INSTALLATION MANUAL

13.2) TABLE “B” - LOGIC MENU - (

logic

)

Logic

Default Definition

Cross out 

setting 

used

Description

TCA

OFF

Automatic Closing 

Time

ON

Activates automatic closing

OFF

Excludes automatic closing

Ibl open

OFF

Opening Impulse 

lock

ON

The Start impulse has no effect during the opening phase.

OFF

The Start impulse becomes effective during the opening phase.

ibl TCA

OFF

Impulse lock TCA

ON

The Start impulse has no effect during the TCA dwell period.

OFF

The Start impulse becomes effective during the TCA dwell period.

3 step

OFF

3 step

ON

Switches to 3-step logic. 

A start impulse has the following effects:

 

3 steps

4 steps

closed

opens

opens

on closing

stop

open

closes

closes

on opening

stop + TCA

stop + TCA

after stop

opens

opens

OFF

Switches to 4-step logic. 

preal

OFF

Pre-alarm

ON

The flashing light comes on approx. 3 seconds before the motors start.

OFF

The flashing light comes on at the same time as the motors start.

hold to run

OFF

Deadman

ON

Hold-to-run operation: the manoeuvre continues as long as the OPEN and CLOSE 

control keys are kept pressed. The radio transmitter cannot be used.  

OFF

Normal impulse operation. 

Photoc. open

OFF

Photocells

during opening

ON

When beam is broken, operation of the photocell is switched off during opening. During closing, 

movement is reversed immediately.

OFF

When beam is broken, photocells are active during both opening and closing. When beam is broken 

during closing, movement is reversed only once the photocell is cleared.

test phot

OFF

Photocell test

ON

Switches photocell testing on

OFF

Switches photocell testing off

If disabled (OFF), it inhibits the photocell testing function, enabling connection of devices not equipped 

with supplementary test contacts.

test bar

OFF

Safety edge 

testing

ON

Switches safety edge testing on.

OFF

Switches safety edge testing off

If disabled (OFF), it inhibits the safety edge testing function, enabling connection of devices not equip-

ped with supplementary test contacts.

ster

OFF

Master/slave

ON

Control panel is set up as the Master unit in a centralized serial connection system.

OFF

Control panel is set up as a Slave unit in a centralized serial connection system.

fixed code

OFF

Fixed code

ON

Receiver is configured for operation in fixed-code mode.

OFF

Receiver is configured for operation in rolling-code mode.

radio prog

ON

Remote control 

programming

ON

Enables wireless memorizing of transmitters: 

1- Press in sequence the hidden key (P1) and normal key (T1-T2-T3-T4) of a transmitter that has already 

been memorized in standard mode via the radio menu.

2- Press within 10 secs. the hidden key (P1) and normal key (T1-T2-T3-T4) of a transmitter to be memorized.

IMPORTANT: Enables the automatic addition of new transmitters, clones and replays. 

The receiver exits programming mode after 10 secs.: you can use this time to enter other new tran-

smitters. This mode does not require access to the control panel.

OFF

Disables wireless memorizing of transmitters. 

Transmitters are memorized only using the relevant Radio menu.

IMPORTANT: Disables the automatic addition of new transmitters, clones and replays.

SCA 2Ch

OFF

Gate open light or 

2nd radio channel

ON

The output between terminals 14-15 is set as Gate open light:

in this case, the 2nd radio channel controls pedestrian opening.

OFF

The output between terminals 14-15 is set as 2nd radio channel.

start - 
close

OFF

START - CLOSE 

setting

ON

Input between terminals 21-22 works as CLOSE.

OFF

Input between terminals 21-22 works as START.

change  ot.

OFF

Reversing motion

ON

Change this parameter if the opening direction needs to be changed

OFF

Standard operating mode.

ICE

(special dip  2*)

OFF

ICE

ON

The controller automatically adjusts the Amperostop safety trip threshold. 

Check that the force of impact 

measured at the points provided for by standard EN 12445 is lower than the value laid down by standard 

EN 12453.

 If in doubt, use auxiliary safety devices. This feature is useful when dealing with installations 

running at low temperatures.

WARNING: once this feature has been activated, you will need to perform an autoset opening and 

closing cycle.

OFF

The Amperostop safety trip threshold stays at the same set value.

*=Refer for universal handheld programmer.

13.3) TABLE C: RADIO MENU (

RADIO

)

Logic

Description

Add start

Add Start Key 

associates the desired key with the Start command.

add 2ch

Add 2ch Key 

associates the desired key with the 2nd radio channel command.

erase 64

Erase List WARNING! 

Erases all memorized remote controls from the receiver’s memory.

Read receiver code 

Displays receiver code required for cloning remote controls.

ON

 = Enables remote programming of cards via a previously memorized W LINK transmitter. It remains enabled for 3 minutes from the time the 

W LINK remote control is last pressed.

OFF

= W LINK programming disabled.

22  -

  ARES

D811692 00100_04

Summary of Contents for ARES

Page 1: ... ANTRIEB FÜR ZAHNSTANGEN SCHIEBETORE SERVOMOTOR PARA CANCELAS CORREDERAS DE CREMALLERA ACTUATOR VOOR SCHUIFHEKKEN MET TANDHEUGEL Attenzione Leggere attentamente le Avvertenze all interno Caution Read Warnings inside carefully Attention Veuillez lire attentivement les Avertissements qui se trouvent à l intérieur Achtung Bitte lesen Sie aufmerksam die Hinweise im Inneren Atención Leer atentamente la...

Page 2: ... accesorios transmisión Montage accessoires overbrenging Fissaggio staffe finecorsa dx e sx Fastening limit switch brackets RH LH Fixation étriers fin de course drt et gch Befestigung Bügel Anschläge rechts und links Fijación abrazaderas final de carrera der e izq Bevestiging stangen aanslag rechts en links Y Y Collegamento morsettiera Terminal board wiring Connexion plaque à bornes Anschluss Klem...

Page 3: ... 12 14 SCA II CH 15 JP9 14 15 24 V VSAFE VSAFE 24V 0V 25W max LOGICA test fotocellule OFF Photocell test LOGIC OFF LOGIQUE essai photocellules Désactivée LOGIK Test Fotozellen OFF LÓGICA prueba fotocélulas OFF LOGICA test fotocellen OFF ne ngstasten Display programmeringstoetsen Display tasti programmazio Display programming keys Display Programmieru Pantalla botones programación 1 2 3 4 5 6 7 8 9...

Page 4: ...ing opening 99 99 99 99 99 99 Speed during closing 99 99 99 99 99 99 Partial opening 40 40 40 40 40 40 Zone 0 0 0 0 0 0 Slow down distance 0 0 0 0 0 0 Opening deceleration space 10 10 10 10 10 10 Closing deceleration space 10 10 10 10 10 10 LOGIC Automatic Closing Time OFF ON OFF ON OFF OFF Block Pulses OFF OFF OFF ON ON OFF Impulse lock TCA OFF OFF OFF OFF OFF OFF 3 step OFF ON OFF ON OFF OFF Pre...

Page 5: ...8888 K N M O P CFZ CP 37 30 12 28 22 22 CVZ 28 60 6 40 KO OK Q R P1 P2 S L O1 100 25 50 25 2mm 2 6 0 1 6 0 1 0 0 300 152 65 2 0 0 Z18 Ø p72 Z25 Ø p100 2 2 4 0 10 ARES D811692 00100_04 ...

Page 6: ...20 21 22 23 24 25 26 27 JP2 JP1 31 32 33 34 COM NC BAR2 COM NC SWC NC SWO 24 V 0 V 0 V V Safe V Safe RX RX TX TX 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 JP2 JP1 31 32 33 34 COM NC SWC NC SWO FAULT PHOT FAULT BAR 2 FAULT BAR 1 COM NO 24 V V Safe V Safe RX RX TX TX ANT 24V 25W Max 24V 25W Max SCA 2 CH PED COM NO NO NC NO NC NC ST ART CLOSE STOP PHOT BAR1 OPEN U NO SCS...

Page 7: ... 3 4 5 6 13 12 21 25 17 Bar 2 1 2 3 4 5 6 13 12 27 21 17 Bar 1 1 2 3 4 5 6 13 12 21 25 17 Bar 2 1 2 3 4 5 6 13 12 5 SCS1 MA 4 SCS1 MA 2 SCS1 MA 1 SCS1 MA 17 Bar 3 1 2 3 4 5 6 13 12 27 21 17 6 SCS1 MA Bar 1 1 2 3 4 5 6 13 12 21 25 17 Bar 2 1 2 3 4 5 6 13 12 17 Bar 4 1 2 3 4 5 6 13 12 27 21 17 Bar 3 1 2 3 4 5 6 13 12 5 SCS1 MA 3 SCS1 MA 6 SCS1 MA 4 SCS1 MA 17 26 27 25 24 23 22 21 20 19 18 COM FAULT ...

Page 8: ...activated svo opening limit switch input activated svc closing limit switch input activated set the board is standing by to perform a com plete opening closing cycle uninterrupted by intermediate stops in order to acquire the tor que required for movement WARNING Obstacle detection function is not active Er01 photocell test error check photocell connection and or logic settings Er02 safety edge te...

Page 9: ...s closed If the automated system is installed at a height of less than 2 5 m or is accessible the electrical and mechanical parts must be suitably protected Install any fixed controls in a position where they will not cause a hazard away from moving parts More specifically hold to run controls must be positioned withindirectsightofthepartbeingcontrolledand unlesstheyarekeyoperated must be installe...

Page 10: ...omponents have been fastened at the predetermined points thenextstepistoconnectthemasdirectedandillustratedinthediagrams containedintherelevantinstructionmanuals Connectthelive neutralandearth wire compulsory The mains cable must be clamped in the relevant cable gland FIG R ref P1 and the accessories wires in the cable gland FIG R ref P2 while the earth wire with the yellow green coloured sheath m...

Page 11: ...E Fig V the SCS MA auxiliary board must be used 15 4 Interface with WIEGAND systems via SCS WIE module Refer to the SCS WIE module s instructions 13 1 TABLE A PARAMETERS MENU PARA Parameter min max default personal Definition Description tca 0 120 40 Automatic Closing Time Automatic closing time s slov speed 15 50 15 Slow down speed Slow down speed Fig 2 Rif F Set the speed the gate must reach slo...

Page 12: ... code mode radio prog ON Remote control programming ON Enables wireless memorizing of transmitters 1 Press in sequence the hidden key P1 and normal key T1 T2 T3 T4 of a transmitter that has already been memorized in standard mode via the radio menu 2 Press within 10 secs the hidden key P1 and normal key T1 T2 T3 T4 of a transmitter to be memorized IMPORTANT Enables the automatic addition of new tr...

Page 13: ...della porta se in presenza di guasti meccanici o di condizioni di squilibrio Incasodiapritapparelle sorvegliarelatapparellainmovimentoetenerelontano le persone finché non è completamente chiusa Porre cura quando si aziona lo sbloccosepresente poichéunatapparellaapertapotrebbecadererapidamente in presenza di usura o rotture Larotturaol usuradiorganimeccanicidellaporta parteguidata qualiadesempio ca...

Page 14: ... le levier de déverrouillage prévu à cet effet Ne pas entrer dans le rayon d action du portail de la porte motorisé e pendant son mouvement Ranger les radiocommandes ou les autres dispositifs de commande hors de portée des enfants afin d éviter tout actionnement involontaire L activation du déverrouillage manuel risque de provoquer des mouvements incontrôlés de la porte en présence de pannes mécan...

Page 15: ...puede provocar situaciones de peligro Todo aquello que no expresamente previsto en el manual de uso no está permitido El buen funcionamiento del operador es garantizado sólo si se respetan las prescripciones indicadas en el presente manual La Empresa no se responsabiliza por los daños causados por el incumplimiento de las indicaciones dadas en el presente manual Dejandoinalteradaslascaracterística...

Page 16: ......

Reviews: