AS-Interface Analog Module
Operating the Modules
Subject to reasonable modifications due to technical advances
Copyright Bihl+Wiedemann, Printed in Germany
Bihl+Wiedemann GmbH · D-68199 Mannheim · Phone +49-621-339960 · Fax +49-621-3392239 · Internet http://www.bihl-wiedemann.de
is
sue da
te
20
.1
.2
0
0
4
64
AS-Interface parameter bit 3:
Not used
5.3.2.2
Analog Output Modules in IP20, 2 Channels
Parameter settings of AS-Interface analog output modules in IP20 with 2 channels
can be adjusted as follows:
AS-Interface parameter bit 0:
With the parameter bit 0 it can adjusted, if the AS-Interface analog output module
should detect the respective ouput mode automatically or the mode is adjustetd
stationary by the AS-Interface parameter bits P1 respectively P3.
AS-Interface parameter bits 1 and 3: Adjusting the mode for channel 1 and 2
If parameter bit P0 = 0, the mode for channel 1 and 2 can be adjusted stationary
with the help of parameter bits P1 and P3.
AS-Interface parameter bit 2: Display of a peripheral fault
By means of this bit, it is possible to adjust whether an adjacent peripheral fault is
notified by the flashing "FAULT"-LED of the module and the peripheral fault is
transmitted to the AS-Interface master.
5.3.2.3
Analog Output Modules in IP20 and IP65 with M12 Connection, 4 Channelsl
Parameter settings of AS-Interface analog output modules in IP20 and IP65 with
M12 connection and 4 channels can be adjusted as follows:
AS-Interface parameter bit 0: Monitoring of the Profile 7.3
By means of this bit, it is possible to adjust whether the data transmission accor-
ding profile 7.2 is monitored, that means each channel is checked by interruption
P0
selection of the output mode
1
Automatic detection of the module
0
With the parameter bits P1, P3 the mode for channel 1 and 2 can be adju-
sted
P1 channel 1 works as
1
current output
0
voltage output
P3 channel 2 works as
1
current output
0
voltage output
P2 peripheral fault is
1
notified
0
not notified