background image

IS200 Electro-Hydraulic Actuator Positioner 

 

 

Orange Instruments Limited. 

Drwg. No.: 1357-007     Issue : K     Date : 07/10/2013          Page : 

4 of 9 

Iss c - Certificate number added.   Iss D - Ta changed to -20 to +60    
Iss E - Details of fail modes, timers and retrans. O/P added.   Retrans. Signal barrier changed to KFD0-CC-Ex1  
Iss F 

– Details of change in Max/min on & off times + addition of 10R in line with pos o/p –ve 

Iss G 

– Stepping times range change to allow finer adjustment 15/11/2007 

Iss H 

– CE Cert. of Conformity details added, Ta to –40degC, 60079:0,26 mods 25/06/2008 

Iss J 

– Harmonised standards in C of C modified to meet current status 04/08/2008 

Iss K -  Markings changed to meet EN 60079-0:2012 02/10/2103 
ATEX Certified Equipment - Change Authority ATEX Manager ONLY 

Setting the command signal break default operation 

The positioner can be configured to move to a default position or freeze at the current position in the event of the command 
or feedback signal faults.  These faults are characterised as: 
     a) the command falling below 1mA - command signal break 
     b) the potentiometer wiper showing less than 0.25V - potentiometer maximum or wiper break 
     c) the potentiometer wiper showing more than 4.7V - potentiometer minimum break.   
A one-off operation of the positioner will store the choice in non-volatile EEPROM memory. 
 

1.  Hold in the MANUAL pushbutton and apply power to the positioner. 
2.  The MANUAL LED will light continuously and pressing the manual DECREASE and INCREASE pushbuttons will 

cause the appropriate DECREASE and INCREASE LEDS to “toggle” on and off. 

3.  Select the DECREASE LED on for drive downscale on fault,  
4.  Select the INCREASE LED on for drive upscale on fault. 
5.  Leave both LEDs off to select freeze at the current position on fault. 
6.  When satisfied press the MANUAL pushbutton again. 
7.  Remove power from the positioner. 

 

Setting the stepping option timers 

If stepping operation is required, the ON and OFF timers for the open and close solenoids have to be set.  This operation is 
best performed when the actuator hydraulics are isolated but the settings can be trimmed during normal operation of the 
system.   Minimum ON / OFF times 20mS.  Maximum ON / OFF times 11 seconds. 
 

1.  Set DIP switch 3 to ON.   This selects timer setting mode.  Manual mode is selected automatically.           
2.  Set DIP switch 1 to ON.   

Do not select DIP switches 1 and 2 ON together.

   The DECREASE LED will flash and the 

decrease solenoid will operate.   Adjust CAL1 potentiometer to vary the ON time and CAL2 potentiometer to vary the 
off time.   Time the on/off transition over a few cycles to obtain the required result. 

3.  Press the CALIBRATE button to store the decrease step timer values. 
4.  Set DIP switch 1 to OFF. 
5.  Set DIP switch 2 to ON.   

Do not select DIP switches 1 and 2 ON together.

   The INCREASE LED will flash and the 

increase solenoid will operate.   Adjust CAL1 potentiometer to vary the ON time and CAL2 potentiometer to vary the 
off time.   Time the on/off transition over a few cycles to obtain the required result. 

6.  Press the CALIBRATE button to store the increase step timer values. 
7.  Set DIP switch 1 to OFF. 
8.  Set DIP switch 3 to OFF. 
9.  The stepping option can be selected by setting DIL switch 4 ON. 
10.  The above sequence, or part of it, can be selected at any time during normal operation but the actuator will move 

during the adjustment so hydraulic isolation is advised. 

 

First time operation 
 
WARNING !! 
The actuator and associated mechanical equipment connected to it could possibly move in an unpredictable 
manner during initial calibration.  Ensure that all personnel take appropriate precautions.   

 
1.  Ensure that any end of travel limit switches and mechanical stops are correctly adjusted before operation. 
2.  Apply power and provide the 4-20mA command signal.  Press the Auto/Manual Switch.   Check that the Auto/Manual LED 

is lit. 

3.  Operate the Open and Close buttons and confirm that the actuator moves as required.

 

4.  The system must be calibrated before automatic mode is selected.

 

 

Summary of Contents for IS200

Page 1: ...IS200 Intrinsically Safe Actuator Positioner Operation Installation and Maintenance Manual Operation Installation and Maintenance Manual ORM0006 IS200 O M Rev 0...

Page 2: ...co uk Northampton NN3 6XF United Kingdom The IS200 has the following specific approvals Name and Type ACTUATOR POSITIONER TYPE IS200 Certificate Number Baseefa 03ATEX0686X Specific Marking of Explosi...

Page 3: ...t panel of the enclosure Wiring To comply with the IS Certification the IS200 must be wired as shown in the circuit on Page 7 Wiring should be completed by suitably trained personnel taking into accou...

Page 4: ...s required the ON and OFF timers for the open and close solenoids have to be set This operation is best performed when the actuator hydraulics are isolated but the settings can be trimmed during norma...

Page 5: ...sh twice briefly every second 6 Use the INCREASE and DECREASE buttons to set the actuator to the required position for the maximum 20mA command signal As before this can be any position within the mec...

Page 6: ...standards in C of C modified to meet current status 04 08 2008 Iss K Markings changed to meet EN 60079 0 2012 02 10 2103 ATEX Certified Equipment Change Authority ATEX Manager ONLY IS200 dimensions a...

Page 7: ...y Safe barriers before connection to the IS200 See circuits on Page 7 COMMAND SIGNAL INPUT 4 20mA nominal 240R input impedance ANALOGUE POSITION OUTPUT SIGNAL 0 4 9V can be calibrated anywhere in this...

Page 8: ...2 24V dc 7 8 16 15 16V 1 2 24V dc 7 8 3 4 16V 1 2 24V dc 7 8 8 9 4 20mA 1 5 6 4 20mA Command MK35 Li Ex0 2 24V dc 7 8 20 21 0 4 9V 1 9 8 KFD0 CC Ex1 2 18 19 6 7 2 1 13 14 or Fault O P ESD Soln Instume...

Page 9: ...16V Always at supply potential 2 Increase Solenoid ve output 16V Set to 0V to energise solenoid 3 Increase Solenoid Supply ve 16V Must be an isolated IS supply 4 Increase Solenoid Supply 0V 0V 5 No c...

Reviews: