15.6 Checking the burner ignition:
•
Turn the boiler OFF.
•
Open the gas valve outlet
pressure test point 15
(figure 15.5) and connect
the gauge.
•
Turn
the
boiler
ON
positioning the function
selector B in the position
shown in figure 15.7 and
ensure
that
the
room
thermostat is set to “heat
demand”.
B
Figure 15.7
•
Loosen screws D and
remove the service panel
(figure 15.8).
D
D
D
Figure 15.8
•
Watch the gauge and
check to see if the ignition
pressure
registerd
corresponds to the values
given in the Technical
Data. Turn off the boiler
and reignite it by turning
the function selector B to
the 0 position and then
back to that indicated in
figure 15.7.
•
Repeat this process two to
three times leaving 30
second intervals between
each ignition. Check the
ignition
pressures
and
visually check that the
burner lights uniformly and
in a controlled manner.
•
To
carry
out
the
adjustment
move
the
function selector 3 to the
OFF position (Fig. 15.9)
and use the device (ACC).
2
3
4
OFF
ON
1
ACC
RISC
+
+
Figure 15.9
•
Adjust the gas pressure at
the injectors to the value
indicated in the tables of
section 2. By rotating the
device
clockwise
the
pressure increases.
•
After
the
adjustment
operations
bring
the
selector 3 of figure 15.9
back to the normal position
(ON).
•
Reassemble the service
panel.
•
Close the gas valve outlet
pressure test point 15
(figure 15.5).
•
Reassemble
the
front
pannel of the case.
Important:
after
the
checks all of the test
points must be sealed.
15.7 Adjustment of the useful c.h. output:
•
Turn the boiler OFF.
•
Open the gas valve outlet
pressure test point 15
(figure 15.5) and connect
the gauge.
•
Turn
the
boiler
ON
positioning the function
selector B in the position
shown in figure 15.7 and
ensure
that
the
room
thermostat is set to “heat
demand”.
•
Loosen screws D and
remove the service panel
(figure 15.8).
•
To
carry
out
the
adjustment
use
the
adjustment device (RISC)
with
the
help
of
a
screwdriver.
•
By rotating the device
clockwise
the
pressure
increases.
•
Adjust the gas pressure at
the burner to the value
according to the useful c.h.
output wanted (Tab. 15.1).
•
Reassemble the service
panel.
•
Close the gas valve outlet
pressure test point 15
(figure 15.5).
•
Reassemble
the
front
pannel of the case.
15. Commissioning Cont.