
- 27 -
USE
USEFUL ADVICE
so that the causes can be understood.
In order to access the INFO mode, press
key 16 (Fig. 3.6) the index
J00
and the val-
ue of the parameter appear on the display
(Fig. 3.7).
Fig. 3.6
11
12
13
14 15
16
17
18
19
Fig. 3.7
To scroll the values press 17 (reduce) and
18 (increase) keys. In order to exit the
INFO mode, hold keys 14 and 18 (Fig. 3.6)
pressed at the same time.
The table summarises the possible values
visible in INFO mode.
Value visualised
Index
Primary circuit pressure
J00 + value
External temperature
J01 + value
K curve value configured
in loco
J02 + value
Offset climatic curve value J03 + value
Calculated heating set
point (with climatic curve
or set configured)
J04 + value
Temperature NTC delivery J05 + value
Temperature NTC return
J06 + value
Domestic set
J07 + value
Temp. d.h.w. inlet (if
foreseen)
J08 + value
Temp. d.h.w. output
J09 + value
D.h.w. capacity
J10 + value
Flue
temperature
(if
foreseen)
J11 + value
Fan speed (if foreseen)
J12 + value
Pressure transducer
pressure (if foreseen)
J13 + value
Ionization value
J14 + value
Number of months to
maintenance
J15 + value
3 star status
(ON=01, OFF=00)
J16 + value
HWCH Hardware code
high
J17 + value
HWCL Hardware code low J18 + value
SWCH Software code high J19 + value
SWCL Software code low
J20 + value
Summary of Contents for Inovia 25C
Page 90: ...90 NOTES...
Page 91: ......