53
English
UPSI-1208(D) | UPSI-2406(D)
11 Connecting diagram UPSI-1208D / UPSI-2406D
CONNECTING ORDER
1.
BAT DATA
2.
BAT PWR
3.
APPLICATION
4.
V
IN
5.
RELAY / USB / RS232
PLEASE NOTE!
The correct connecting order must be strictly followed.
When changing the battery
packs while the system is running
(hot swapping),
a period of at least
6 seconds
must
elapse between disconnecting and re-connecting a battery pack.
ENERGY STORAGE
+
+
–
–
V
IN
4 (LiFePO4) or 5 (EDLC) BAT DATA
4 BAT PWR
USB
RS232 for individual use
2 RELAY
APPLICATION
OR