UPSI-1208(D) | UPSI-2406(D)
20 Software
Parameter
adjustable
Value / unit
Description
Load Sensor
100mA…800mA
in steps of mA
A shortfall of this current value leads to the assumption that
the connected system is shut down. Thereupon the system
will be separated for x seconds (restart delay) for running
the reboot function, in case input voltage has returned.
Shutdown
System after
1s…3600 s
in steps of seconds
Concerns the hold-up time: During this time, the supply of
the system is maintained. After this time has expired and
the input supply is still missing, the shutdown process of
the PC gets started. If the voltage returns at the grid side
within this time there will be no action.
Maximum
Backup Time
1s…3600 s
in steps of seconds
The maximum hold-up time. After this time the application
will be disconnected. This setting can be used for systems
which do not need a shut down process or in case the
application hangs up and has to be disconnected abruptly.
Need capacity
before power up
1%...100%
in steps of 1%
Minimum capacity for release of UPS. Hereby can be
secured that the application can safely be powered at a
power fail. As a result, the switch-on time can be delayed.
Ignition Timer
1s…3600 s
in steps of seconds
A second signal (X10 Pin 6=V+ auf Pin3=GND) is evalu-
ated. If it shows „high“ (>3,8 V, 29 V max) this time is used
instead of shutdown time to shut down the system. This
setting can be used to adjust an alternative time than the
„Shutdown System After“ setting. If a „high“ signal is present
the time of „Shutdown System After“ is ignored and the
„Ignition Timer“ time is used to delay the shut down
process.
Restart Delay
1s…180 s
in steps of seconds
Time delay after disconnecting the application for a re-
newed activation of the upstream supply. If the upstream
supply returns while or afterwards the shutdown process,
the application will be restarted via the output voltage of
the UPS.