background image

6

2   INSTALLATION

2.1  Cleaning the system and characteristics of water

In the case of a new installation or replacement of the boiler, it is necessary 

to clean the heating system. To ensure the device works well, top up the 

additives and/or chemical treatments (e.g. anti-freeze liquids, filming agents, 

etc.) and check the parameters in the table are within the values indicated.

PARAMETERS

udm

HEATING CIRCUIT 

WATER

FILLING 

WATER

pH value

-

7-8

-

Hardness

°F

-

<15 

Appearance

-

-

clear

Fe

mg/kg

<

0,5

-

Cu

mg/kg

<

0,1

-

The boiler must be connected to a heating system and a DHW system, 

both sized on the basis of its performance and power.

Before installation, wash every system piping carefully in order to remo

-

ve any residues that may impair the operation of the appliance.

Under  the  safety  valve,  install  a  water  collecting  funnel  with  the 

corresponding discharge in the event of leaks due to the overpressure 

of the heating system. The domestic hot water circuit does not need a 

safety valve, but make sure that the pressure of waterworks does not 

exceed 6 bar. In case of doubts, install a pressure reducer.

 

b

Prior to ignition, make sure that the boiler is designed to operate 

with the gas available; this can be checked by the wording on the 

packaging and by the adhesive label indicating the gas type.

 

b

It is very important to highlight that in some cases the flues are un

-

der pressure, so the joints of the various elements must be airtight.

2.2  Installation regulations

The installation must be carried out by qualified personnel, in compliance 

with the following reference standards: UNI 7129-7131 and CEI 64-8.

 

b

During boiler installation the use of protective clothing is 

recommended, in order to avoid personal injury.

Always  comply  with  local  standards  of  the  Fire  Department,  the  Gas 

Company and with possible municipal dispositions.

POSITION

This type C condensation boiler is designed for heating and domestic 

hot water production. There are two categories, depending on the type 

of installation:

1. 

B23P-B53P boiler type - forced open installation, with flue gas discharge 

pipe and pickup of combustion air from the installation area. If the boiler 

is not installed outdoors, air intake in the installation area is compulsory

;

2. 

C13,C13x;  C33,C33x;  C43,C43x;  C53,C53x;  C83,C83x,  C93,C93x 

boiler type: appliance with airtight chamber, with flue gas discharge 

pipe and pick-up of combustion air from outside. It does not require an 

air intake point in the installation area.

The appliance can be installed indoors (

fig. A

) or outdoors (but in a partially 

protected place (

fig. B

) where it is not directly exposed to rain, snow or hail). 

It can work within a temperature range from >0°C to +60°C.

fig. B

fig. A

ANTI-FREEZE SYSTEM

The boiler is fitted as standard with an automatic anti-freeze system that acti

-

vates when the temperature of the water in the primary circuit falls below 5°C. 

This system is always active and provides protection for the boiler up to an air 

temperature in the installation area of 0°C.

To take advantage of this protection (based on burner operation), the boiler 

must be able to switch itself on; any lockout condition (for ex. due to a lack of 

gas or electrical supply, or the intervention of a safety device) therefore deacti

-

vates the protection.

In normal operating conditions, the boiler can protect itself against frost

You are advised to add a good quality anti-freeze liquid to the primary circuit 

(respecting the manufacturer’s indications) if the temperature falls below 0°C, 

with the electricity supply disconnected and the heating system full. 

For the hot domestic water part, we recommend you drain the circuit

.

The boiler component materials are resistant to ethylene glycol based antifreeze 

liquids.

MINIMUM DISTANCES

To ensure access to the boiler for normal maintenance operations, respect the 

minimum installation clearances envisaged.

For correct appliance positioning, bear in mind that

:

 - it must be installed on a wall that can support its weight

 - it must not be placed above a cooker or other cooking device

 -

it is forbidden to leave inflammable products in the room where the boiler is 

installed

 - heat-sensitive walls (e.g. wooden walls) must be protected with proper in-

sulation.

measured in mm

°C

5

0

8

.

2.3  Access to the electrical components

3

2.4  Electrical connections

Low voltage connections

CE4 connector: 

use 4-poles connector, supplied as standard, for connections 

with ModBus 485 signal. Once the operations have been completed, place the 

connector correctly in its counterpart.

 

b

We recommend using conductors with a section no larger than

 0,5 mm

2

.

4-poles 

ModBus

connector (CE4)

- A B +

Connection on the main board: 

make the TA (ambient thermostat), OT+ 

and SE (external sensor) connections on X11 connector - see diagram “7.5 

Multiwire electrical diagram”.

NOTE: 

when an OT+

 remote control is connected to the system, if parameter

 

803= 1 (SERVICE), 

the boiler display shows the following screen:

o

t

o

t

Summary of Contents for 20183151

Page 1: ...C 5 0 8 Ciao EN INSTALLER AND USER MANUAL RO MANUAL DE INSTALARE I UTILIZARE...

Page 2: ...at requirements of the system and in fact it is possible to set the range rated parameter as shown in the specific paragraph After setting the desired output report the value in the table on the back...

Page 3: ...to harm hu man health and without employing procedures or methods which may damage the environment At the end of its life the product should be not be di sposed of as solid urban waste but rather it...

Page 4: ...Hz 230 50 230 50 Protection level IP X5D X5D Stop loss W 30 32 Losses at the flue with burner off burner on 0 09 2 80 0 08 2 26 Heating operation Maximum pressure bar 3 3 Minimum pressure for standard...

Page 5: ...Countries contained in the data plate regardless of the present translation language NOTE with reference to the Delegated Regulation EU No 811 2013 the information in the table can be used for comple...

Page 6: ...ipe and pick up of combustion air from outside It does not require an air intake point in the installation area The appliance can be installed indoors fig A or outdoors but in a partially protected pl...

Page 7: ...Ifremovingthesidepanels putthembackintheirinitialposition referring to the adhesive label on its wall b If the front panel is damaged it must be replaced b The noise absorbing panels inside the front...

Page 8: ...length that can be installed ONLY with class H1 discharge pipes The 50 or 60 or 80 configurations contain Lab test data In the event of installations that differ from the indications in the standard...

Page 9: ...REQUEST FROM OT CHRONOTHERMOSTAT In this case the delivery setpoint is calculated by chronohermostat on the basis of the external temperature value and the difference between the real ambient temperat...

Page 10: ...Combustion control sequence 1 4 5 2 3 Installer manual QR fumes adaptor 90 80 70 60 50 40 30 20 10 Temperatura di mandata C Temperatura esterna C 20 15 10 5 0 5 10 15 20 RIDUZIONE NOTTURNA PARALLELA C...

Page 11: ...minimum fan speed 307 maximum fan speed 308 slow ignition 309 maximum fan speed for heating table 3 MAX NO FAN ROTATIONS METHANE GAS G20 LPG G31 25C f CH DHW 7 000 8 700 6 900 8 500 rpm 30C f CH DHW 7...

Page 12: ...s 2 sec Res If the correct operating conditions have been restored the boiler will start up again automatically In the presence of a remote control a maximum of 5 consecutive unlocking attempts are av...

Page 13: ...the heat exchanger with a soft bristled brush DO NOT USE METAL BRUSHES THAT COULD DAMAGE THE COM PONENTS Clean the spaces between the coils using a 0 4 mm thick blade also available in a kit Vacuum a...

Page 14: ...P MAIN ZONE HT 80 5 LT 45 0 INSTALLER HT 80 5 LT 45 0 417 MIN TEMP MAIN ZONE 20 MAXTEMP MAINZONE INSTALLER HT 40 LT 20 418 THERMOREGULATION MAIN ZONE 0 1 INSTALLER ifext probepresent 0 419 CURVE SLOPE...

Page 15: ...point value that can be set range 20 C 80 5 C default 80 5 C for high temperature systems range 20 C 45 C default 45 C for low temperature systems NB the value of 416 cannot be lower than 417 417 This...

Page 16: ...r make sure it is active and adjusted 20 C Bring the boiler to WINTER or SUMMER mode 6 1 Operating status Pressing key 1 the operating type switches cyclically between OFF SUMMER WINTER and then OFF a...

Page 17: ...output then maintained until the delivery water temperature reaches 35 C the display shows AF1 DHW anti freeze this function is activated if the temperature meas ured by the domestic hot water probe d...

Page 18: ...clusiv unor persoane calificate profesional a Produc torul nu i asum r spunderea pentru eventualele daune cauzate de nerespectarea indica iilor de mai sus i sau a normelor n vigoare n anumite sec iuni...

Page 19: ...colectare corespunz toare b De eurile trebuie s fie eliminate f r riscuri pentru s n tatea uman i f r a recurge la proceduri sau la metode care ar putea cauza daune de mediu La sf r itul ciclului de...

Page 20: ...X5D Pierderi la oprire W 30 32 Pierderi la co cu arz torul stins arz torul aprins 0 09 2 80 0 08 2 26 Func ionare pentru circuitul de nc lzire Presiune maxim bari 3 3 Presiune minim pentru func ionar...

Page 21: ...punere n func iune NOT conform regulamentului delegat UE nr 811 2013 datele reprezentate n tabel pot fi utilizate pentru completarea fi ei produsului i etichetare n cazul produ selor pentru nc lzirea...

Page 22: ...er n spa iul de instalare 2 central de tip C13 C13x C33 C33x C43 C43x C53 C53x C63 C63x C83 C83x C93 C93x aparat cu carcas etan cu conduct de evacuare a gazelor arse i aspirare a aerului de ardere din...

Page 23: ...omponentele interne ndep rta i carcasa dup cum se indic n figur b Dac scoate i panourile laterale pune i le napoi n pozi ia ini ial referindu v la eticheta adeziv de pe peretele s u b Eventuala deteri...

Page 24: ...51 255 431 7 600 9 300 24 57 285 465 7 700 9 400 27 63 315 500 modelul B 7 400 8 700 0 7 35 190 7 500 8 800 4 17 85 256 7 600 8 900 7 23 115 300 7 700 9 000 10 29 145 340 7 800 9 100 13 35 175 380 7 9...

Page 25: ...IT 3 4 Setarea termoregl rii Reglarea termic func ioneaz numai cu sonda extern conectat i este activ numai pentru func ia NC LZIRE Pentru activarea TERMOREGL RII proceda i n felul urm tor seta i param...

Page 26: ...loare de referin de alimentare n ap de 20 C ulterior cresc nd conform tabelului de mai jos ZI OR TEMPERATUR 1 0 20 C 6 22 C 12 24 C 18 26 C 2 0 28 C 12 30 C 3 0 32 C 4 0 35 C 5 0 35 C 6 0 30 C 7 0 25...

Page 27: ...tur de 95 C arz torul se opre te Reaprinde rea va avea loc atunci c nd aceast temperatur va cobor sub 75 C b Func ia de analiz a arderii este efectuat n mod normal cu vana cu trei c i setat pe nc lzi...

Page 28: ...unc ionarea n modul de nc lzire alimenta i centrala seta i parametrul 310 Gama nominal Range rated Seta i valoarea maxim de nc lzire rot min i confirma i 0 0 7 rpm 0 0 7 rpm confirmare rpm MAX nregist...

Page 29: ...bar presiune ridicat veri ca i instala ia semnalizare 4 NTRE INERE I CUR ARE ntre inerea periodic este o obliga ie prev zut de normele n vigoare i este esen ial pentru siguran a randamentul i durata...

Page 30: ...t continua i cu procedurile de cur are a arz torului Cur a i arz torul cu o perie cu peri moi av nd grij s nu deteriora i panoul izolator i electrodul NU UTILIZA I PERII METALICE CARE POT DETERIORA CO...

Page 31: ...zactiva avertizarea sonor 0 avertizor sonor buzzer OPRIT 1 avertizor sonor buzzer PORNIT 301 Pentru a seta tipul de con gura ie hidraulic a centralei 0 DOAR NC LZIRE 1 ACM INSTANTANEE FLUXOSTAT 2 ACM...

Page 32: ...ntru a seta valoarea de referin maxim ce se poate seta pentru nc lzire interval 20 C 80 5 C implicit 80 5 C pentru instala ii cu temperatur ridicat interval 20 C 45 C implicit 45 C pentru instala ii c...

Page 33: ...3 Ciclul de evacuare a aerului Ulterior interfa a trece la afi area st rii active n acel moment b Regla i termostatul de mediu la temperatura dorit 20 C sau dac instala ia este dotat cu un cronotermos...

Page 34: ...men inut p n c nd temperatura apei de alimentare ajunge la 55 C pe ecran se afi eaz AF2 antiblocare circulator Pompa de circula ie se activeaz la fiecare 24 de ore timp de 30 de secunde 6 7 Oprirea p...

Page 35: ...ei c i 4 Traductor presiune 5 By pass automat 6 Sond ap cald menajer 7 Sond tur 8 Termostat limit 9 Schimb tor principal 10 Sond retur 11 Supap inferioar de aerisire 12 Vas de expansiune 13 Pomp de ci...

Page 36: ...a este deja dotat cu o pomp de circula ie cu conexiuni hidraulice i electrice a c rei performan util disponibil este indicat pe grafic Func ia anti blocare este activ numai c nd centrala termic este a...

Page 37: ...r on primary circuit S M Temperature flow sensor on primary circuit S F Flue gas sensor T L A Water limit thermostat T P Pressure transducer S S Domestic hot water circuit temperature return sensor F...

Page 38: ...85 vertical vertical 90 bend 80 125 80 125 14 12 1 1 5 130 curba 90 80 125 adaptor from 60 100 to 80 125 adaptor de la 60 100 la 80 125 adaptor vertical connection 80 100 adaptor vertical conexiune 8...

Page 39: ...tabelul pentru ac iuni mai imediate bar rpm C 1 88 8 sau or sau or Actions Sequence password entry points 1 7 parameter choice points 8 10 modify and confirm parameter points 11 12a exit without savin...

Page 40: ...813 2013 Reglementare delegat UE nr 814 2013 CIAO boiler complies with basic requirements of the following Di rectives Regulation UE 2016 426 Efficiency directive Article 7 2 and Annex III of directi...

Reviews: