36
2000
2092 Defines the number of fan rpm at max. power (it depends on
the model and is defined at Par. 9098).
0…12750
De-
fined
by
Par.
9098
RPM
2093 Defines the number of fan rpm at minimum power (it de-
pends on the model and is defined at Par. 9098).
0…12750
De-
fined
by
Par.
9098
RPM
2094 Defines the fan speeds on the module start up (depending
on the model defined on Par. 9098).
0…12750
De-
fined
by
Par.
9098
RPM
2109 Defines the offset of the calculated set point on climatic
mode (Par. 2001= 1). Makes a climatic curve compensation.
Off, -10…10
0
2110 Sets the minimum delivery temperature value in heating
mode (Par. 2001) = 4.
20…50
30
°C
2111 Sets the maximum delivery temperature value in heating
mode (Par. 2001) = 4.
50…90
80
°C
2112 Sets the value in degrees below the set-point at which the
burner switches on again for thermoregulation.
0…20
5
°C
2113 Defines the domestic hot water circuit's % max. power.
50…100
100
%
2114 Defines the domestic hot water circuit's % minimum power.
1…30
1
%
2115 Defines the Accumulation sanitary Setpoint in mode 1
40…71
50
°C
2116 The value of this parameter is defined by Par. 9097.
0 Disabled 1 Water
pressure sensor 2
CH flow switch 3 Flue
pressure switch
De-
fined
by
Par.
9097
2117 The value of this parameter is defined by Par. 9097.
0 Disabled 1 DHW
flow sensor 2 DHW
flow switch 3 CH flow
sensor
De-
fined
by
Par.
9097
2118 The value of this parameter is defined by Par. 9097.
0 Disabled 1 Drain
switch 2 Gas pres-
sure switch
De-
fined
by
Par.
9097
2120 The value of this parameter is defined by Par. 9097.
0 Disabled 1 T_Re-
turn sensor 2 Extern
switch
De-
fined
by
Par.
9097
2121 The value of this parameter is defined by Par. 9097.
0 Disabled 1 T_Flue
sensor 2 Flue switch
3 APS switch
De-
fined
by
Par.
9097
2122 The value of this parameter is defined by Par. 9097.
0 Disabled 1
T_Flue_2 sensor 2
T_ Bl. Flue
3 T_System sensor 4
Blocked Flue switch 5
Cascade Sensor
De-
fined
by
Par.
9097
2123 The value of this parameter is defined by Par. 9097.
0 Disabled 1 T_DCW
sensor 2 Water pres-
sure switch
De-
fined
by
Par.
9097
2124 The value of this parameter is defined by Par. 9097.
0 Disabled 1 Enabled
De-
fined
by
Par.
9097
2125 The value of this parameter is defined by Par. 9097.
0 Disabled 1 General
Pump 2 CH Pump 3
DHW Pump 4 System
Pump 5 Cascade
Pump 6 Alarm Relay
7 Filling Valve 8 LPG
Tank 9 External Ignit-
er 10 Air Damper 14
Alarm Burner CC 15
Status Burner CC 17
Antilegionella pump
De-
fined
by
Par.
9097