Failures
8-2
Problem:
Display:
Cause:
Remedy:
Burner fails
Flame signal (soft-
ware) drops. Below the
shut-off threshold, the
flame relay switched
off.
No flame, weak
flame signal
Check flame
Inspect compact flame control-
ler
Check alignment and lens
Check sensitivity setting
Check switching thresholds
Replace compact flame con-
troller
Check electrical connection
Flame signal above
shut-off threshold
Yellow LED OFF
Device or self-test
fault
Check fault memory
Possibly remove plug for 5
seconds then start the burner
again
Replace compact flame con-
troller
Summary of Contents for CFC 2000
Page 2: ......
Page 20: ...Safety 2 8...
Page 26: ...Technical data 3 6...
Page 40: ...Transport Installation and Connection 4 14...
Page 46: ...Operation of the Compact Flame Controller 6 2...
Page 48: ...Care and Maintenance 7 2...
Page 52: ...9 2...
Page 54: ...10 2...
Page 55: ...Accessories 10 3...