background image

INSTALLATION MANUAL

ORO - Ver.  03 - 

9

INSTALLATION MANUAL

ENGLISH

WARNING!

 All versions are provided with a ball joint which allows the rod

to be lengthened or shortened by approximately 5mm, but only if it was fixed

using the dimensions shown in fig.8 before installation after installation, this

adjustment allows the rod stroke to be corrected.

Fig.9 illustrates the oscillation that the controllers may show with respect to

their horizontal axis.

During installation, carefully follow all the phases described below, taking

care to protect the actuator’s chromium-plated rod at all times, in order to

prevent it from being damaged by impact or any welding slag.

1) Identify “a - b - 

α

°

 ” in the table in fig. 3.

2) Fix bracket “P” (fig.10) to the pillar.

3) Fit the piston in bracket “P”.

4) Make sure that the rod eye is adjusted see fig 8.

5) Pull  the  rod  out  completely  after  activating  the  emergency  release

(fig.18)

6) Push the rod back in manually until you position the eye hole with the

hole of the template (fig.22).

7) Fit fork “F” (fig.8) to the rod.

8) Fully close the gate leaf against the centre stop plate.

9) Keeping the piston level, mark the position for attaching fork (fig. 10 ref.

“F”) to the leaf.

10) Remove fork “F” from the rod and move the piston sideways.

11) Fix fork (fig.10 ref. “F”) to the leaf by means of screws or welding.

12) Reconnect the rod to fork “F” remove bleed screw “S” (Fig.17) and

supply the actuator with power.

13) Make some full cycles.

14) In  the  case  when  you  have  to  adjust  the  opening  angle,  do  so  by

adjusting the ball joint see fig.8.

15) After  adjustment  proceed  as  follows  in  order  to  secure  piston  into

mounting bracket: clean piston cover and secure with fastener, insert

mounting pin and tighten lock nut with open end wrench as shown in

Fig.8A.

5.4) Suggestions for particular installations

Fig.5 A recess must be made to house the controller when the leaf is

completely open; the recess measurements are shown in fig.5.

Fig.7 When the ”b” dimension is greater than the values shown in the

installation tables, it is necessary to move the leaf hinge-pivot or

make a recess in the pillar, as in fig.6.

5.5) Anchoring of attachments to the pillar

Weld or fix the bracket base supplied to the pillar, check the “a” and “b”

measurements and then weld plate “P” to the said base. (fig. 10).

• If the pillar is made of masonry, plate “P” must be welded to the metal

base “PF” and deeply anchored by means of suitable hooks “Z” which are

to be welded on the back of the said base (fig. 11a).

• If the pillar is made of stone, plate “P” is welded to the metal base “PF”

and can be fixed by means of four metal screw anchors “T” (fig. 11b); if

the gate is large, it is advisable to weld plate “P” to an angle-shaped base

(fig. 11c).

5.6) Anchoring of attachments to the leaf

Weld or fix fork “F” to the leaf at distance between centres “C” shown in fig.4,

making sure that the actuator is perfectly level (level “L”, fig. 10) with respect

to the gate movement plane.

• If the gate is made of metal, the fork can be welded (fig. 12a) or fixed

using appropriate screws (fig. 12c).

• If the gate is made of wood, the fork can be fixed using appropriate

screws (fig. 12b).

6) GROUND LEAF STOP PLATES

For the actuator to operate correctly, stop plates “FA” must be used during

both opening and closing manoeuvres, as shown in fig. 13.

The leaf stop plates must prevent the actuator rod from going to the end-

of- stroke position. Fig.14 specifies the dimensions needed to check the

correct actuator installation both for pushing and towing. The plates must

be  positioned  in  such  a  way  as  to  maintain  a  rod  stroke  margin  of

approximately 5mm; this is to avoid possible operation anomalies (such as

a lock-up).

7) ELECTRIC LOCK FITTING

This is needed on mod. 

ORO/E

 only since these are not supplied with a

hydraulic lock on closing.

The 

EBP

  model  electric  lock  (fig.15)  consists  of  a  continuous  service

electromagnet being anchored to the ground.

This device remains energized throughout the actuator operation time, and

allows the catch to stay lifted when it reaches the closing position, without

opposing any resistance; the catch will drop into position when the gate has

completed the closing cycle.

The electric lock can also be used to keep the block of the gate in case of

actuator malfunction or current failure.

8) ELECTRICAL INSTALLATION SET-UP

Lay out the electrical installation (fig. 16) with reference to the CEI 64-8 and

IEC 364 provisions, complying with the HD 384 and other national standards

in force for electrical installation. The mains power supply connections must

be kept totally separate from the service connections (photocells, electric

edges, control devices etc.).

WARNING! For connection to the mains, use a multipolar cable with

a minimum of 3x1.5mm

2

 cross section and complying with the

previously mentioned regulations. For example, if the cable is out side

(in the open), it has to be at least equal to H07RN-F, but if it is on the

inside (or outside  but placed in a  plastic cable cannel) it has to be or

at least egual to H05VV-F with section 3x1.5mm

2

.

Connect the control and safety devices in compliance with the previously

mentioned electrical installation standards.

Fig.16 shows the number of connections and the cross section for power

supply cables having a length of approximately 100 metres; in case of

longer cables, calculate the cross section for the true automation load.

When the auxiliary connections exceed 50-metre lengths or go through

critical disturbance areas, it is recommended to decouple the control and

safety devices by means of suitable relays.

8.1) The main automation components are

 (fig.16):

I

Type-approved  omnipolar  circuit  breaker  with  at  least  3mm  contact

opening,  provided  with  protection  against  overloads  and  short  circuits,

suitable for cutting out automation from the mains. If not already installed,

place  a  type-approved  differential  switch  with  a  0.03A  threshold  in  the

circuit just before the automation system.

Qr

Control panel and incorporated receiver.

SPL

Preheating board for operation with temperature lower than 5

°

C

(optional).

S

Key selector.

AL

Blinker with tuned antenna and RG58 cable.

M

Actuator.

E

Electric lock.

Fte

Pair of external photocells (transmitter).

Fre

Pair of external photocells (receiver).

Fti

Pair of internal photocells with CF posts.

Fri

Pair of internal photocells with CF posts (receiver).

T

1-2-4 channel transmitter.

IMPORTANT

:  Before  electrically  activating  the  actuator,  remove  bleed

screw “S” (fig. 17) which is positioned under the base with articulated joint

and keep it for any later reuse. Only remove bleed screw “S” when the

actuator is installed.

9) MANUAL OPENING

In emergency case, such as in the case of power cut-out, to release the

gate, insert the same key C used for the adjustment of the by-pass valve

inside the triangular pin (Fig.18) and rotate it counterclockwise.

The gate  can now be opened manually.

WARNING! make sure that you manually push the gate open at the

same speed as the motor would have.

To reset the electric  operation of the actuator, turn the key in clockwise

direction until pin is blocked.

9.1) Mod. ORO

In case of emergency, for example when the electrical power is disconnected,

to release the gate, insert the same key C used for the adjustment of the by-

pass valve inside the triangular pin (Fig.18) and rotate it counterclockwise.

The gate can now be opened manually. To reset the electric operation of

the actuator, turn the key in clockwise direction until pin is blocked.

9.2) Mod. ORO/E

Since these models are reversible, for the manual operation of the gate it

is sufficient that the electric lock be opened with the appropriate key. To

make the manual manoeuvre easier, the lock can be released by means of

a triangular pin which can be reached using the appropriate key.

10) PUSHING FORCE ADJUSTMENT

The pushing force is adjusted by two valves marked with the writing “

Close

and “

Open

” respectively, which are used to adjust the closing and opening

pushing force (fig.19).

Lift open the lid indicated in (Fig.19) there you will find the two valves.

ORO - Ver.  03 - 

9

INSTALLATION MANUAL

ENGLISH

WARNING!

 All versions are provided with a ball joint which allows the rod

to be lengthened or shortened by approximately 5mm, but only if it was fixed

using the dimensions shown in fig.8 before installation after installation, this

adjustment allows the rod stroke to be corrected.

Fig.9 illustrates the oscillation that the controllers may show with respect to

their horizontal axis.

During installation, carefully follow all the phases described below, taking

care to protect the actuator’s chromium-plated rod at all times, in order to

prevent it from being damaged by impact or any welding slag.

1) Identify “a - b - 

α

°

 ” in the table in fig. 3.

2) Fix bracket “P” (fig.10) to the pillar.

3) Fit the piston in bracket “P”.

4) Make sure that the rod eye is adjusted see fig 8.

5) Pull  the  rod  out  completely  after  activating  the  emergency  release

(fig.18)

6) Push the rod back in manually until you position the eye hole with the

hole of the template (fig.22).

7) Fit fork “F” (fig.8) to the rod.

8) Fully close the gate leaf against the centre stop plate.

9) Keeping the piston level, mark the position for attaching fork (fig. 10 ref.

“F”) to the leaf.

10) Remove fork “F” from the rod and move the piston sideways.

11) Fix fork (fig.10 ref. “F”) to the leaf by means of screws or welding.

12) Reconnect the rod to fork “F” remove bleed screw “S” (Fig.17) and

supply the actuator with power.

13) Make some full cycles.

14) In  the  case  when  you  have  to  adjust  the  opening  angle,  do  so  by

adjusting the ball joint see fig.8.

15) After  adjustment  proceed  as  follows  in  order  to  secure  piston  into

mounting bracket: clean piston cover and secure with fastener, insert

mounting pin and tighten lock nut with open end wrench as shown in

Fig.8A.

5.4) Suggestions for particular installations

Fig.5 A recess must be made to house the controller when the leaf is

completely open; the recess measurements are shown in fig.5.

Fig.7 When the ”b” dimension is greater than the values shown in the

installation tables, it is necessary to move the leaf hinge-pivot or

make a recess in the pillar, as in fig.6.

5.5) Anchoring of attachments to the pillar

Weld or fix the bracket base supplied to the pillar, check the “a” and “b”

measurements and then weld plate “P” to the said base. (fig. 10).

• If the pillar is made of masonry, plate “P” must be welded to the metal

base “PF” and deeply anchored by means of suitable hooks “Z” which are

to be welded on the back of the said base (fig. 11a).

• If the pillar is made of stone, plate “P” is welded to the metal base “PF”

and can be fixed by means of four metal screw anchors “T” (fig. 11b); if

the gate is large, it is advisable to weld plate “P” to an angle-shaped base

(fig. 11c).

5.6) Anchoring of attachments to the leaf

Weld or fix fork “F” to the leaf at distance between centres “C” shown in fig.4,

making sure that the actuator is perfectly level (level “L”, fig. 10) with respect

to the gate movement plane.

• If the gate is made of metal, the fork can be welded (fig. 12a) or fixed

using appropriate screws (fig. 12c).

• If the gate is made of wood, the fork can be fixed using appropriate

screws (fig. 12b).

6) GROUND LEAF STOP PLATES

For the actuator to operate correctly, stop plates “FA” must be used during

both opening and closing manoeuvres, as shown in fig. 13.

The leaf stop plates must prevent the actuator rod from going to the end-

of- stroke position. Fig.14 specifies the dimensions needed to check the

correct actuator installation both for pushing and towing. The plates must

be  positioned  in  such  a  way  as  to  maintain  a  rod  stroke  margin  of

approximately 5mm; this is to avoid possible operation anomalies (such as

a lock-up).

7) ELECTRIC LOCK FITTING

This is needed on mod. 

ORO/E

 only since these are not supplied with a

hydraulic lock on closing.

The 

EBP

  model  electric  lock  (fig.15)  consists  of  a  continuous  service

electromagnet being anchored to the ground.

This device remains energized throughout the actuator operation time, and

allows the catch to stay lifted when it reaches the closing position, without

opposing any resistance; the catch will drop into position when the gate has

completed the closing cycle.

The electric lock can also be used to keep the block of the gate in case of

actuator malfunction or current failure.

8) ELECTRICAL INSTALLATION SET-UP

Lay out the electrical installation (fig. 16) with reference to the CEI 64-8 and

IEC 364 provisions, complying with the HD 384 and other national standards

in force for electrical installation. The mains power supply connections must

be kept totally separate from the service connections (photocells, electric

edges, control devices etc.).

WARNING! For connection to the mains, use a multipolar cable with

a minimum of 3x1.5mm

2

 cross section and complying with the

previously mentioned regulations. For example, if the cable is out side

(in the open), it has to be at least equal to H07RN-F, but if it is on the

inside (or outside  but placed in a  plastic cable cannel) it has to be or

at least egual to H05VV-F with section 3x1.5mm

2

.

Connect the control and safety devices in compliance with the previously

mentioned electrical installation standards.

Fig.16 shows the number of connections and the cross section for power

supply cables having a length of approximately 100 metres; in case of

longer cables, calculate the cross section for the true automation load.

When the auxiliary connections exceed 50-metre lengths or go through

critical disturbance areas, it is recommended to decouple the control and

safety devices by means of suitable relays.

8.1) The main automation components are

 (fig.16):

I

Type-approved  omnipolar  circuit  breaker  with  at  least  3mm  contact

opening,  provided  with  protection  against  overloads  and  short  circuits,

suitable for cutting out automation from the mains. If not already installed,

place  a  type-approved  differential  switch  with  a  0.03A  threshold  in  the

circuit just before the automation system.

Qr

Control panel and incorporated receiver.

SPL

Preheating board for operation with temperature lower than 5

°

C

(optional).

S

Key selector.

AL

Blinker with tuned antenna and RG58 cable.

M

Actuator.

E

Electric lock.

Fte

Pair of external photocells (transmitter).

Fre

Pair of external photocells (receiver).

Fti

Pair of internal photocells with CF posts.

Fri

Pair of internal photocells with CF posts (receiver).

T

1-2-4 channel transmitter.

IMPORTANT

:  Before  electrically  activating  the  actuator,  remove  bleed

screw “S” (fig. 17) which is positioned under the base with articulated joint

and keep it for any later reuse. Only remove bleed screw “S” when the

actuator is installed.

9) MANUAL OPENING

In emergency case, such as in the case of power cut-out, to release the

gate, insert the same key C used for the adjustment of the by-pass valve

inside the triangular pin (Fig.18) and rotate it counterclockwise.

The gate  can now be opened manually.

WARNING! make sure that you manually push the gate open at the

same speed as the motor would have.

To reset the electric  operation of the actuator, turn the key in clockwise

direction until pin is blocked.

9.1) Mod. ORO

In case of emergency, for example when the electrical power is disconnected,

to release the gate, insert the same key C used for the adjustment of the by-

pass valve inside the triangular pin (Fig.18) and rotate it counterclockwise.

The gate can now be opened manually. To reset the electric operation of

the actuator, turn the key in clockwise direction until pin is blocked.

9.2) Mod. ORO/E

Since these models are reversible, for the manual operation of the gate it

is sufficient that the electric lock be opened with the appropriate key. To

make the manual manoeuvre easier, the lock can be released by means of

a triangular pin which can be reached using the appropriate key.

10) PUSHING FORCE ADJUSTMENT

The pushing force is adjusted by two valves marked with the writing “

Close

and “

Open

” respectively, which are used to adjust the closing and opening

pushing force (fig.19).

Lift open the lid indicated in (Fig.19) there you will find the two valves.

10 -

 

ORO - Ver.  03

INSTALLATION MANUAL

ENGLISH

Turn the valves towards the “

+

” sign to increase the force transmitted; turn

the valves towards the “

-

” sign to reduce the force.

To achieve proper antisquash safety, the pushing force must be slightly

higher than that needed to move the leaf during both closing and opening

manoeuvres; the strength, which is measured on the leaf edge, must never

exceed the limits set out by the current national standards.

Under no circumstances whatsoever must the by-pass valves be fully

closed.

Complete the adjustments and restore the release system.

The actuator is not provided with electrical limit switches.

 Therefore

the motors switch off at the end of the operation time set by the control unit.

The said operation time must last approximately 2-3 seconds after the

moment when the leaves meet the ground stop plates.

11) COVERING ELEMENT POSITIONING

Covering element “C” for all models can become left or right-handed by

reversing the position of cap “T” (fig. 21), taking care to keep the water

drainage channel always at the bottom, remember to screw back the Q

screw.

12) AUTOMATION CHECK

Before the automation device finally becomes operational, scrupulously

check the following conditions:

• Check that all components are tightly fixed.

• Check that all control devices (photocells, pneumatic edge etc) operate

correctly.

• Check the emergency manoeuvre command.

• Check the opening and closing operations using the control devices

provided.

• Check the normal (or personalised) function control logic in the control

unit.

13) AUTOMATION OPERATION

Since the automation system can be remotely controlled by means of a

radio control device or a Start button, all safety devices must be frequently

checked in order to ensure their perfect efficiency.

In the event of any irregular operation, request immediate assistance from

qualified personnel.

Children must be kept at a safe distance from the automation operation

area.

14) CONTROL

Various types of controls are provided (manual, radio control, magnetic

card access control etc.) depending on the installation requirements and

characteristics.

(See the specific instructions for the various control systems).

The installer undertakes to instruct the user about the correct automation

operation, and also point out the operations required in case of emergency.

15) MAINTENANCE

Before  carrying  out  any  maintenance  to  the  controller,  disconnect  the

system power supply.

• Periodically check the system for oil leaks.

To recap the oil, please use the same oil as descibed in the ”

TECHNICAL

SPECIFICATIONS

” paragraph and proceed with tho following instruction:

a) With the piston all the way out take of the screw( P) situated on the

base see (Fig.20).

b) Top up using the prescribed oil until its level reaches the level of the

oil lid see (Fig.20).

c) Refit all the components paying attention to the seals.

ATTENTION - 

Replace the actuator oil every 2 years with the same oil as

described in the ”

TECHNICAL SPECIFICATIONS

” paragraph.

• Check all automation safety devices.

• When any operational malfunction if found, and not resolved, disconnect

the systems power supply and request the assistance of a qualified

technician (installer).

• When the automation is out of order, activate the manual release knob

to allow the manual opening and closing operations to be carried out by

means of the electric lock.

16) MALFUNCTIONS AND REMEDIES

16.1) Faulty operation of the actuator

Using an appropriate instrument, check that the ends of the actuator are

supplied with voltage after the opening or closing command is given.

If the motor vibrates but does not turn, the causes could be as follows: 

• Wrong connection of common wire C (always light blue).

• No connection between the drive capacitor and the two drive terminals.

• If the leaf movement is opposite to what it should be, reverse the motor

drive connections in the control unit.

Leaf stops: when the operation time is insufficient, the leaves may not

complete their strokes. In that case, slightly increase the operation time

setting in the control unit.

16.2) Faulty operation of the electrical accessories

All  faulty  control  and  safety  devices  can  cause  abnormal  operation  or

automation block.

If the control unit is provided with a self-diagnosing system, identify the

fault.

In  case  of  malfunction,  it  is  advisable  to  disconnect  and  bridge  all  the

automation  devices  one  by  one,  if  necessary,  until  the  faulty  device  is

identified. After replacing or repairing it, restore all the devices which were

previously disconnected or bridged. For all devices installed, refer to their

respective instruction manual.

WARNING !

 the above operation must be carried out by qualified personnel.

During  maintenance,  the  gate  operational  area  must  be  appropriately

indicated and closed off, in order to avoid any danger to persons, animals

and property.

WARNINGS! Correct controller operation is only guaranteed when the

data specified in this manual are respected. The company cannot be

held responsible for any damage caused by failure to observe the

standards on safety, installation and good technical practice, as well

as the directives specified in the present manual.

17) SCRAPPING

WARNING:

 This operation should only be carried out by qualified personnel.

Materials must be disposed of in conformity with the current regulations.

In case of scrapping, the automation devices do not entail any particular

risks or danger.

In  case  of  recovered  materials,  these  should  be  sorted  out  by  type

(electrical components, copper, aluminium, plastic etc.).

18) DISMANTLING

WARNING!

 This operation should only be carried out by qualified personnel.

When  the  automation  system  is  disassembled  to  be  reassembled  on

another site, proceed as follows:

• Disconnect the power supply and the entire external electrical installation.

• Replace the bleed screw (fig. 17) under the articulated joint block.

• In the case where some of the components cannot be removed or are

damaged, they must be replaced.

The descriptions and illustrations contained in the present manual

are not binding. The Company reserves the right to make any alterations

deemed appropriate for the technical, manufacturing and commercial

improvement of the product, while leaving the essential product

features.

ORO - Ver.  03 - 

9

INSTALLATION MANUAL

ENGLISH

WARNING!

 All versions are provided with a ball joint which allows the rod

to be lengthened or shortened by approximately 5mm, but only if it was fixed

using the dimensions shown in fig.8 before installation after installation, this

adjustment allows the rod stroke to be corrected.

Fig.9 illustrates the oscillation that the controllers may show with respect to

their horizontal axis.

During installation, carefully follow all the phases described below, taking

care to protect the actuator’s chromium-plated rod at all times, in order to

prevent it from being damaged by impact or any welding slag.

1) Identify “a - b - 

α

°

 ” in the table in fig. 3.

2) Fix bracket “P” (fig.10) to the pillar.

3) Fit the piston in bracket “P”.

4) Make sure that the rod eye is adjusted see fig 8.

5) Pull  the  rod  out  completely  after  activating  the  emergency  release

(fig.18)

6) Push the rod back in manually until you position the eye hole with the

hole of the template (fig.22).

7) Fit fork “F” (fig.8) to the rod.

8) Fully close the gate leaf against the centre stop plate.

9) Keeping the piston level, mark the position for attaching fork (fig. 10 ref.

“F”) to the leaf.

10) Remove fork “F” from the rod and move the piston sideways.

11) Fix fork (fig.10 ref. “F”) to the leaf by means of screws or welding.

12) Reconnect the rod to fork “F” remove bleed screw “S” (Fig.17) and

supply the actuator with power.

13) Make some full cycles.

14) In  the  case  when  you  have  to  adjust  the  opening  angle,  do  so  by

adjusting the ball joint see fig.8.

15) After  adjustment  proceed  as  follows  in  order  to  secure  piston  into

mounting bracket: clean piston cover and secure with fastener, insert

mounting pin and tighten lock nut with open end wrench as shown in

Fig.8A.

5.4) Suggestions for particular installations

Fig.5 A recess must be made to house the controller when the leaf is

completely open; the recess measurements are shown in fig.5.

Fig.7 When the ”b” dimension is greater than the values shown in the

installation tables, it is necessary to move the leaf hinge-pivot or

make a recess in the pillar, as in fig.6.

5.5) Anchoring of attachments to the pillar

Weld or fix the bracket base supplied to the pillar, check the “a” and “b”

measurements and then weld plate “P” to the said base. (fig. 10).

• If the pillar is made of masonry, plate “P” must be welded to the metal

base “PF” and deeply anchored by means of suitable hooks “Z” which are

to be welded on the back of the said base (fig. 11a).

• If the pillar is made of stone, plate “P” is welded to the metal base “PF”

and can be fixed by means of four metal screw anchors “T” (fig. 11b); if

the gate is large, it is advisable to weld plate “P” to an angle-shaped base

(fig. 11c).

5.6) Anchoring of attachments to the leaf

Weld or fix fork “F” to the leaf at distance between centres “C” shown in fig.4,

making sure that the actuator is perfectly level (level “L”, fig. 10) with respect

to the gate movement plane.

• If the gate is made of metal, the fork can be welded (fig. 12a) or fixed

using appropriate screws (fig. 12c).

• If the gate is made of wood, the fork can be fixed using appropriate

screws (fig. 12b).

6) GROUND LEAF STOP PLATES

For the actuator to operate correctly, stop plates “FA” must be used during

both opening and closing manoeuvres, as shown in fig. 13.

The leaf stop plates must prevent the actuator rod from going to the end-

of- stroke position. Fig.14 specifies the dimensions needed to check the

correct actuator installation both for pushing and towing. The plates must

be  positioned  in  such  a  way  as  to  maintain  a  rod  stroke  margin  of

approximately 5mm; this is to avoid possible operation anomalies (such as

a lock-up).

7) ELECTRIC LOCK FITTING

This is needed on mod. 

ORO/E

 only since these are not supplied with a

hydraulic lock on closing.

The 

EBP

  model  electric  lock  (fig.15)  consists  of  a  continuous  service

electromagnet being anchored to the ground.

This device remains energized throughout the actuator operation time, and

allows the catch to stay lifted when it reaches the closing position, without

opposing any resistance; the catch will drop into position when the gate has

completed the closing cycle.

The electric lock can also be used to keep the block of the gate in case of

actuator malfunction or current failure.

8) ELECTRICAL INSTALLATION SET-UP

Lay out the electrical installation (fig. 16) with reference to the CEI 64-8 and

IEC 364 provisions, complying with the HD 384 and other national standards

in force for electrical installation. The mains power supply connections must

be kept totally separate from the service connections (photocells, electric

edges, control devices etc.).

WARNING! For connection to the mains, use a multipolar cable with

a minimum of 3x1.5mm

2

 cross section and complying with the

previously mentioned regulations. For example, if the cable is out side

(in the open), it has to be at least equal to H07RN-F, but if it is on the

inside (or outside  but placed in a  plastic cable cannel) it has to be or

at least egual to H05VV-F with section 3x1.5mm

2

.

Connect the control and safety devices in compliance with the previously

mentioned electrical installation standards.

Fig.16 shows the number of connections and the cross section for power

supply cables having a length of approximately 100 metres; in case of

longer cables, calculate the cross section for the true automation load.

When the auxiliary connections exceed 50-metre lengths or go through

critical disturbance areas, it is recommended to decouple the control and

safety devices by means of suitable relays.

8.1) The main automation components are

 (fig.16):

I

Type-approved  omnipolar  circuit  breaker  with  at  least  3mm  contact

opening,  provided  with  protection  against  overloads  and  short  circuits,

suitable for cutting out automation from the mains. If not already installed,

place  a  type-approved  differential  switch  with  a  0.03A  threshold  in  the

circuit just before the automation system.

Qr

Control panel and incorporated receiver.

SPL

Preheating board for operation with temperature lower than 5

°

C

(optional).

S

Key selector.

AL

Blinker with tuned antenna and RG58 cable.

M

Actuator.

E

Electric lock.

Fte

Pair of external photocells (transmitter).

Fre

Pair of external photocells (receiver).

Fti

Pair of internal photocells with CF posts.

Fri

Pair of internal photocells with CF posts (receiver).

T

1-2-4 channel transmitter.

IMPORTANT

:  Before  electrically  activating  the  actuator,  remove  bleed

screw “S” (fig. 17) which is positioned under the base with articulated joint

and keep it for any later reuse. Only remove bleed screw “S” when the

actuator is installed.

9) MANUAL OPENING

In emergency case, such as in the case of power cut-out, to release the

gate, insert the same key C used for the adjustment of the by-pass valve

inside the triangular pin (Fig.18) and rotate it counterclockwise.

The gate  can now be opened manually.

WARNING! make sure that you manually push the gate open at the

same speed as the motor would have.

To reset the electric  operation of the actuator, turn the key in clockwise

direction until pin is blocked.

9.1) Mod. ORO

In case of emergency, for example when the electrical power is disconnected,

to release the gate, insert the same key C used for the adjustment of the by-

pass valve inside the triangular pin (Fig.18) and rotate it counterclockwise.

The gate can now be opened manually. To reset the electric operation of

the actuator, turn the key in clockwise direction until pin is blocked.

9.2) Mod. ORO/E

Since these models are reversible, for the manual operation of the gate it

is sufficient that the electric lock be opened with the appropriate key. To

make the manual manoeuvre easier, the lock can be released by means of

a triangular pin which can be reached using the appropriate key.

10) PUSHING FORCE ADJUSTMENT

The pushing force is adjusted by two valves marked with the writing “

Close

and “

Open

” respectively, which are used to adjust the closing and opening

pushing force (fig.19).

Lift open the lid indicated in (Fig.19) there you will find the two valves.

WARNING! For connection to the mains power supply, use a multicore 

cable with a cross-sectional area of at least 3x1.5mm

2

 of the kind 

provided for by the regulations in force. 

To connect the motors, use a cable with a cross-sectional area of at 

least 1.5mm

2

 of the kind provided for by the regulations in force. 

The cable must be type H05RN-F at least.

26 -

 ORO - ORO E

D811247_05

Summary of Contents for ORO

Page 1: ...TORE AUTOMATIZACIONES A PISTON PARA PORTONES CON BATIENTE AUTOMATIZAÇÕES DE PISTÃO PARA PORTÕES DE BATENTE Attenzione Leggere attentamente le Avvertenze all interno Caution Read Warnings inside carefully Attention Veuillez lire attentivement les Avertissements qui se trouvent à l intérieur Achtung Bitte lesen Sie aufmerksam die Hinweise im Inneren Atención Leer atentamente las Advertencias en el i...

Page 2: ...tofthepartbeingcontrolledand unlesstheyarekeyoperated must be installed at a height of at least 1 5 m and in a place where they cannot be reached by the public Apply at least one warning light flashing light in a visible position and also attach a Warning sign to the structure Attach a label near the operating device in a permanent fashion with informa tion on how to operate the automated system s...

