis not performed aft...

Page 16: ...t magnets If persons with active implants e g pacemakers defibrillators keep a safe distance distance of field source to implant of 30 cm an influence of these implants can be excluded with high proba...

Page 17: ...nduction Due to the Peltier cooling shocks are omitted which would occur during start and stop of conventional refrigeration systems with a compressor The chamber is characterized by its low energy co...

Page 18: ...igure 4 Cooling incubator KB ECO KB ECO UL size 240 1 Main power switch 2 Instrument panel with RD4 chamber controller and USB interface 3 USB interfaces 4 Door handle 5 Chamber door 6 Location of Pel...

Page 19: ...e aid of six people or with a fork lifter Set the fork lifter only from the front or rear in the middle of the chamber Lift the chambers sizes 720 and 1020 from the pallet using technical devices fork...

Page 20: ...age of the chamber is possible in a closed and dry room Observe the guidelines for tem porary decommissioning chap 25 2 Permissible ambient temperature range during storage 10 C 14 F to 60 C 140 F Per...

Page 21: ...low ambient temperature high ambient humidity may lead to condensation on the chamber Installation height max 2000 m 6562 ft above sea level Minimum distances When placing several chambers of the same...

Page 22: ...at 25 C there is so little condensate that it will evaporate in the condensate collection pan so that the collection pan does not have to be emptied Under operating conditions with increased condensat...

Page 23: ...ding to the above specification UL chambers Use only a UL Listed Power supply cord UL category ELBZ SJT 3x14 AWG 2 08 mm C13L For outside USA use a certified power supply cord according to national re...

Page 24: ...onnecting supply Check socket before inserting plug 5 Functional overview of the RD4 chamber controller The RD4 chamber controller controls the temperature inside the chamber You can enter the desired...

Page 25: ...n the setting You can set passwords for different access levels User The password enables access to the standard operating functions Factory setting is 00 00 no password assigned Admin The password en...

Page 26: ...ure to the last entered values Warming chambers may release odors in the first few days after commissioning This is not a quality defect To reduce odors quickly we recommend heating up the chamber to...

Page 27: ...to the Setpoints submenu and repeatedly pressing it to Normal display 8 Automatic setpoint switchover Control modes With the setpoint switchover an automatic switchover of the setpoint e g at weekend...

Page 28: ...the der Cyclic control In state of delivery both control modes are deactivated A soon as one of the control is activated setpoint switchover becomes enabled 8 1 Control by date In this menu you can en...

Page 29: ...he right two digits are flashing Enter the last two digits of the desired year with the arrow buttons Confirm the entry with the OK button Date ON With the arrow down button you can change to enter th...

Page 30: ...and deactivated Path Normal display Setpoint switchover Cyclic Press the OK button to enable the setting Active submenu The current setting flashes Select with the arrow buttons between YES cyclic co...

Page 31: ...ress the OK button to enable the setting Setting the time hours The current setting flashes Enter the desired hour and minutes with the arrow buttons and confirm all entries each entry with the OK but...

Page 32: ...are displayed from left to right Example Function 2 Idle mode activated 0100 Function 2 Idle mode deactivated 0000 Submenu Functions on off This view shows the switching states of the four available...

Page 33: ...nction Idle mode Press the OK button to access the first individual function Then press the arrow down button to access the Idle mode function This ist he only adjustable function with the present cha...

Page 34: ...esired numbers with the ar row buttons Confirm the setting with the OK button Password Password request The right two digits are flashing Enter the desired numbers with the ar row buttons Confirm the...

Page 35: ...shing Enter the desired numbers with the arrow buttons Confirm the setting with the OK button Password User With the arrow down button you can now proceed to enter the Admin password With the Back but...

Page 36: ...of an error it limits the temperature inside the chamber to the entered safety controller value This condition state of alarm is indicated visually and additionally with an audible alert if the buzze...

Page 37: ...e must be selected first chap 11 2 1 Depending on the mode setting one of the following setting menus will appear Path Normal display Setpoints Safety controller Limit or Offset Press the OK button to...

Page 38: ...OK button the alarm message Safety controller and the Collective alarm icon are reset together with the buzzer If the state of alarm is still active when pressing the OK button i e the inner chamber...

Page 39: ...tton to enable the setting Setting the menu language example English The current setting flashes Use the arrow buttons to select the de sired language Confirm the entry with the OK button Language Wit...

Page 40: ...rst two digits of the current year with the arrow buttons Confirm the entry with the OK button Date Setting the date year The right two digits are flashing Enter the last two digits of the current yea...

Page 41: ...between ON and OFF Confirm the setting with the OK button Language sel at restar With the arrow down button you can now change to the next parameter chamber address With the Back button you can go ba...

Page 42: ...triggers tolerance alarm In addition you can specify a delay time for this alarm If the actual value is outside the tolerance range after the configured alarm delay time the alarm message Temperature...

Page 43: ...ts and with activated self test function optical and possibly acoustic alarm messages are given out via the con troller In Normal display a text message indicates the alarm cause The collective alarm...

Page 44: ...d stop time or week programs at the RD4 controller The programming itself has to be done using the APT COM 4 Multi Management Software from BINDER chap 22 1 There you can create the programs and trans...

Page 45: ...Normal display Programs Stop program Press the OK button to activate the settings Stop program submenu The current setting flashes Select with the arrow buttons between YES stop program and NO do not...

Page 46: ...thernet IP address Display of the IP address example Toggle forth and back with the Back button and the OK button IP address 0 0 0 0 With the arrow down button you can now change to the next parameter...

Page 47: ...play Chamber info Ethernet DNS server address Display of the DNS server address example Toggle forth and back with the Back button and the OK button DNS server address 0 0 0 0 With the arrow down butt...

Page 48: ...ent setting flashes Use the arrow buttons to select between AUTO automatic and MANU manual Confirm the setting with the OK button IP address assignment With the arrow down button you can now change to...

Page 49: ...he desired value with the arrow buttons Use the OK button to confirm the entry and proceed to the second sec tion of the IP address IP address IP address assignment sample values The second section of...

Page 50: ...ment has been selected chap 16 2 1 Path Normal display Settings Ethernet Standard gateway Press the OK button to enable the setting The standard gateway entry is done in four steps corresponding to th...

Page 51: ...processed in the desired program The data is unencrypted Always the entire data memory is read out 17 1 Recorded data All data is given out in tabular form The headlines of the values number date and...

Page 52: ...K button to enable the setting Function Storage interval The current setting flashes Use the arrow buttons to enter the desired storage interval Setting range 1 minute to 60 minutes Press the OK butto...

Page 53: ...The Service folder is created on the USB stick and can be sent to BINDER Service In addition to the configuration and recorder data it contains further service relevant information 18 1 Connecting th...

Page 54: ...on you can now change to the next function Function Export service data To write the chamber data from the controller to the USB stick press the OK button Export service data 18 4 Ongoing data transfe...

Page 55: ...ion Export recorder data to USB stick chap 18 BINDER Service will evaluate the data using an analyzing tool In order to allow an optimum comparison of the determined characteristic values with the ref...

Page 56: ...play example values Self test completed To delete the alarm message then deactivate the self test function chap 19 2 19 2 Deactivating the self test mode You can deactivate the self test mode via the...

Page 57: ...e Peltier modules ensures that the humidity is limited With the Anti condensation protection function you can adjust the degree of dehumidification in order to reduce con densation Path Normal display...

Page 58: ...ng up to 64000 measuring values Reading out is done with the Data Logger evaluation soft ware You can give out a combined alarm and status protocol directly to a serial printer Data Logger Kit T 220 S...

Page 59: ...suitability of cleaning products please contact BINDER service We recommend using the neutral cleaning agent Art No 1002 0016 for a thorough cleaning Any corrosive damage that may arise following use...

Page 60: ...ou can use the following disinfectants Inner chamber Standard commercial surface disinfectants free from acid or halides Alcohol based solutions We recommend using the disinfectant spray Art No 1002 0...

Page 61: ...her troubleshooting must be performed by BINDER Service or by BINDER qualified service partners or technicians in accordance with the de scription in the Service Manual For personnel requirements plea...

Page 62: ...al times a year We recommend taking out a maintenance agreement Please consult BINDER Service BINDER telephone hotline 49 0 7462 2005 555 BINDER fax hotline 49 0 7462 2005 93555 BINDER e mail hotline...

Page 63: ...ection to power sup ply Check whether the chamber is turned on at the main power switch Wrong voltage Check power supply for correct voltage chap 4 1 Chamber fuse has responded Check chamber fuse and...

Page 64: ...e of alarm If the alarm state continues contact BINDER service Alarm message or or Sensor rupture between sensor and controller or Pt 100 sensor defective Contact BINDER service Short circuit 24 5 Sen...

Page 65: ...of the chamber in the Federal Republic of Germany According to Annex I of Directive 2012 19 EU of the European Parliament and of the Council on waste electrical and electronic equipment WEEE BINDER de...

Page 66: ...rding to national law Fill out the contamination clearance certificate chap 28 and enclose it with the chamber WARNING Danger of intoxication and infection through contamination of the chamber with to...

Page 67: ...ed or residual toxic substances from the chamber Prior to disposal disinfect the chamber from all sources of infection Be aware that sources of infection may also be located outside the inner chamber...

Page 68: ...ver current protection The chambers are equipped with an internal fuse not accessible from outside If this fuse is blown please contact an electronic engineer or BINDER service 26 3 Definition of usab...

Page 69: ...acks max 9 15 15 Maximum load per rack kg lbs 30 66 45 99 45 99 Maximum permitted total load kg lbs 100 220 150 331 150 331 Weight Weight empty kg lbs 152 335 272 600 327 721 Temperature data Temperat...

Page 70: ...s produced in series We reserve the right to change technical specifications at any time If the chamber is fully loaded the specified heating up and cooling down times may vary ac cording to the load...

Page 71: ...0674 8012 0968 Rack lockings 4 pieces 8012 0620 8012 0620 8012 0620 Door gasket silicone kettle 6005 0147 6005 0196 6005 0196 Door gasket silicone outer door 6005 0161 6005 0197 6005 0197 Intermediate...

Page 72: ...KB ECO KB ECO UL E6 2 12 2021 Page 72 85 26 7 Dimensions Dimensions size 240 mm...

Page 73: ...KB ECO KB ECO UL E6 2 12 2021 Page 73 85 Dimensions size 720 mm...

Page 74: ...KB ECO KB ECO UL E6 2 12 2021 Page 74 85 Dimensions size 1020 mm...

Page 75: ...KB ECO KB ECO UL E6 2 12 2021 Page 75 85 27 Certificates and declarations of conformity 27 1 EU Declaration of Conformity...

Page 76: ...KB ECO KB ECO UL E6 2 12 2021 Page 76 85...

Page 77: ...KB ECO KB ECO UL E6 2 12 2021 Page 77 85...

Page 78: ...KB ECO KB ECO UL E6 2 12 2021 Page 78 85 27 2 Certificate for the GS mark of conformity of the Deutsche Gesetzliche Unfallversicherung e V German Social Accident Insurance DGUV...

Page 79: ...KB ECO KB ECO UL E6 2 12 2021 Page 79 85...

Page 80: ...on vorliegt bevor das Ger t Bauteil eintrifft Eine weitere Kopie soll dem Ger t Bauteil beigef gt sein Ggf ist die Spedition zu informieren Incomplete information or non conformity with this procedure...

Page 81: ...zardous substances weder giftige noch sonstige gef hrliche Stoffe enth lt oder solche anhaften That eventually generated reaction products are non toxic and also do not represent a hazard auch evtl en...

Page 82: ...ngaben entsteht haften und BINDER gegen eventuell entste hende Schadenanspr che Dritter freistellen We are aware that in accordance with Article 823 of the German Civil Code BGB we are directly liable...

Page 83: ...at any time Take notice of shipping laws and regulations Please fill Reason for return request Duplicate order Duplicate shipment Demo Page one completed by sales Power Plug Voltage 115V 230 V 208 V...

Page 84: ...______________________________________________________________________ c ____________________________________________________________________________ 3 2 Safety measures required for handling the list...

Page 85: ...nc for all damages that are a con sequence of incomplete or incorrect information provided by us and that we will indemnify and hold harmless BINDER Inc from eventual damage claims by third parties Na...

Reviews: