4.2  Parameters description

Some of the following functions may not be available depending on the machine type and access level.

PARAMETER DESCRIPTION

004

To change the measurement unit: 0 = METRIC measurement units / 1 = not available on this model

006

To enable/disable the acoustic signal 0 = buzzer OFF / 1 = buzzer ON

301

To set the type of hydraulic confi guration for the boiler: 0 = HEATING ONLY - 1 = INSTANTANEOUS FLOW SWITCH - 2 = INSTANTANEOUS FLOW METER 

3 = STORAGE TANK WITH PROBE - 4 = STORAGE TANK WITH THERMOSTAT

306

To alter the minimum number of fan rotations.

307

To alter the maximum number of fan rotations.

308

To regulate slow ignition.

309

To alter the maximum number of fan rotations in heating mode.

310

To modify the heating output in heating mode. The factory value for this parameter is 309 but it can be programmed within the range 

306 - 309

.

For more details about the use of this parameter, refer to paragraph “3.12 Range rated”.

311

To confi gure the operation of a supplementary relay (only if board BE09 (accessory kit) is installed) in order to bring a phase (230V AC) to a second heating pump 

(supplementary pump) or to a zone valve. The factory value for this parameter is 0, but it can be programmed within the range 0 - 2 with the following meaning: 

311= 0 - control depends on the confi guration of the wiring of the BE09 board (jumper cut: supplementary pump - jumper present: zone valve)

311= 1 - control of the zone valve

311= 2 - control of the supplementary pump

312

This parameter is used to reset the operating hours counter in certain conditions (for more details, see “3.13 Faults and reporting, fault A91).

The factory value for this parameter is 0. Bring the value to 1 to reset the fl ue gas probe hour counter after the cleaning of the primary heat exchanger.

When the reset procedure has been completed, the parameter will return automatically to 0.

409

This parameter is used to activate the screed heater function (refer to paragraph “3.7 Screed heater” for more details).

The factory value is 0. With the boiler OFF, set the value at 1 to activate the screed heater function on the low temperature heating areas.

The parameter returns automatically to 0 when the screed heater function ends, but the function can be interrupted by manually setting the value at 0.

410

This parameter is used to modify the forced heating off timer with regards the delay time for re-igniting the burner if it is OFF because the heating temperature has been 

reached. The factory value for this parameter is 3 minutes but it can be se t within a range from 0 min to 20 min.

411

This parameter is used to annul the HEAT TIME RESET function and REDUCED MAX. HEATING POWER TIMER, during which the fan speed is limited to a range between 

minimum and 60% of the max. heating output set, with a 10% increase every 15 minutes. The factory value for this parameter is 0. Bring the value to 1 to reset the timers.

415

This parameter is used to specify the type of area to be heated. Choose from the following options: 

0 = HIGH TEMPERATURE (factory setting)

1 = LOW TEMPERATURE

416

This parameter is used to specify the maximum heating setpoint value that can be set:

range 20°C - 80.5°C, default 80.5°C for high temperature systems 

range 20°C - 45°C, default 45°C for low temperature systems

NB: the value of 

416 cannot be lower than 417.

417

This parameter is used to specify the minimum heating setpoint value that can be set:

range 20°C - 80.5°C, default 40°C

 for high temperature systems

range 20°C - 45°C, default 20°C for low temperature systems

NB: the value of 

417 cannot be higher than 416.

418

This parameter is used to activate temperature control when the system is connected to an external probe. With the factory value of 0, the boiler always works with a fi xed 

point. If the parameter is set at 1 and an external probe is connected, the boiler works in thermoregulation mode. If the external probe is disconnected, the boiler always 

works with a fi xed point. See paragraph “3.4 Setting the thermoregulation” for more details about this function.

419

This parameter is used to set the number of the compensation curve used by the boiler in thermoregulation mode.

The factory value for this parameter is 2.0 for high temperature systems and 0.5 for low temperature systems. 

The parameter can be programmed within the range 1.0 - 3.0 for high temperature systems, or 0.2 - 0.8 for low temperature systems.

See paragraph “3.4 Setting the thermoregulation” for more details about this function.

420

This parameter activates the “night-time compensation” function. The default value is 0. Set at 1 to activate the function.

See paragraph “3.4 Setting the thermoregulation” for more details about this function.

432

Building type

433

External probe reactivity 

508

To set the minimum DHW setpoint

509

To set the maximum DHW setpoint

511

Enabling of special DHW functions: 0 = no function - 1 = fl ow switch/fl ow meter start-up delay

2 = with OFF due to overtemperature in DHW mode (with request in progress), the fan is kept at the switch-on speed to reduce the waiting time on restart

3 = absolute DHW thermostats - 4 = smart anti-oscillation DHW function - 5 = all four previous functions active

02

iI

0

04

iI

0

05

iI

0

01

3

access to info menu

choise info

or

access to 

parameter value 

back to the previous level

4.3  INFO menu 

 

b

The interface 

automatically 

quits the info 

menu if no key 

is pressed for 

60 sec.

PARAMETER 

NAME

DESCRIPTION

I001

Screed heater hours

Number of hours of screed heater function activation 

I002

Delivery probe

Boiler delivery probe value 

I003

Return probe

Boiler return probe value 

I004

DHW probe

DHW probe value with boiler in instantaneous mode 

I005

OT+ DHW setpoint

DHW setpoint sent by OT+ remote control to the boiler

I008

Flue gas probe

Flue gas probe value

I009

External probe

Instantaneous external probe value

I010

External temperature for thermoregulation

Filtered external probe value used in the temperature control algorithm to calculate 

the heating setpoint 

I011

DHW fl ow rate

DHW setpoint (only with OT+ connection)

I012

Fan rotations

Number of fan rotations (rpm) 

I013

Flow sensor (main zone)

Value of the main zone fl ow sensor (when P4.12 = 1) 

I015

Flue gas probe counter

Number of operating hours of the heat exchanger in “condensing mode” 

I016

Delivery setpoint (main zone)

Delivery setpoint for the main zone

I017

OT+ CH setpoint

Heating setpoint sent by the OT+ timed thermostat to the boiler

I018

System pressure

System pressure level 

I032

DHW comfort

DHW comfort mode 

I033

Special DHW functions

Special functions active for high DHW inlet temperatures

I034

ID board

Identifi cation of the electronic board

I035

FW board revision

Firmware revision of the electronic board

I038

WIFI pendrive radio signal

Indicates the quality of the WIFI connection

I039

ALARM LOG 1  (the oldest)

List of the last fi ve alarms recorded

I040

ALARM LOG 2

I041

ALARM LOG 3

I042

ALARM LOG 4

I043

ALARM LOG 5 (the latest)

Summary of Contents for 20183151

Page 1: ...C 5 0 8 Ciao EN INSTALLER AND USER MANUAL RO MANUAL DE INSTALARE I UTILIZARE...

Page 2: ...at requirements of the system and in fact it is possible to set the range rated parameter as shown in the specific paragraph After setting the desired output report the value in the table on the back...

Page 3: ...to harm hu man health and without employing procedures or methods which may damage the environment At the end of its life the product should be not be di sposed of as solid urban waste but rather it...

Page 4: ...Hz 230 50 230 50 Protection level IP X5D X5D Stop loss W 30 32 Losses at the flue with burner off burner on 0 09 2 80 0 08 2 26 Heating operation Maximum pressure bar 3 3 Minimum pressure for standard...

Page 5: ...Countries contained in the data plate regardless of the present translation language NOTE with reference to the Delegated Regulation EU No 811 2013 the information in the table can be used for comple...

Page 6: ...ipe and pick up of combustion air from outside It does not require an air intake point in the installation area The appliance can be installed indoors fig A or outdoors but in a partially protected pl...

Page 7: ...Ifremovingthesidepanels putthembackintheirinitialposition referring to the adhesive label on its wall b If the front panel is damaged it must be replaced b The noise absorbing panels inside the front...

Page 8: ...length that can be installed ONLY with class H1 discharge pipes The 50 or 60 or 80 configurations contain Lab test data In the event of installations that differ from the indications in the standard...

Page 9: ...REQUEST FROM OT CHRONOTHERMOSTAT In this case the delivery setpoint is calculated by chronohermostat on the basis of the external temperature value and the difference between the real ambient temperat...

Page 10: ...Combustion control sequence 1 4 5 2 3 Installer manual QR fumes adaptor 90 80 70 60 50 40 30 20 10 Temperatura di mandata C Temperatura esterna C 20 15 10 5 0 5 10 15 20 RIDUZIONE NOTTURNA PARALLELA C...

Page 11: ...minimum fan speed 307 maximum fan speed 308 slow ignition 309 maximum fan speed for heating table 3 MAX NO FAN ROTATIONS METHANE GAS G20 LPG G31 25C f CH DHW 7 000 8 700 6 900 8 500 rpm 30C f CH DHW 7...

Page 12: ...s 2 sec Res If the correct operating conditions have been restored the boiler will start up again automatically In the presence of a remote control a maximum of 5 consecutive unlocking attempts are av...

Page 13: ...the heat exchanger with a soft bristled brush DO NOT USE METAL BRUSHES THAT COULD DAMAGE THE COM PONENTS Clean the spaces between the coils using a 0 4 mm thick blade also available in a kit Vacuum a...

Page 14: ...P MAIN ZONE HT 80 5 LT 45 0 INSTALLER HT 80 5 LT 45 0 417 MIN TEMP MAIN ZONE 20 MAXTEMP MAINZONE INSTALLER HT 40 LT 20 418 THERMOREGULATION MAIN ZONE 0 1 INSTALLER ifext probepresent 0 419 CURVE SLOPE...

Page 15: ...point value that can be set range 20 C 80 5 C default 80 5 C for high temperature systems range 20 C 45 C default 45 C for low temperature systems NB the value of 416 cannot be lower than 417 417 This...

Page 16: ...r make sure it is active and adjusted 20 C Bring the boiler to WINTER or SUMMER mode 6 1 Operating status Pressing key 1 the operating type switches cyclically between OFF SUMMER WINTER and then OFF a...

Page 17: ...output then maintained until the delivery water temperature reaches 35 C the display shows AF1 DHW anti freeze this function is activated if the temperature meas ured by the domestic hot water probe d...

Page 18: ...clusiv unor persoane calificate profesional a Produc torul nu i asum r spunderea pentru eventualele daune cauzate de nerespectarea indica iilor de mai sus i sau a normelor n vigoare n anumite sec iuni...

Page 19: ...colectare corespunz toare b De eurile trebuie s fie eliminate f r riscuri pentru s n tatea uman i f r a recurge la proceduri sau la metode care ar putea cauza daune de mediu La sf r itul ciclului de...

Page 20: ...X5D Pierderi la oprire W 30 32 Pierderi la co cu arz torul stins arz torul aprins 0 09 2 80 0 08 2 26 Func ionare pentru circuitul de nc lzire Presiune maxim bari 3 3 Presiune minim pentru func ionar...

Page 21: ...punere n func iune NOT conform regulamentului delegat UE nr 811 2013 datele reprezentate n tabel pot fi utilizate pentru completarea fi ei produsului i etichetare n cazul produ selor pentru nc lzirea...

Page 22: ...er n spa iul de instalare 2 central de tip C13 C13x C33 C33x C43 C43x C53 C53x C63 C63x C83 C83x C93 C93x aparat cu carcas etan cu conduct de evacuare a gazelor arse i aspirare a aerului de ardere din...

Page 23: ...omponentele interne ndep rta i carcasa dup cum se indic n figur b Dac scoate i panourile laterale pune i le napoi n pozi ia ini ial referindu v la eticheta adeziv de pe peretele s u b Eventuala deteri...

Page 24: ...51 255 431 7 600 9 300 24 57 285 465 7 700 9 400 27 63 315 500 modelul B 7 400 8 700 0 7 35 190 7 500 8 800 4 17 85 256 7 600 8 900 7 23 115 300 7 700 9 000 10 29 145 340 7 800 9 100 13 35 175 380 7 9...

