• Seven emergency messages - using a combination of multiple audio file elements, these seven messages can be

used to direct staff and passengers to the correct area for whichever emergency zone they're currently located. The
'Upper Level' messages comprise of 5 elements - an Alarm tone, an audio file 'alarm active', another audio file
'please proceed to the' then an audio file dependent on location directing passengers to the left or right stairs, then
a final audio file instructing further directions will be given once the lower deck has been reached. Once the person
reaches the lower deck, emergency messages will provide direction to the closest assembly point for that location.

• All amplifiers in the system are emergency capable. All have emergency Zone assignments in addition to non-

emergency Zone assignments.

• The LSI-16e is used to switch system the system from non-emergency to emergency mode in the event of a fire or

other critical event. The EWS-10 paging stations allow for live paging while the system is operating in emergency
mode.

• The message processor (MS-1e) is used for hosting non-emergency recorded messages and scheduled

announcements of daily activities.

External connections to the system

Fire panel connection to the LSI-16e

The functionality of the LSI-16e has been tailored to the specific requirements in the EN 54-16 European life safety
standard. However, the LSI-16e and CI-1 are still applicable in installations that require highly reliable and fault-tolerant
systems with voice evacuation functionality, even if there is no need to meet EN 54-16 standards. Some notifications are
specific to EN 54-16, for example, General Fault, General Alarm, Protection Fault, etc and may not be applicable for
your jurisdiction. More information on Alarms and Faults can be found

here

. In this application using the CI-1 facilitates

connectivity to the Fire/Evacuation System (CIE) allowing bi-directional control and monitoring. Extra contact closure
inputs on the LSI-16e are being used for scheduled fire drills and system testing in Areas 1 - 4 on the lower deck.

Setup requirements:

• Links between LSI-16e Life Safety Interface and CI-1 Control Interface with supplied jumpers. A detailed setup

guide can be found

here

Copyright 2013-2020 Biamp Systems

http://support.biamp.com/

5

Summary of Contents for Vocia ANC-1

Page 1: ...gency it s critical structured clear to follow evacuation directions are given Vocia is capable of meeting and exceeding that requirement Paging system design Paging System Functionality Scope 7 Paging Stations to provide live pages from the Bar Bridge Casino Pool Restaurant Security and Theater 2 Emergency Paging Stations to provide live paging from the Bridge Helm and Security room 10 Regular Pa...

Page 2: ...djustments in response to changes in ambient noise levels PoE CobraNet audio control Enhanced emergency interface between the Vocia paging system and the emergency fire alarm systems Control interface for LSI 16e Message Processor for recorded announcements scheduling Speaker line monitoring device for Vocia Amplifiers VA 8600 Speaker line monitoring device for Vocia Amplifiers VA 8150CV and VA 43...

Page 3: ...ovide a better understanding on the most essential settings inside the software the Zones and Page Code assignment can be previewed below Zones Configuration Pages Codes Emerge Emergency Messages Amplifier Zone Assignment Lower Deck VA 4300CV LSI 16 Em Copyright 2013 2020 Biamp Systems http support biamp com 3 ...

Page 4: ...ecreases as guests move between different areas ANC 1 s have been installed in the restaurant and casino to automatically adjust BGM and paging levels to account for this Zone assignment ten Zones one for each main section of the ship during non emergency operation Additional two paging Zones to all of the upper deck and all of lower deck available Emergency Zone assignment Upon detection of an al...

Page 5: ... The message processor MS 1e is used for hosting non emergency recorded messages and scheduled announcements of daily activities External connections to the system Fire panel connection to the LSI 16e The functionality of the LSI 16e has been tailored to the specific requirements in the EN 54 16 European life safety standard However the LSI 16e and CI 1 are still applicable in installations that r...

Page 6: ... but leaves the system in emergency mode Physical Input 16 returns the system to regular non emergency mode Please refer to the picture on the right or review the full LSI 16e connection documentation here Speaker lines Speaker circuits are being installed as constant voltage speaker lines 70V or 100V can be selected via software In this example all speaker circuits are 70V Select speaker transfor...

Page 7: ...efault to unity gain This allows the system to start working once the file is loaded with minimal adjustments Select the output voltage on the amplifiers to 70V or 100V as needed Adjust the amplifier output level as needed for each zone While at the amplifier s properties go to ELD Assignment tab and assign PLD s if being used Adjust ambient sense microphones input levels and values Check and conf...

Page 8: ...Further reading Vocia Network Communications CI 1 Wiring Guide LSI 16 setup and wiring guide Constant voltage speaker systems Copyright 2013 2020 Biamp Systems http support biamp com 8 ...

Reviews: