15
4.2 Parameters description
Some of the following functions may not be available depending on the machine type and access level.
PARAMETER DESCRIPTION
004
To change the measurement unit: 0 = METRIC measurement units / 1 = not available on this model
006
To enable/disable the acoustic signal 0 = buzzer OFF / 1 = buzzer ON
301
To set the type of hydraulic confi guration for the boiler: 0 = HEATING ONLY - 1 = INSTANTANEOUS FLOW SWITCH - 2 = INSTANTANEOUS FLOW METER
3 = STORAGE TANK WITH PROBE - 4 = STORAGE TANK WITH THERMOSTAT
306
To alter the minimum number of fan rotations.
307
To alter the maximum number of fan rotations.
308
To regulate slow ignition.
309
To alter the maximum number of fan rotations in heating mode.
310
To modify the heating output in heating mode. The factory value for this parameter is 309 but it can be programmed within the range
306 - 309
.
For more details about the use of this parameter, refer to paragraph “3.12 Range rated”.
311
To confi gure the operation of a supplementary relay (only if board BE09 (accessory kit) is installed) in order to bring a phase (230V AC) to a second heating pump
(supplementary pump) or to a zone valve. The factory value for this parameter is 0, but it can be programmed within the range 0 - 2 with the following meaning:
311= 0 - control depends on the confi guration of the wiring of the BE09 board (jumper cut: supplementary pump - jumper present: zone valve)
311= 1 - control of the zone valve
311= 2 - control of the supplementary pump
312
This parameter is used to reset the operating hours counter in certain conditions (for more details, see “3.13 Faults and reporting, fault A91).
The factory value for this parameter is 0. Bring the value to 1 to reset the fl ue gas probe hour counter after the cleaning of the primary heat exchanger.
When the reset procedure has been completed, the parameter will return automatically to 0.
409
This parameter is used to activate the screed heater function (refer to paragraph “3.7 Screed heater” for more details).
The factory value is 0. With the boiler OFF, set the value at 1 to activate the screed heater function on the low temperature heating areas.
The parameter returns automatically to 0 when the screed heater function ends, but the function can be interrupted by manually setting the value at 0.
410
This parameter is used to modify the forced heating off timer with regards the delay time for re-igniting the burner if it is OFF because the heating temperature has been
reached. The factory value for this parameter is 3 minutes but it can be se t within a range from 0 min to 20 min.
411
This parameter is used to annul the HEAT TIME RESET function and REDUCED MAX. HEATING POWER TIMER, during which the fan speed is limited to a range between
minimum and 60% of the max. heating output set, with a 10% increase every 15 minutes. The factory value for this parameter is 0. Bring the value to 1 to reset the timers.
415
This parameter is used to specify the type of area to be heated. Choose from the following options:
0 = HIGH TEMPERATURE (factory setting)
1 = LOW TEMPERATURE
416
This parameter is used to specify the maximum heating setpoint value that can be set:
range 20°C - 80.5°C, default 80.5°C for high temperature systems
range 20°C - 45°C, default 45°C for low temperature systems
NB: the value of
416 cannot be lower than 417.
417
This parameter is used to specify the minimum heating setpoint value that can be set:
range 20°C - 80.5°C, default 40°C
for high temperature systems
range 20°C - 45°C, default 20°C for low temperature systems
NB: the value of
417 cannot be higher than 416.
418
This parameter is used to activate temperature control when the system is connected to an external probe. With the factory value of 0, the boiler always works with a fi xed
point. If the parameter is set at 1 and an external probe is connected, the boiler works in thermoregulation mode. If the external probe is disconnected, the boiler always
works with a fi xed point. See paragraph “3.4 Setting the thermoregulation” for more details about this function.
419
This parameter is used to set the number of the compensation curve used by the boiler in thermoregulation mode.
The factory value for this parameter is 2.0 for high temperature systems and 0.5 for low temperature systems.
The parameter can be programmed within the range 1.0 - 3.0 for high temperature systems, or 0.2 - 0.8 for low temperature systems.
See paragraph “3.4 Setting the thermoregulation” for more details about this function.
420
This parameter activates the “night-time compensation” function. The default value is 0. Set at 1 to activate the function.
See paragraph “3.4 Setting the thermoregulation” for more details about this function.
432
Building type
433
External probe reactivity
508
To set the minimum DHW setpoint
509
To set the maximum DHW setpoint
511
Enabling of special DHW functions: 0 = no function - 1 = fl ow switch/fl ow meter start-up delay
2 = with OFF due to overtemperature in DHW mode (with request in progress), the fan is kept at the switch-on speed to reduce the waiting time on restart
3 = absolute DHW thermostats - 4 = smart anti-oscillation DHW function - 5 = all four previous functions active
02
iI
0
04
iI
0
05
iI
0
01
3
access to info menu
choise info
or
access to
parameter value
back to the previous level
4.3 INFO menu
b
The interface
automatically
quits the info
menu if no key
is pressed for
60 sec.
PARAMETER
NAME
DESCRIPTION
I001
Screed heater hours
Number of hours of screed heater function activation
I002
Delivery probe
Boiler delivery probe value
I003
Return probe
Boiler return probe value
I004
DHW probe
DHW probe value with boiler in instantaneous mode
I005
OT+ DHW setpoint
DHW setpoint sent by OT+ remote control to the boiler
I008
Flue gas probe
Flue gas probe value
I009
External probe
Instantaneous external probe value
I010
External temperature for thermoregulation
Filtered external probe value used in the temperature control algorithm to calculate
the heating setpoint
I011
DHW fl ow rate
DHW setpoint (only with OT+ connection)
I012
Fan rotations
Number of fan rotations (rpm)
I013
Flow sensor (main zone)
Value of the main zone fl ow sensor (when P4.12 = 1)
I015
Flue gas probe counter
Number of operating hours of the heat exchanger in “condensing mode”
I016
Delivery setpoint (main zone)
Delivery setpoint for the main zone
I017
OT+ CH setpoint
Heating setpoint sent by the OT+ timed thermostat to the boiler
I018
System pressure
System pressure level
I032
DHW comfort
DHW comfort mode
I033
Special DHW functions
Special functions active for high DHW inlet temperatures
I034
ID board
Identifi cation of the electronic board
I035
FW board revision
Firmware revision of the electronic board
I038
WIFI pendrive radio signal
Indicates the quality of the WIFI connection
I039
ALARM LOG 1 (the oldest)
List of the last fi ve alarms recorded
I040
ALARM LOG 2
I041
ALARM LOG 3
I042
ALARM LOG 4
I043
ALARM LOG 5 (the latest)