-12-

heat should shut off when the wires are separated. 

For more complex troubleshooting of either thermal cutouts or 

heater contactors, please consult a qualified electrician or the 

factory.

Q. Why didn’t the Intelliswitch™ save the changes I made to 

a program?

A.

  If a program is active (a dot is illuminated by one of the 

clock digits), changes can be made to any settings on the User 

Menu. These changes however will only remain in effect until 

the program changes to the next time zone. To make changes 

permanent, settings must be changed in the program from the 

Program Menu. Access the Program Menu by holding down the 

left arrow for 5 seconds until “PRO” is displayed. Arrow down 

to select programming and arrow left to select the program to 

edit. Use the down arrow to step through the options and make 

changes as desired. Continue to press the down arrow until Stor 

is displayed. Press OK or down to keep or store the changes.

Q. How do I undo a change that I made to a program in the 

Program Menu?

A. 

 Changes to programs cannot be undone. The programs can 

however be reset to the factory default settings. This must be 

done on the Factory Menu. Access to the Factory Menu is at-

tained through the Diagnostics Menu. Press and hold the right 

arrow for 5 seconds until “DIAG” is displayed. From the “DIAG” 

display press and hold the up and down simultaneously for 10 

seconds until “FACT” is displayed. Use the down arrow to select 

“DEFn” on the display then use the right arrow to select “DEFP”. 

Press “OK” to reset. The control display will go blank then blink 

as confirmation.

Q. My air curtain won’t turn on?

A.

   Check the AM/PM setting on the Start and Stop times or the 

clock (considering the AM indicator light whensetting values). 

Note: set the start time and stop time to the exact time for the 

unit to be active full time. Check to see if a program is active 

that may have different start/stop times than those expected.

Q. My building has a Building Management System, can the 

Intelliswitch work with a BMS?

A.

  The Intelliswitch can be controlled by a Building Manage-

ment System (BMS) but currently does not have the ability to 

communicate with them. Dry contacts on the BMS may be used 

to control the unit activation through the door switch connec-

tions (blue wires 9 & 10) and the heat activation thought the 

remote thermostat connections (orange wires 6 & 7). Consult 

factory.

any mode that is activated by the door switch.

5.) If the air curtain is heated, make sure that the thermostat 

isn’t wired to the door switch leads. Door switch leads are blue 

and labeled 9 & 10.

Q.  How can I check the door switch to be sure it’s working?

A.

 The Intelliswitch™ may be in the wrong mode, be mis-wired 

or have a faulty door switch.

1.) Test the wiring and controller function at the same time first. 

Locate the door switch and open its wiring compartment by re-

moving the two screws holding on the back cover. There should 

be two wires connected to screws inside the switch. There is no 

danger of getting shocked because the signal is 5 volt dc. Be 

sure not to touch the wires to anything metal (or grounded). 

Either disconnect both wires from the screws (noting which 

screws the wires are under) and touch them together (with air 

curtain in “Auto” mode) or make a short jumper wire and touch 

the jumper to both screws at the same time to see if air curtain 

comes on. If it does, the controller and wiring work.

2.) If the wiring and unit pass the function test, the problem 

could be either misalignment or a faulty door switch. On a 

magnetic reed switch check for magnet alignment, for plunger/

roller type switch, check contact engagement with door.

3.) If you have access to an electrical test meter, the door switch 

contacts can be tested for continuity when the door switch 

wires are disconnected from the unit.

Q.  Why won’t my heat shut off?

A.

  The Intelliswitch may need adjusted, have been mis-wired or 

have a faulty thermostat.

1.) Heat is activated by one of two thermostat connections. 

To test the internal thermostat set the external thermostat to 

OFF. The settings of the unit mounted thermostat probe are 

accessed through the display. Press the down arrow until the 

Temp Set indicator lights up; check if the temperature setting 

and unit of measure are correct. Test to see if it shuts off by set-

ting the thermostat temperature to OFF or lower than the room 

temperature.

2.) If an external thermostat is connected to the unit, there 

could be a short in the field connections or the thermostat 

leads may be mis-wired. To test the external thermostat set the 

internal thermostat to OFF. Disconnect the external thermostat 

connections at the unit. Open the wiring tray on top of the unit 

and be cautious of high voltage connections. Disconnect the 

orange wires labeled 6 & 7 from the field wiring to the thermo-

stat or make sure they are not tied together. There is no danger 

of getting shocked because the signal is 5 volt dc. Be sure not 

to touch the orange wires to anything metal (or grounded). The 

INTELLISWITCH™ FAQ’s Continued (Frequently Asked Questions)

www.Berner.com/intelliswitch

Summary of Contents for AHD10

Page 1: ...ING INSTRUCTIONS 7 INTELLISWITCH QUICK START OPERATION 9 FAQ s FREQUENTLY ASKED QUESTIONS 11 VIII MAINTENANCE AND CLEANING 8 IX SERVICE 8 X TROUBLESHOOTING 13 XI APPENDIX A SERIAL NETWORK CONNECTION P...

Page 2: ...aving jurisdiction including fire rated construction See page 6 ELECTRICAL CONNECTIONS NEC Code ANSI NFPA No 70 E When cutting or drilling into wall or ceiling do not damage electrical wiring and othe...

Page 3: ...ace add locking screws 2 Locking Screws One In Each Corner Mounting Plate 45 Lip and Rubber Vibration Gasket Discharge Nozzle Before hanging check to see what the clearance is above the door 6 minimum...

Page 4: ...rway a door opening device etc the effectiveness of the air curtain will be greatly reduced See Figure 2 B For optimum performance the bottom of the air curtain discharge nozzle should be no more than...

Page 5: ...2 Lower the unit into place allowing it to rest on the lower lip of the mounting plate 3 After the unit is securely attached to the mounting plate re install the two 2 locking screws at the bottom cor...

Page 6: ...e temperature is to be measured the sensor may be left on the endplate or positioned elsewhere Do not put any clamps on the rubber coated tip D Remove the junction box cover E Connect all supply and c...

Page 7: ...ts will have the fans activated by a door switch or sensor The unit speed can be selected from the Intelliswitch display 3 Heated units will have fans activated by a door switch or sensor but may also...

Page 8: ...ps head screws on the bottom of the unit Vacuum and scrape if necessary to remove the build up of dirt and debris The motor s are permanently lubricated and require no additional lubrication Re instal...

Page 9: ...to run after the door closes Start Time Programmable time of day air curtain becomes active Stop Time Programmable time of day air curtain stops running T Stat Mode Set only heat or heat fan Set Time...

Page 10: ...ir curtain turns off Door opens The air curtain activates Door shuts The air curtain continues to run Door opens The air curtain is off Door shuts The air curtain is off OFF 5 Standard Mode of Operati...

Page 11: ...e panel and lock the service disconnecting means to prevent power from being switched on accidentally When the service disconnecting means cannot be locked securely fasten a prominent warning device s...

Page 12: ...curtain is heated make sure that the thermostat isn t wired to the door switch leads Door switch leads are blue and labeled 9 10 Q How can I check the door switch to be sure it s working A The Intelli...

Page 13: ...FANS ARE NOT ROTATING MINIMUM AIR ELECTRICAL CONTROLS NOT FUNCTIONING WHEN DOOR IS OPEN SYMPTOMS REMEDY CAUSE Broken or damaged flexible hub Shaft rotating inside fan Selector switch is in off positio...

Page 14: ...operated in a network there are three options available under the Programming Menu that manage how they interact with each other Door Switch door Thermostat temp Stand By Stby Each option can be set t...

Page 15: ...PURE mode operation When the door opens The air curtain and if applicable the heater s activate and run at set speed When the door closes for heated models The PURE mode allows for the air curtain to...

Page 16: ...iability for repairs made outside its factory without proper written consent from its service manager nor for any transportation charges on apparatus returned to the factory without written authorizat...

Reviews: