7
Switch Choice:
1.Microstepping choice:
SW 6
off
on
off
on
on
SW 7
off
off
on
on
on
SW 8
off
off
off
off
on
Micro
200
400
800
1600
3200
2.Current choice
::::
SW 1
off
on
off
on
off
on
off
on
off
on
off
on
off
SW 2
off
off
on
on
off
off
on
on
off
off
on
on
off
SW 3
off
off
off
off
on
on
on
on
off
off
off
off
on
SW 4
off
off
off
off
off
off
off
off
on
on
on
on
on
Current
(A)
0.25
0.4
0.5
0.6
0.75
0.85
1
1.2
1.33
1.5
1.7
1.8
2
Note:-Any DIP Switch Setting other than above
Current:-The 0.25 A current will be set.
Microstep:-3200 microstep will be set.
4.Sequence Chart of Control Signals
In order to avoid some fault operations and deviations, PUL, DIR and ENA should abide by some
rules, shown as following diagram
:
NOTE
: Enable signal is always high in this drive. Any external supply of 5 Vdc applied will disable the
Drive.
Remark:
a)
t1 :ENA must be ahead of DIR by at least 5uS. ENA signal is necessary to be driven High in case
Direction is needed to be changed.
Sequence for changing the direction as follows:-
1) User must drive ENA signal high,wait for 5
µ
s
2) Change DIR signal as per need,wait for 5
µ
s
3) Drive ENA signal low
b)
t2: DIR must be ahead of PUL effective edge by 5
µ
s to ensure correct direction;
c)
t3: Pulse width not less than 1.5
µ
s;
d)
t4: Low level width not less than 1.5
µ
s.