Page 25: ...IT 3 4 Setarea termoregl rii Reglarea termic func ioneaz numai cu sonda extern conectat i este activ numai pentru func ia NC LZIRE Pentru activarea TERMOREGL RII proceda i n felul urm tor seta i param...

Page 26: ...loare de referin de alimentare n ap de 20 C ulterior cresc nd conform tabelului de mai jos ZI OR TEMPERATUR 1 0 20 C 6 22 C 12 24 C 18 26 C 2 0 28 C 12 30 C 3 0 32 C 4 0 35 C 5 0 35 C 6 0 30 C 7 0 25...

Page 27: ...tur de 95 C arz torul se opre te Reaprinde rea va avea loc atunci c nd aceast temperatur va cobor sub 75 C b Func ia de analiz a arderii este efectuat n mod normal cu vana cu trei c i setat pe nc lzi...

Page 28: ...unc ionarea n modul de nc lzire alimenta i centrala seta i parametrul 310 Gama nominal Range rated Seta i valoarea maxim de nc lzire rot min i confirma i 0 0 7 rpm 0 0 7 rpm confirmare rpm MAX nregist...

Page 29: ...bar presiune ridicat veri ca i instala ia semnalizare 4 NTRE INERE I CUR ARE ntre inerea periodic este o obliga ie prev zut de normele n vigoare i este esen ial pentru siguran a randamentul i durata...

Page 30: ...t continua i cu procedurile de cur are a arz torului Cur a i arz torul cu o perie cu peri moi av nd grij s nu deteriora i panoul izolator i electrodul NU UTILIZA I PERII METALICE CARE POT DETERIORA CO...

Page 31: ...zactiva avertizarea sonor 0 avertizor sonor buzzer OPRIT 1 avertizor sonor buzzer PORNIT 301 Pentru a seta tipul de con gura ie hidraulic a centralei 0 DOAR NC LZIRE 1 ACM INSTANTANEE FLUXOSTAT 2 ACM...

Page 32: ...ntru a seta valoarea de referin maxim ce se poate seta pentru nc lzire interval 20 C 80 5 C implicit 80 5 C pentru instala ii cu temperatur ridicat interval 20 C 45 C implicit 45 C pentru instala ii c...

Page 33: ...3 Ciclul de evacuare a aerului Ulterior interfa a trece la afi area st rii active n acel moment b Regla i termostatul de mediu la temperatura dorit 20 C sau dac instala ia este dotat cu un cronotermos...

Page 34: ...men inut p n c nd temperatura apei de alimentare ajunge la 55 C pe ecran se afi eaz AF2 antiblocare circulator Pompa de circula ie se activeaz la fiecare 24 de ore timp de 30 de secunde 6 7 Oprirea p...

Page 35: ...ei c i 4 Traductor presiune 5 By pass automat 6 Sond ap cald menajer 7 Sond tur 8 Termostat limit 9 Schimb tor principal 10 Sond retur 11 Supap inferioar de aerisire 12 Vas de expansiune 13 Pomp de ci...

Page 36: ...a este deja dotat cu o pomp de circula ie cu conexiuni hidraulice i electrice a c rei performan util disponibil este indicat pe grafic Func ia anti blocare este activ numai c nd centrala termic este a...

Page 37: ...r on primary circuit S M Temperature flow sensor on primary circuit S F Flue gas sensor T L A Water limit thermostat T P Pressure transducer S S Domestic hot water circuit temperature return sensor F...

Page 38: ...85 vertical vertical 90 bend 80 125 80 125 14 12 1 1 5 130 curba 90 80 125 adaptor from 60 100 to 80 125 adaptor de la 60 100 la 80 125 adaptor vertical connection 80 100 adaptor vertical conexiune 8...

Page 39: ...tabelul pentru ac iuni mai imediate bar rpm C 1 88 8 sau or sau or Actions Sequence password entry points 1 7 parameter choice points 8 10 modify and confirm parameter points 11 12a exit without savin...

Page 40: ...813 2013 Reglementare delegat UE nr 814 2013 CIAO boiler complies with basic requirements of the following Di rectives Regulation UE 2016 426 Efficiency directive Article 7 2 and Annex III of directi...

Reviews: