background image

19

ENGLISH

LEDs Lit

To Inverter

(Input AC is Low)

Boost

Nominal

Voltage

Buck

To Inverter

(Input AC is High)

2, 3, 4

(Default)

96

109

120

130

146

1, 3, 4

96

109

120

138

156

2, 3, 5

90

104

120

130

146

1, 3, 5

90

104

120

138

156

3, 4, 5

90

104

110

120

130

2, 4, 5

90

104

110

130

146

3, 4, 6

90

96

110

120

130

2, 4, 6

90

96

110

130

146

1, 2, 4

96

109

128

146

156

1, 2, 5

90

104

128

146

156

Table 4: Voltage Settings for U Models (750, 1050, 1425, 1800, and 2250 VA)

Table 5: Voltage Settings for E Models (750, 1050, 1425, and 2250 VA)

270

244

230

200

180

3, 4, 6

284

250

230

210

188

2, 4, 5

270

244

230

210

188

3, 4, 5

(Default)

290

264

240

210

188

1, 3, 5

284

250

240

210

188

2, 3, 5

290

264

240

222

200

1, 3, 4

284

250

240

222

200

2, 3, 4

To Inverter

(Input AC is High)

Buck

Nominal

Voltage

Boost

To Inverter

(Input AC is Low)

LEDs Lit

284

250

230

200

180

2, 4, 6

244

222

208

188

165

4, 5, 6

270

244

208

188

165

3, 5, 6

Summary of Contents for Fortress 1050 VA

Page 1: ...USER GUIDE Fortress Rackmount 750 VA 1050 VA 1425 VA 1800 VA and 2250 VA...

Page 2: ...ge must be limited to 3 mA on the U model and 2 5 mA on the E model If you do not know the load leakage current replace the UPS power cord with a power cord that uses a lock ing plug with a minimum ra...

Page 3: ...F o r t r e s s Rackmount 750 VA 1050 VA 1425 VA 1800 VA and 2250 VA User Guide FSS 0388B Copyright 1998 Best Power All rights reserved...

Page 4: ...he unit If you prefer you can contact Best on the World Wide Web to get more product information Best s toll free Fax on Demand service is also available 24 hours a day to give you access to technical...

Page 5: ...eplacing the Batteries 10 Battery Replacement Instructions 11 Communication Port 12 DB 9 Pinouts 13 Specifications 13 Warranty 15 Appendix A Adjusting Voltage Settings 17 Best Power Offices 20 Tradema...

Page 6: ...bove 25 Celsius 77 Fahrenheit recharge the batteries more often CAUTION Whenever the Fortress is On there may be dangerous voltage present at the unit s outlets This is true because the unit s battery...

Page 7: ...panel LEDs and an audible alarm keep you aware of the unit s sta tus Use the drawings on this and the following page to identify features of the unit Line Buck boost Battery Mode Load or Battery Char...

Page 8: ...ULT 1050 1425 E 1050 1425 U 1 Status Indicators 8 5 15 Outlets 1800 and 2250 2 On Standby Button have breaker 3 Alarm Program Button 9 5 20 Outlets 2250 has breaker 4 Battery Access Panel 10 L5 30 Out...

Page 9: ...hardware from electronics distributors below the intended rack location for the Fortress Secure the shelf or brackets at both the front and back of the rack using bolts nuts and washers Carefully lift...

Page 10: ...main on If the unit beeps or if the top light does not remain on even though input power is available from the wall outlet go to the Troubleshooting section 4 Switch off the equipment you want to prot...

Page 11: ...s labled Site Wiring Fault lights to indicate a wiring fault in the circuit to which the Fortress is connected If this LED is on the outlet needs to be checked and repaired by an electrician Do not us...

Page 12: ...is running on battery power Output Overload Refer to Tables 2 and 3 Replace the Battery or UPS Fault Refer to Tables 2 and 3 Blinking The unit is boosting or bucking utility power Boost Automatically...

Page 13: ...onds 1 Utility power outage 2 Loose plug 3 Tripped circuit breaker 4 Power cord failure 1 Wait for power to return 2 Make sure the power cord is connected 3 Reset the circuit breaker 4 Phone Best Powe...

Page 14: ...s could fall into the UPS Never allow any tool to contact both a battery terminal and the UPS cabinet or another battery terminal Do not lay tools or metal parts on top of batteries To ensure continue...

Page 15: ...plug the protected load equipment from the Fortress Then turn off the Fortress and disconnect the line cord 3 Use the drawings below to identify the location on the battey pack in the model Fortress t...

Page 16: ...l to the front panel 11 If you followed the option in step 2 Reconnect the line cord to the Fortress and turn the unit on 12 Reconnect the load equipment Switch on the protected load equipment one pie...

Page 17: ...n 9 Unused Contacts consist of open collector circuits capable of switching up to 30 VDC 6 mA resistive load Specifications Best Power reserves the right to change specifications without prior notice...

Page 18: ...me to 95 of capacity 750 VA 1050 VA 1425 VA 1800 VA and 2250 VA 3 hours 1425 VA 7 hours with output fully loaded Recharge time is lower with reduced load Overcurrent Protection on line All Models Circ...

Page 19: ...he PURCHASER must promptly notify BEST POWER in writing within the duration of the warranty or not later than one month after expiration of the warranty BEST POWER s obligation under this warranty is...

Page 20: ...the Product beginning with the date of sale to the initial retail purchaser subject to the following conditions This warranty is applicable only to the initial retail purchaser hereinafter called PURC...

Page 21: ...above limitation on duration of implied warranties may not apply to you Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusio...

Page 22: ...en input voltage rises to 130 the Fortress begins to decrease buck the output voltage With 146 volts input or higher the Fortress switches to battery power 3 Use the appropriate table on the next page...

Page 23: ...146 156 1 2 5 90 104 128 146 156 Table 4 Voltage Settings for U Models 750 1050 1425 1800 and 2250 VA Table 5 Voltage Settings for E Models 750 1050 1425 and 2250 VA 270 244 230 200 180 3 4 6 284 250...

Page 24: ...NGAPORE 188647 Telephone 65 430 6168 FAX 65 430 6170 Sola Australia Ltd 13 Healey Road Dandenong Victoria 3175 AUSTRALIA Telephone 61 3 9706 5022 FAX 61 3 9794 9150 BEST House Wykeham Industrial Estat...

Page 25: ...is equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmfu...

Page 26: ...FSS 0388A...

Reviews: