- 67 -
INST
ALLA
TION
ADVANCED COMMISSIONING
the 17 and 18 keys simultaneously for 5
seconds (Fig. 8.25) until the code
P00
ap
-
pears on the display, indicating entry into
“parameter P00” (Fig. 8.26).
Fig. 8.25
12
13
14
15
16
17
18
Fig. 8.26
bar
RESET
•
Scroll through the various menus by
pressing the keys 12 (back) or 13 (for
-
ward), until the LCD display shows the
code
P05
, indicating entry into “parameter
P05” (Fig. 8.27).
Fig. 8.27
bar
RESET
•
Press the keys 16, until the value of pa
-
rameter P05 on the LCD display (Fig.
8.28).
Fig. 8.28
bar
RESET
•
It is possible to modify the value of param
-
eter
05
from
0
to
255
minutes by pressing
the 15 or 16 keys.
•
Press 12 or 13 (Fig. 8.21) to confirm the
value entered and return to the list of pa
-
rameters (Fig. 8.23).
•
Press the 17 button (Fig. 8.21) to exit “pro
-
gramming mode”.
8.8 Factory reset
The RESET returns all parame-
ters to the factory settings.
•
Enter “programming mode” by following
the steps described in the section "Access
parameters for installer" on page 61.
Fig. 8.29
12
13
14
15
16
17
18
•
Press 12 and hold until the LCD display
shows the code
A49
, indicating entry into
“parameter A49” (Fig. 8.30).