28
MYNUTE X R
DAY
8.6
Reset function
The “RESET” icon comes on when there is an alarm that requires a manual reset by the user
(for example flame lockout).
To reset the lockout press key 2 RESET.
DAY
RESET
If the release attempts do not restart the boiler, contact your local Technical Assistance
Centre
.
8.7
Time band scheduling function (room thermostat)
If the heating system is managed by a room thermostat, and therefore without programming
timing, the programming timing on the boiler interface can be enabled by setting in the CH
menu the parameter POR = 1.
To access the programming timing menu press the keys
B
+
D
for at least 2sec.
RESET
+
MENU
+
D
B
The displays appears as in the following figure:
Using the
,
arrows select the day or the pre-selected group of days:
1-2-3-4-5-6-7 programming the individual days
1-5 programming from Monday to Friday
6-7 programming from Saturday to Sunday
1-7 programming the entire week
With the
key you confirm the selection made and you pass to the programming of the
time bands, with the
Enter
key you exit the programming timing menu confirming the
changes made.
With the key you exit without saving the selections.
Setting the Time Bands
- The display shows TIME ON, press to set the ignition time, with
,
change
the time, confirm with
.
- The display shows TIME OFF, press to set the switching off time, with
,
change the time, confirm with
.
- Open TIME ON again, then the programming of the time bands is resumed up to the
maximum number of programmable bands (four), or else press
Enter
to confirm the bands
set and you move on to the programming of the next day.
For each day of the week it is possible to programme up to 4 bands, each one having a start
time and an end time.
Outside these time bands, heat requests from the room thermostat are ignored.
The central heating time bands enabled by default are:
07:30 - 08:30 / 12:00 - 13:30 / 18:00 - 22:30 from MON to FRI
08:00 - 22:30 from SAT to SUN.
When heating programming timing is enabled pressing the keys
C
+
D
allows you to move
from AUTO programming timing to MAN ON or MAN OFF.
RESET
+
MENU
+
D
C
9 MALFUNCTIONING (see "4.20 Lights and
faults")