background image

447

D811230_04

ORION G-GBR

ORION G-GBR

Thank you for buying this product, our company is sure that you will be more
than satisfied with the product

s performance. The product is supplied with

a

WARNINGS

 leaflet and an 

INSTRUCTION MANUAL

. These should

both be read carefully as they provide important information about safety,
installation, operation and maintenance. This product complies with the
recognised technical standards and safety regulations. We declare that this
product is in conformity with the following European Directives: 89/336/
EEC and subsequent amendments.

1) GENERAL OUTLINE

The

ORION G

 board is used to control one single-phase motor of up to 800W.

Its main feature is the electronic breaking control during the stopping phase.

ATTENTION - Only qualified personnel should be employed.

2) GENERAL SAFETY
WARNING! An incorrect installation or improper use of the product
can cause damage to persons, animals or things.

The

Warnings

  leaflet  and 

Instruction  booklet

  supplied  with  this

product should be read carefully as they provide important information
about safety, installation, use and maintenance.

Scrap packing materials (plastic, cardboard, polystyrene etc) according
to the provisions set out by current standards. Keep nylon or polystyrene
bags out of children

s reach.

Keep  the  instructions  together  with  the  technical  brochure  for  future
reference.

This product was exclusively designed and manufactured for the use
specified in the present documentation. Any other use not specified in
this documentation could damage the product and be dangerous.

The Company declines all responsibility for any consequences resulting
from improper use of the product, or use which is different from that
expected and specified in the present documentation.

Do not install the product in explosive atmosphere.

The Company declines all responsibility for any consequences resulting
from  failure  to  observe  Good  Technical  Practice  when  constructing
closing structures (door, gates etc.), as well as from any deformation
which might occur during use.

The installation must comply with the provisions set out by the following
European Directives: 89/336/EEC and subsequent amendments.

Disconnect the electrical power supply before carrying out any work on
the installation. Also disconnect any buffer batteries, if fitted.

Fit an omnipolar or magnetothermal switch on the mains power supply,
having a contact opening distance equal to or greater than 3mm.

Check  that  a  differential  switch  with  a  0.03A  threshold  is  fitted  just
before the power supply mains.

Check that earthing is carried out correctly: connect all metal parts for
closure (doors, gates etc.) and all system components provided with an
earth terminal.

The Company declines all responsibility with respect to the automation
safety and correct operation when other manufacturers

 components

are used.

Only use original parts for any maintenance or repair operation.

Do not modify the automation components, unless explicitly authorised
by the company.

Instruct the product user about the control systems provided and the
manual opening operation in case of emergency.

Do  not  allow  persons  or  children  to  remain  in  the  automation
operation area.

Keep radio control or other control devices out of children

s reach, in

order to avoid unintentional automation activation.

The  user  must  avoid  any  attempt  to  carry  out  work  or  repair  on  the
automation  system,  and  always  request  the  assistance  of  qualified
personnel.

Anything which is not expressly provided for in the present instructions,
is not allowed.

3) TECHNICAL SPECIFICATIONS

Power supply: ....................................................... 230Vac 

±

10% 50/60Hz

Max. motor power: .............................................................................800W
Power supply to accessories: ................................... 24Vac - 180mA max
Panel consumption: ....................................................................... 100 mA
Fixed operation time: ............................................................ 140 s approx.
Fixed pedestrian operation time: .............................................. 9 s approx.

Adjustable automatic closing time: ...................................... from 2 to 90 s
Pre-alarm time: ...................................................................................... 3 s
Environmental conditions: ........................................  from -20

°

C to +55

°

C

Protection degree: ............................................................................  IP 55
Dimensions: .................................................................................  see fig.1
Weight: .............................................................................................  1.2 kg

4) TERMINAL BOARD CONNECTIONS

 (Fig.2)

ATTENTION! -

 Keep the low voltage connections definitely separated from

the power supply connections.

JP3 FILTER

1 Earth (GND).
2-3  Single-phase  power  supply:  230V 

±

10%  50/60  Hz.  (2  Neutral  -  3

Phase).

ORION G

3-4-5 Motor connection (3/5 operation - 4 common wire).
3-6 Capacitor.
2-7 Blinker 230 Vac.
8-9 Open-Close push button and key selector (N.O.).
8-10 Stop push button (N.C.). If not used, leave jumped.
8-11 Photocell contact or rubber skirt(N.C.) If not used, leave jumped.
8-12 Opening limit switch (N.C.). If not used, leave jumped.
8-13 Closing limit switch (N.C.). If not used, leave jumped.
14-15 Output 24 Vac 180mA max.
15-16 Gate-open warning light 24 Vac 3W max.
17-18 Antenna input for radio receiver board (17 signal - 18 braid).

ATTENTION -

 To invert motor running direction, invert the motor connections

3 and 5 and the limit switch connections 12 and 13.

Do not move the capacitor connection.
SOG OPTIONAL BOARD

 (fig.2).

9-20 Opening push button (N.O.). When the 

Open

 command is given,

the motor opens independently of its state.
19-21 Closing push button (N.O.). When the 

Close

 command is given, the

motor closes independently of its state.

ATTENTION: In some versions of the ORION G boards, terminals 20
and  21  of  the  SOG  optional  board  have  the  HOLD-TO-RUN  control
feature (UP) instead of the separate open-close control (ACS).

19-22 Push button for pedestrian access (N.O.). When the 

Pedestrian

command is given, the gate opens of about 1 metre.
23-24 Rubber skirt contact connection (N.C.). If the rubber skirt steps  in,
the  movement  is  reversed  for  about  30  centimetres.  If  not  used,  leave
jumped.
25-26 Second radio channel output (if a twin-channel board is fitted).

5) DIP SWITCH FUNCTIONS

 (Fig.3)

DIP 1 MODE

OFF: A start impulse during the motor run causes the gate to stop (4 - step
operation) both in opening and closing phase.
ON:  A  start  impulse  during  the  motor  run  causes  the  gate  to  reverse
direction (2-step operation) in closing phase.

DIP 2 PRE-ALARM

OFF: The flashing light turns on simultaneously with the start of the motors.
ON: The flashing light turns on abt. 3 seconds before the motors start.

DIP 3 PHOTOCELLS

OFF: Photocell intervention causes the operator to stop both in the  opening
or closing phase. After removing the obstacle, the operator opens.
ON:  Photocell  intervention  has  no  effect  on  the  opening  phase  and
immediately reverses movement during the closing phase.

DIP 4 AUTOMATIC CLOSING TIME TCA

OFF: Switches off the automatic closure
ON:  The  gate  closes  again  automatically  after  a  pause  time  set  on  the
trimmer T1. Such a function is activated:
- In full open position.
- In the opening phase by means of the start push button or radio control.

DIP 5 IMPULSE BLOCK

OFF: A start impulse during the opening phase causes the operator to stop.
ON: A start impulse during the opening phase has no effect.

DIP 6

: Not used.

6) TRIMMER FUNCTIONS

 (Fig.3)

TRIMMER T1 TCA

: Sets the pause time before the automatic closure. The

time can be increased by turning it clockwise.

CONTROL UNITS

CONTROL UNITS

Reviews: