![Biasi Riva ADVANCE SV Owner'S Manual Download Page 8](http://html1.mh-extra.com/html/biasi/riva-advance-sv/riva-advance-sv_owners-manual_2748966008.webp)
8 RIVA ADVANCE USER MANUAL
2. Technical Information Cont.
ENERGY CAPACITY
Nominal heat input
(0/2000 ft)
MBH
1
25
.0
Nominal heat input
(2000/4500 ft)
MBH
1
12.5
Minimum heat input
MBH
32
.0
Maximum useful output
(0/2000 ft)
MBH
1
1
2.
5
Maximum useful output
(2000/4500 ft)
MBH
10
7.2
Minimum useful output
MBH
28.8
GAS PRESSURE AT BURNER
Gas
Min
Max
Ignition
Natural
inwc
6.8
10.0
7
.0
Propane
inwc
10.0
1
3
.0
1
1
.0
FLUE DESIGN
Minimum Venturi pressure
inwc
0.64
Flue pipe diameter
Coaxial
in
2.25/4
3.25/5
Twin split pipes
in
3.25/3.25
Nominal heat flow rate
(0/2000 ft)
MBH
1
25
.0
Nominal heat flow rate
(2000/4500 ft)
MBH
11
2.5
Max Exhaust temperature
°F
190
GAS FLOW RATE
Gas
Min
Max
Natural
ft³/h
31.0
1
21
.1
Propane
lb/h
1.5
5.
7
CLEARANCE TO COMBUSTIBLES
Front
in
18
Back
in
0
Top
in
10
Sides
in
2
Bottom
in
8
Flue pipe enclosed
in
2
Flue pipe free air
in
0
Hot water pipes
in
1”
FLUE GAS FIGURES
(at nominal heat input)
Gas
Min
Max
CO
2
content with Natural gas
8.8
%
9.8%
CO
2
content with Propane gas
9.6
% 11.0%
O
2
content
4.3%
5.0%
FLUE GAS FIGURES
(at minimum heat input)
Gas
Min
Max
CO
2
content with Natural gas
8.8
%
9.8%
CO
2
content with Propane gas
9.6
% 11.0%
O
2
content
4.3%
5.0%