- 66 -
INST
ALLA
TION
COMMISSIONING
If after four ignition attempts (about four min-
utes) the boiler does not function and a code
that precedes the letter
E
and the writing
RE-
SET
appear on the LCD display, it indicates
that the safety lock-out has stopped the boiler.
The display background flashes (Fig. 7.10).
Fig. 7.10
Press the reset key on the boiler control panel
15 (Fig. 7.8) to reset its functioning.
For the first lighting up and following mainte-
nance procedures for the gas supply, it may
be necessary to repeat the resetting operation
several times so as to remove the air present
in the pipework.
After five consecutive resetting attempts the
reset button is inhibited. To restore its func-
tion it is necessary to switch the boiler off and
on from the electrical mains, using the fused
spur isolation switch fitted adjacent to the ap-
pliance.
7.10 Enabling functioning of the
external temperature probe by
the remote control
Functioning with the external probe in the
boiler must be enabled if the remote control
(optional) is used.
Act on the programming of the REMOTE con-
trol to enable its functioning if the remote con-
trol (optional) is used.
• Press button for more than 3 seconds to
enter in
mode.
Fig. 7.11
0
2
1
8
1
21
1 5
6
3
9
Press buttons
and
at the same time
to enter the transparent programming (Fig.
7.12).
Fig. 7.12
• Press buttons
or
to display the
"PM15"
program that enables the external
probe (Fig. 7.13).
Fig. 7.13
• Modify the programmed SET by acting on
buttons
or
until
a setting of 60
is