Berkeley 6S Series Owner'S Manual Download Page 12

12

TROUBLESHOOTING 

PROBLEM

POSSIBLE CAUSE

REMEDY

Fuses blow or overload 

1. Pump sandlocked.

1. a) Check motor winding resistance - see "Circuit

circuit breaker trips when 

(Winding) Resistance", Page 6.

motor starts.

b) If motor is not shorted, turn on current and rap

discharge pipe sharply to loosen sand.

c) Pull pump and clean.

2. Low or high voltage.

2. Check line voltage (see Page 4). If high or low, 

contact power company.

3. Cable damaged or shorted.

3. Check pump cable for ground (see Page 6).

4. Pump forced into crooked well.

4. Forcing pump into a crooked hole will cause mis-

alignment of pump and motor. Consult well driller.

Fuses blow or overload 

1. Low or high voltage.

1. Check voltage on service lines (see Page 4).

trips while motor is running.

2. Water contains abrasives.

2. If water contains excessive sand, remove pump 

and clean sand out of well.

3. Motor or cable shorted and/or 

3. See "Circuit (Winding) Resistance Test" and  

grounded.

"Ground Check", Page 6.

Motor does not start but 

1. Fuses blown or circuit breaker 

1. Reset circuit breakers or replace fuses.

does not blow fuses or 

tripped.

trip circuit breaker.

2. Voltage does not reach terminals.

2. 3-Phase: Check voltage at controller between wire 

pairs: L1 – L3, L3 – L2, L2 – L1. 
Single Phase: Check voltage between L1 and L2 on 
box terminal strip.

3. Loose wire in control box.

3. Check and tighten all wires.

4. Defective magnetic controller coil.

4. Check starter and coil.

Pump does not shut off.

1. Cable leads improperly connected.

1. Check wiring diagram on box cover for correct 

connections.

Motor runs, but delivers 

1. Horizontal line check valve 

1. Reinstall correctly.

little or no water.

installed backwards.

2. Motor running backwards 

2. Reconnect motor for proper rotation (see Page 3).

(3-Phase only).

3. Pump gaslocked.

3. Start and stop pump several times allowing one 

minute between stops and starts.

4. Water level in well has dropped.  

4. a) Restrict pump flow to equal well production.

b) Install liquid level control. 
c) Reset pump lower in well.

5. Leak in discharge pipe.

5. Raise pipe until leak is found.

6. Coupling between motor shaft 

6. remove pump from well and check coupling.

and pump shaft broken.

7. Pump parts worn from abrasives.

7. a) Check pump shut-off pressure. Pressure should 

be at least 90% of pressure at installation.

b) Replace worn parts.

8. Intake screen clogged.

8. Remove pump from well and clean screen.

9. Pump set below recommended 

9. a) Reduce pressure switch setting until pump will

depth.

shut off.

b) Install pump producing higher pressure.

10. Discharge pipe friction reduces

10. Install larger pipe or pump producing higher pressure. 

output.

Hazardous voltage. Can shock, burn, or

kill. When troubleshooting or servicing pump, use all
normal precautions for the voltages involved. 

1.

Disconnect power unless required for testing.

2.

Have electrical testing done by a qualified 
electrician.

3.

Most problems occur above ground. Remove pump
from well only as a last resort.  

Summary of Contents for 6S Series

Page 1: ...nt wear and reduce pump capacity and discharge pressure Never use the pump to develop or clean the well Permanent pump damage can result within the first few hours of operation If the well casing is s...

Page 2: ...Insert wires into connector until insulation butts up against connector Crimp connector to wires with a pair of crimping pliers Pull on cable to make sure the connection is solid and tight 2 SPECIFIC...

Page 3: ...the leak is in the splice 4 If leak is not in splice slowly pull cable out of water until reading changes to infinity Reading will change to infinity when leak comes out of water 5 Repair cable by spl...

Page 4: ...alified electricians should perform these tests When testing use all normal precautions for the voltages involved Electrical test of motor cable connections The cable and splices can be damaged as the...

Page 5: ...s L3 53 Amps L3 52 Amps L3 51 Amps Total 150 Amps Total 150 Amps Total 150 Amps B Divide each total by three to get average amps Example 150 3 50 Example 150 3 50 Example 150 3 50 C For each hookup fi...

Page 6: ...not be freed disconnect pump from motor disassemble liquid end see Page 7 and backwash sand from each part Checking Pump Performance Water containing abrasives can cause impeller wear and reduce impel...

Page 7: ...s 28 and 27 and remove the straps 4 Gently tap the Discharge Key No 24 and remove it 5 Gently tap the Guide Housing Key No 9 and remove it 6 Loosen the M8 Allen Screw in the top of the Shaft Key No 6...

Page 8: ...ntly tapping it with a rubber mallet 9 Slide an Impeller Key No 11 over the Shaft until it rests on the Guide Sleeve Key No 8 10 Slide the first Stage Casing Key No 12 over the Shaft and seat it on th...

Page 9: ...ns Number of Number of Stages Guide Housings Required 0 12 0 13 24 1 at Midpoint of Shaft 25 37 2 at 1 3 and 2 3 Length of Shaft Space Intermediate Guide Housings evenly 9 PREVENTIVE MAINTENANCE To av...

Page 10: ...1 12 13 31 32 8 16 15 11 14 11 17 18 19 20 21 6 9 22 25 26 2 1 32 31 32 24 23 12 5 8 9 27 28 32 29 13 12 13 25 30 30 121 20 48 5 43 5 9 25 4 25 121 20 121 30 121 20 121 30 121 20 Assembly Fixture 3367...

Page 11: ...Standard Guide Housing 2 10 Suction Stage Plate 1 11 Impeller 12 Stage Casing 13 Diffuser 14 Standard Stage Plate 15 IGH Stage Plate 16 Intermediate Guide Housing IGH 17 Discharge Stage Plate 1 18 Sp...

Page 12: ...agnetic controller coil 4 Check starter and coil Pump does not shut off 1 Cable leads improperly connected 1 Check wiring diagram on box cover for correct connections Motor runs but delivers 1 Horizon...

Reviews: