background image

-6-

V. ELECTRICAL CONNECTIONS

VI. FIELD CONNECTIONS

All electrical wiring and connections 

MUST

 be performed by 

qualified personnel in accordance with the latest edition of the 

National Electrical Code ANSI/NFPA No. 70 or, in Canada, the 

Canadian Electrical Code, Part 1-C.S.A. Standard C22.1 and local 

codes and regulations.  

MAKE SURE THE CORRECT

VOLTAGE AS MARKED ON THE UNIT IS USED.

A. 

A separate line voltage supply with a suitable branch 

circuit protection device should be run directly from the 

main electrical panel to the unit. A disconnect switch for 

each branch circuit is a required part of this installation. 

See the voltage label on the unit for circuiting and total 

electrical load.  The wiring diagram is located in the 

junction box.  

See Figure 7.

B. 

All field wiring must be copper with a minimum 

insulation of 60°C within approved conduit. If any of the 

wire supplied with the unit must be replaced, it must be 

replaced with copper wiring with a minimum insulation 

of 90°C.

C. 

Electric, steam and hot water heated air curtains are 

factory equipped with an air curtain mounted solid state 

temperature sensor cable located in the junction box. 

Depending on where the temperature is to be measured, 

the sensor may be left on the endplate or positioned 

elsewhere.  Do not put any clamps on the rubber coated 

tip.

D. 

Remove the junction box cover.

E. 

Connect all supply and control circuit wires according to 

the wiring diagram provided.

NOTE: For Electric heated air curtains provided with 

the optional remote thermostat, mount and wire the 

thermostat according to thermostat instructions and wiring 

diagram. 

For Serial Network Connection

 (previously Master/

Slave Connection)

 

– see Appendix A, “Serial/Network 

Connection.”  

NOTE:  The air curtain must have been 

ordered from the factory with this option.

For Remote Mounted Display Faceplate

 – If operation of the 

Intelliswitch™ is to be through a Factory Ordered Remote 

Mounted Display Faceplate, see Appendix B, “Remote 

Mounted Display Faceplate.”

For Electric, Steam and Hot Water air curtains

 - proceed to 

Section VI - Field Connections

, otherwise proceed to 

Section VII - Operating Instructions

A. ELECTRICALLY HEATED MODELS

 

The heater circuit may be controlled by a remote  

 

thermostat or manually through the Intelliswitch™ 

 

located on the discharge side of the air curtain.  

 

Overheating protection is provided by auto reset thermal  

cutouts built into the heater coil assembly 

 

(see the wiring diagram located in the junction box). 

 

See Figure 7.

FIGURE 7 - Electrical Connections

Junction Box

Hinged Bottom 

Access Cover 

Summary of Contents for AHD10

Page 1: ...ING INSTRUCTIONS 7 INTELLISWITCH QUICK START OPERATION 9 FAQ s FREQUENTLY ASKED QUESTIONS 11 VIII MAINTENANCE AND CLEANING 8 IX SERVICE 8 X TROUBLESHOOTING 13 XI APPENDIX A SERIAL NETWORK CONNECTION P...

Page 2: ...aving jurisdiction including fire rated construction See page 6 ELECTRICAL CONNECTIONS NEC Code ANSI NFPA No 70 E When cutting or drilling into wall or ceiling do not damage electrical wiring and othe...

Page 3: ...ace add locking screws 2 Locking Screws One In Each Corner Mounting Plate 45 Lip and Rubber Vibration Gasket Discharge Nozzle Before hanging check to see what the clearance is above the door 6 minimum...

Page 4: ...rway a door opening device etc the effectiveness of the air curtain will be greatly reduced See Figure 2 B For optimum performance the bottom of the air curtain discharge nozzle should be no more than...

Page 5: ...2 Lower the unit into place allowing it to rest on the lower lip of the mounting plate 3 After the unit is securely attached to the mounting plate re install the two 2 locking screws at the bottom cor...

Page 6: ...e temperature is to be measured the sensor may be left on the endplate or positioned elsewhere Do not put any clamps on the rubber coated tip D Remove the junction box cover E Connect all supply and c...

Page 7: ...ts will have the fans activated by a door switch or sensor The unit speed can be selected from the Intelliswitch display 3 Heated units will have fans activated by a door switch or sensor but may also...

Page 8: ...ps head screws on the bottom of the unit Vacuum and scrape if necessary to remove the build up of dirt and debris The motor s are permanently lubricated and require no additional lubrication Re instal...

Page 9: ...to run after the door closes Start Time Programmable time of day air curtain becomes active Stop Time Programmable time of day air curtain stops running T Stat Mode Set only heat or heat fan Set Time...

Page 10: ...ir curtain turns off Door opens The air curtain activates Door shuts The air curtain continues to run Door opens The air curtain is off Door shuts The air curtain is off OFF 5 Standard Mode of Operati...

Page 11: ...e panel and lock the service disconnecting means to prevent power from being switched on accidentally When the service disconnecting means cannot be locked securely fasten a prominent warning device s...

Page 12: ...curtain is heated make sure that the thermostat isn t wired to the door switch leads Door switch leads are blue and labeled 9 10 Q How can I check the door switch to be sure it s working A The Intelli...

Page 13: ...FANS ARE NOT ROTATING MINIMUM AIR ELECTRICAL CONTROLS NOT FUNCTIONING WHEN DOOR IS OPEN SYMPTOMS REMEDY CAUSE Broken or damaged flexible hub Shaft rotating inside fan Selector switch is in off positio...

Page 14: ...operated in a network there are three options available under the Programming Menu that manage how they interact with each other Door Switch door Thermostat temp Stand By Stby Each option can be set t...

Page 15: ...PURE mode operation When the door opens The air curtain and if applicable the heater s activate and run at set speed When the door closes for heated models The PURE mode allows for the air curtain to...

Page 16: ...iability for repairs made outside its factory without proper written consent from its service manager nor for any transportation charges on apparatus returned to the factory without written authorizat...

Reviews: