33
USER
menu
Par
No Description
Range
Fac-
tory
setting
UM
0000
0003 Sets the desired flow temperature with heating mode. Active
for the heating mode Par. 2001 = 0 o 3
Par. 2023…Par.
2024
70
°C
0048 Establishes the DHW storage tank set-point Par. 2035 in
mode 2.
40…71
50
°C
0200
Activates the test mode:
off = test mode off
fan = the fan is running at the max speed with the burner off
lo = module is brought to min (when on)
ign = module is brought to the ignition speed (when on)
Hi = the module is brought to the max (when on)
reg = the module is brought to the max power but it is set
according to the temperature (when on)
off/fan/lo/ign/hi/
reg
Off
0901 It defines the temperature units
C/F
C
0902 It defines the pressure units
bar/psi
bar
1000
1001 CH flow temperature
Only display
°C
1002 Domestic hot water temperature
Only display
°C
1004 Outdoor temperature
Only display
°C
1006 Flue gas temperature
Only display
°C
1007 Flue gas temperature
Only display
°C
1008 Ionisation current
Only display
μA
1009 Status of the primary pump (on/off)
Only display
1010 Status of the heating system pump (on/off)
Only display
1011 Status of the DHW pump (on/off)
Only display
1012 Calculated heating set point (on climatic mode)
Only display
°C
1013 Status of the room thermostat/heat demand (opened/closed)
Only display
1015 Secondary probe temperature (if on)
Only display
°C
1031 Error code
Only display
1040 Actual fan speed
Only display
RPM
1041 Ignition fan speed
Only display
RPM
1042 Fan speed at the minimum
Only display
RPM
1043 Fan speed at the maximum
Only display
RPM
1051 Code of the last permanent error
Only display
1052 Code of the last temporary error
Only display
1054 Number of successful ignitions
Only display
1055 Number of failed ignitions
Only display
1056 Total heating hours
Only display
Hr x 10
1057 Total Sanitary hours
Only display
Hr x 10
1058 Total working days
Only display
Days
1059
Time delay from the last Permanent error
The measuring unit is defined by the number preceding the
value.
1: = minutes
2: = hours
3: = days
4: = weeks
Only display
1060
Time delay from the last Temporary error
The measuring unit is defined by the number preceding the
value.
1: = minutes
2: = hours
3: = days
4: = weeks
Only display
1062 Water flow of the present module
Only display
from/
min
1063 Signal voltage 0-10 on inlet
Only display
Volt
1098 Scheme type
Only display
1099 Software version identification code
Only display
Code
---> Enter menu password INSTALLER / MANUFACTURER