QUADRA GREEN C.S.I.
26
To restore operation (deactivate alarms):
Faults A01-02-03
Position the function selector to
(OFF) (fi g. 32), wait 5-6 seconds then
set it to the required position
(summer mode) or
(winter mode).
If the reset attempts do not reactivate the boiler, contact the Technical As-
sistance Centre.
Fault A04
In addition to the fault code, the digital display shows the symbol
.
Check the pressure value indicated by the water gauge: if it is less than 0.3
bar, position the function selector to (OFF) (fi g. 32) and adjust the fi lling
tap until the pressure reaches a value between 1 and 1.5 bar. Then position
the mode selector to the desired position
(summer) or
(winter).
The boiler will perform one purge cycle lasting approximately 2 minutes. If
pressure drops are frequent, request the intervention of the Technical As-
sistance Service.
Fault A06
The boiler operates normally but cannot reliably maintain a constant do-
mestic hot water temperature, which remains set at around 50°C. Contact
the Technical Assistance Centre.
Fault A07
-
A08
Contact the Technical Assistance Centre.
Fault A09 with fi xed red LED lit
Position the function selector to
(OFF) (fi g. 32), wait 5-6 seconds then
set it to the required position (summer mode) or (winter mode). If the reset
attempts do not reactivate the boiler, request the intervention of the Techni-
cal Assistance Service.
Fault A09 with fl ashing red and green LEDs
The boiler is equipped with an auto-diagnostic system which, based on the
total number of hours in certain operating conditions, can signal the need
to clean the primary exchanger (alarm code 09 with fl ashing red and green
LEDs and fl ue gas meter >2.500). Once the cleaning operation has been
completed, using the special kit supplied as an accessory, the total hour
meter will need to be reset to zero as follows:
- switch off the power supply
- remove the housing
- loosen the fi xing screw then turn the instrument panel
- loosen the fi xing screws on the cover (
F
) to access the terminal board
(fi g. 16)
- while the boiler is powered up, using a small screwdriver included, press
the
CO
button (fi g. 26) for at least 4 seconds, to check the meter has
been reset, power down then power up the boiler; the meter reading is
shown on the monitor after the “-C-” sign.
Live electrical parts.
NOTE:
the meter resetting procedure should be carried out after each
in-depth cleaning of the primary exchanger or if this latter is replaced. To
check the status of the total hour meter, multiply the reading by 100 (e.g.
reading of 18 = 1800 total hours; reading of 1 = 100 total hours).
The boiler continues to operate normally even when the alarm is activated.
Fault A77
This is an automatic-reset fault, if the boiler does not restart, contact the
Technical Assistance Centre.
Fixed yellow LED
Pre-heating function activated.
Flashing yellow LED
Combustion analysis in progress.
4.4 Alarm records
The “ALARM RECORDS” function starts automatically once the display has
been on for 2 hours, or immediately by setting the P1 parameter to 1.
The records include all the latest alarms, up to a maximum of 5 alarms, and
they are displayed in sequence by pushing and releasing the P1 button on
the display board. If the records are empty (P0=0) or if tracking the same is
disabled (P1=0), the display function is not available. Alarms are displayed
in reverse order compared to the order in which they occurred: this means
that the last alarm generated is the fi rst to be displayed.
BOILER STATUS
DISPLAY
RED LED
YELLOW LED
GREEN LED
TYPES OF ALARMS
Off status (OFF)
OFF
fl ashing 0.5 on/
3.5 off
None
Stand-by
-
fl ashing 0.5 on/
3.5 off
Signal
ACF alarm lockout module
A01
on
Defi nitive lockout
ACF electronics fault alarm
Fumes exhaust - air intake obstruction alarm
Limit thermostat alarm
A02
fl ashing 0.5 on/
0.5 off
Defi nitive lockout
Tacho fan alarm
A03
on
Defi nitive lockout
Water pressure switch alarm
A04
on
on
Defi nitive lockout
NTC domestic water fault
A06
fl ashing 0.5 on/
0.5 off
fl ashing 0.5 on/
0.5 off
Signal
NTC heating outlet fault
A07
on
Temporary stop
Heating outlet probe overtemperature
Temporary then
defi nitive
Outlet/return line probe diff erential alarm
Defi nitive lockout
NTC heating return line fault
A08
on
Temporary stop
Heating return line probe overtemperature
Temporary then
defi nitive
Outlet/return line probe diff erential alarm
Defi nitive lockout
Cleaning the primary heat exchanger
A09
fl ashing 0.5 on/
0.5 off
fl ashing 0.5 on/
0.5 off
Signal
NTC fl ue gases fault
Temporary stop
Flue gases probe overtemperature
on
Defi nitive lockout
False fl ame
A11
fl ashing 0.2 on/
0.2 off
Temporary stop
Low temperature system thermostat alarm
A77
on
Temporary stop
Temporary pending ignition
fl ashing 0.5 on/
0.5 off
Temporary stop
Water pressure switch intervention
fl ashing 0.5 on/
0.5 off
Temporary stop
Calibration service
ADJ
fl ashing 0.5 on/
0.5 off
fl ashing 0.5 on/0.5 off fl ashing 0.5 on/
0.5 off
Signal
Calibration installer
Chimney sweep
ACO
fl ashing 0.5 on/0.5 off
Signal
Vent cycle
fl ashing 0.5 on/
1.0 off
fl ashing 0.5 on/1.0 off
fl ashing 0.5 on/
1.0 off
Signal
Pre-heating active function
on
Signal
Pre-heating heat request
fl ashing
Signal
External probe presence
Signal
Domestic water heat request
60
°C
Signal
Heating heat request
80
°C
Signal
Antifreeze heat request
Signal
Flame present
on
Signal
4.3 Light signals and faults