Page 3: ...ock has not been relea sed by means of the appropriate key In mod ORO the release has not been activated by means of the appropriate key fig 1 2 EMERGENCY MANOEUVRE 2 1 Mod ORO In case of emergency for example when the electrical power is disconnected to release the gate insert the same key C used for the adjustment of the by pass val ve inside the triangular pin Fig 1 and rotate it counter clockw...

Page 4: ... 1 Mod ORO En casos de emergencia por ejemplo cuando falta el suministro de corriente para desbloquear la cancela hay que introducir la llave C utilizada para la regula ción de la válvula by pass en el perno triangular fig 1 y girarla en sentido contrario a las agujas del reloj La cancela de esta manera se puede abrir manual mente Para restablecer el funcionamiento eléctrico del servomotor habrá q...

Page 5: ...b Carrera total Cu Corsa utile Working stroke Course utile Nutzhub Carrera útil a mm b mm 630 890 950 5 80 64 75 5 70 64 70 5 104 99 94 91 112 99 94 91 88 105 94 91 100 89 87 95 95 95 103 90 90 89 86 96 106 84 α 89 80 97 83 88 80 90 100 110 120 130 140 150 160 80 90 100 110 120 130 140 150 160 16 ORO ORO E D811247_05 ...

Page 6: ...28 ORO Ver 03 Fig 4 Fig 6 Fig 5 Fig 8 Fig 7 45 a b Min 1000 b 40 b 5 5 b kg C a P D F b x Z b x 40mm F ORO ORO E 17 D811247_05 ...

Page 7: ...ORO Ver 03 29 Fig 11 Fig 12 Fig 10 Fig 9 Fig 8A P L Z a b c a b c PF F F F T PF F 7 18 ORO ORO E D811247_05 ...

Page 8: ... 262 T 11 Close Open EBP FA FA FA x D x S E S P I R Q M M AL 2 2 2 3x1mm 2x1 5mm 2 2 2 4x1mm 2 4x1 5mm 3x1mm 2x1mm Fte 2x1 5mm RG58 2 2 2x1mm 2 2 3x1 5mm Fti CF CF Fri 4x1mm 4x1 5mm ORO ORO E 5 D811247_04 ORO ORO E 19 D811247_05 ...

Page 9: ...ORO Ver 03 31 Fig 19 Fig 18 Fig 17 a b S C CLOSE OPEN 20 ORO ORO E D811247_05 ...

Page 10: ...RELAND BFT AUTOMATION LTD Dublin 12 BENELUX BFT BENELUX SA 1400 Nivelles www bftbenelux be POLAND BFT POLSKA SP Z O O 05 091 ZĄBKI www bft pl CROATIA BFT ADRIA D O O 51218 Drazice Rijeka www bft hr PORTUGAL BFT SA COMERCIO DE AUTOMATISMOS E MATERIAL DE SEGURANCIA 3020 305 Coimbra www bftportugal com CZECH REPUBLIC BFT CZ S R O Praha www bft it TURKEY BFT OTOMATIK KAPI SISTEMELERI SANAY VE Istanbul...

Page 11: ...s requirements and type of operation They are models available with a hydraulic lock on closing or without a hydraulic lock in which an electric lock is required To make the manual manoeuvre easier the lock can be released by means of a triangular pin which can be reached using the appropriate key The pushing force is adjusted with extreme precision by means of two by pass valves which provide ant...

Page 12: ...opriate key To make the manual manoeuvre easier the lock can be released by means of a triangular pin which can be reached using the appropriate key 10 PUSHING FORCE ADJUSTMENT The pushing force is adjusted by two valves marked with the writing Close and Open respectively which are used to adjust the closing and opening pushing force fig 19 Lift open the lid indicated in Fig 19 there you will find...

Page 13: ... usly rate ices ntrol of a ently rom tion netic and ation ncy the Leaf stops when the operation time is insufficient the leaves may not complete their strokes In that case slightly increase the operation time setting in the control unit 16 2 Faulty operation of the electrical accessories All faulty control and safety devices can cause abnormal operation or automation block If the control unit is p...

Page 14: ...ITALY ...

Reviews: