66
English
UPSI-1208(D) | UPSI-2406(D)
GetOutputVoltage() 0x27
This read-word function returns the measured output voltage of the UPS.
Cmd
Name
Access
Type
Min.
Max
Unit
0x27
GetOutputVoltage()
R
Int16
0
32768
mV
Transfer packet: 0x01 0x03 0x03 0x27 0x04
GetInputCurrent() 0x28
This read-word function returns the measured input current of the UPS.
Cmd
Name
Access
Type
Min.
Max
Unit
0x28
GetInputCurrent ()
R
Int16
0
32768
mA
Transfer packet: 0x01 0x03 0x03 0x28 0x04
GetChargeCurrent() 0x29
This read-word function returns the measured charge current of the UPS.
Cmd
Name
Access
Type
Min.
Max
Unit
0x29
GetChargeCurrent ()
R
Int16
-32768
32768
mA
Transfer packet: 0x01 0x03 0x03 0x29 0x04
22.4 Command Index “Battery A” and “Battery B” 0x04 / 0x05
GetBatteryTemperature() 0x08
This read-word function returns the measured temperature.
Cmd
Name
Access
Type
Min. Max Unit
0x08
GetBatteryTemperature()
R
Uint16
0
65535 0.1°K
Transfer packet: 0x01 0x03 0x04 0x08 0x04
GetBatteryVoltage() 0x09
This read-word function returns the sum of measured cell voltages.
Cmd
Name
Access
Type
Min. Max Unit
0x09
GetBatteryVoltage()
R
Uint16
0
65535 mV
Transfer packet: 0x01 0x03 0x04 0x09 0x04