Installer and user manual

CONNECT AT/BT LE

CONNECT AT/2BT LE

Summary of Contents for 20083971

Page 1: ...CONNECT BASE MIX 1 LE IT ISTRUZIONI PER L INSTALLATORE E PER IL SERVIZIO TECNICO DI ASSISTENZA EN INSTRUCTIONS FOR THE INSTALLER AND FOR TECHNICAL ASSISTANCE PL INSTRUKCJA MONTA U I OBS UGI Installer...

Page 2: ...ristinare la pressione come da libretto istruzioni Se si dovessero verificare cali di pressione frequenti chiedere l intervento di personale professionalmente qualificato che verificher lo stato del v...

Page 3: ...chiudere il dispositivo d intercettazione combustibile fare intervenire con sollecitudine il Servizio Tecnico di Assisten za B oppure personale professionalmente qualificato a a vietato toccare l app...

Page 4: ...to di scarico 2 Bottiglia di miscela 3 Circolatore impianto bassa temperatura 1 4 Circolatore impianto alta temperatura 5 Valvola di non ritorno interna alla tubazione 6 Valvola miscelatrice impianto...

Page 5: ...capacit adeguata alle dimensioni dell impianto b b Provvedere a sigillare i fori di passaggio dei tubi di collegamento dal CONNECT LE alla caldaia 1 6 Dati tecnici 1 7 Attacchi idraulici Le caratteri...

Page 6: ...3 4 5 6 7 8 0 5 1 1 5 Portata m3 h Prevalenza circolatore m 2 2 5 3 3 5 4 0 0 10 20 30 40 50 60 0 5 1 1 5 Portata m3 h Potenza assorbita circolatore W 2 2 5 3 3 5 4 CC4 CC3 CC2 CC1 CC1 CC2 CC3 CC4 PP...

Page 7: ...3 4 5 6 7 8 9 10 11 12 1314 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 3435 36 37 38 39 40 41 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 PT1B PT1C BL MA NE BL MA NE BL MA NE BL MA NE MA BL G...

Page 8: ...R1 M2 M7 M9 M11 M8 M10 TR1 TR2 TR3 PT1A M6 1 2 3 4 5 6 7 8 9 10 11 12 1314 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 1 2 3 4 5 6 7 8 9 10 11 PT1B PT1C BL MA NE B...

Page 9: ...2 Dimensioni e pesi L P H CONNECT LE AT BT AT 2BT L 400 P 160 H 720 Peso netto box 8 Peso netto frutto 15 18 Il box un accessorio che viene fornito separatamente su richie sta 2 3 Installazione all i...

Page 10: ...are le tubazioni 6 e 7 sugli attacchi 6a e 7A posti sulla bottiglia di miscela interponendo le apposite guarnizioni di tenuta fornite a corredo Inserire il i termometro i T1 T2 all interno della propr...

Page 11: ...TA 230V 50Hz IBT2 zona 2 IAT zona 3 IBT1 zona 1 REC TA CT1 ch1 REC TA CT2 ch2 REC TA CT3 ch3 REC TA Connessione termostato ambiente controllo re modo REC TA CT1 Controllo remoto termostato ambiente c...

Page 12: ...LE con tutte le tipologie di caldaie In questa modalit il CONNECT LE non trasferisce alla caldaia il set point calcolato sulle singole zone La caldaia avr perci una temperatura di mandata pari al set...

Page 13: ...ica b b I Termostati Ambiente e Cronotermostati devono avere un con tatto pulito libero da potenziale 2 6 2 Modalit Link Mode REC La modalit Link Mode configurabile per l utilizzo del CONNECT LE con c...

Page 14: ...rica b b I Termostati Ambiente e Cronotermostati devono avere un con tatto pulito libero da potenziale b b In caso di alimentazione fase fase verificare con un tester qua le dei due fili ha potenziale...

Page 15: ...e ad ogni canale la zona idraulica che si pre ferisce cos da definire per ogni singolo REC TA o CT quale zona 1 2 3 deve gestire Per associare i canali alle zone idrauliche occorre inserire i ponticel...

Page 16: ...3 MESSA IN SERVIZIO 3 1 Prima messa in servizio Prima di avviare il CONNECT LE verificare la corretta esecuzione dei collegamenti idraulici ed elettrici Durante la fase di collaudo possibile verificar...

Page 17: ...LE e caldaia agire sul REC del Canale 1 CH1 per impostare il regime voluto in caldaia estate inverno e su eventuali REC colle gati affinch non ci sia richiesta di calore con un collegamento Stand Alon...

Page 18: ...mento prevede una gestione antiblocco dei circo latori e delle valvole miscelatrici Al termine di ogni richiesta di calore su una zona viene attivato un re lativo timer della durata di 24 ore Se il ti...

Page 19: ...m postazioni disponibili appariranno in una sequenza ciclica Non premendo il tasto A l ultima impostazione scelta verr me morizzata 10 s 2 s 2 s impostazione visualizzazione impostazione visualizzazio...

Page 20: ...l impianto di riscaldamento sia in pressione l intervento dell interruttore generale di impianto la correttezza degli allacciamenti elettrici Per richieste di calore degli impianti miscelati verificar...

Page 21: ...Phillips n 2 nel foro 1 del circolatore premere a e ruotare b il cacciavite fino allo sblocco dell albero motore 1 a b Effettuare l operazione con estrema cautela per non danneggiare i componenti stes...

Page 22: ...emoto PER AZIONARE VALVOLE O TESTINE DI ZONA Collegamento LINK MODE collegare sugli ingressi BUS di scheda o della scheda interfaccia ove prevista Le sigle che identificano il BUS possono essere OT o...

Page 23: ...rc 2 TA2 Circ 2 SCHEMA FUNZIONALE per maggiori dettagli vedere foglio istruzioni scheda multizona e caldaia Ai morsetti M1B 26 27 Ai morsetti M1A 23 24 Per TUTTE le caldaie collegare ai contatti T A d...

Page 24: ...the system and restore if necessary following indications provided in the instruction man ual If the pressure should fall frequently request the intervention of a qualified technician to check the sy...

Page 25: ...shut off device immediately call the B Technical Assistance or a professionally qualified technician a a Do not touch the appliance when barefoot or with any wet parts of the body a a It is forbidden...

Page 26: ...13 16 1 3 2 4 5 6 7 12 13 16 8 1 Drain cock 2 Mixing bottle 3 Circulation unit low temperature system 1 4 Circulation unit high temperature system 5 Non return valve inside the pipe 6 Mixing valve lo...

Page 27: ...the pipe connection holes from the CONNECT LE to the boiler are sealed 1 6 Technical data 1 7 Plumbing connections The characteristics of the plumbing connections are as follows Ec Inlet from boiler 3...

Page 28: ...he circulation units rotate This is necessary because especially after lengthy periods of inactivity deposits and or residue may stop it rotating freely a a Do not run the circulation unit without wat...

Page 29: ...8 9 10 11 12 1314 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 3435 36 37 38 39 40 41 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 PT1B PT1C BL MA NE BL MA NE BL MA NE BL MA NE MA BL GI VE MA BL...

Page 30: ...2 M7 M9 M11 M8 M10 TR1 TR2 TR3 PT1A M6 1 2 3 4 5 6 7 8 9 10 11 12 1314 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 1 2 3 4 5 6 7 8 9 10 11 PT1B PT1C BL MA NE BL MA...

Page 31: ...s and weights L P H CONNECT LE AT BT AB 2BT W 400 D 160 H 720 Net weight of box 8 Net weight of appliance 15 18 The box is supplied separately on request as an accessory 2 3 Installation inside the bo...

Page 32: ...the couplings 6a and 7a located on the mixing bottle and positioning the designated seals sup plied Insert the thermometer s T1 T2 inside the seat 1 T2 6a 7a T1 6 7 Using the designated clips secure t...

Page 33: ...EC TA 230V 50Hz IBT2 zone 2 IAT zone 3 IBT1 zone 1 REC TA CT1 ch1 REC TA CT2 ch2 REC TA CT3 ch3 REC TA Remote control ambient thermostat connection REC TA CT1 Remote control ambient thermostat chrono...

Page 34: ...N BOILER Below are the connection diagrams of the CONNECT LE board to the boiler REC TA or CT and to the external sensor N B The connections are in relation to the model with 2 mixing zones Do not con...

Page 35: ...l connection box Insert the jumper into the seat ST6 of the CONNECT LE board disconnect the cable from the connector M6 and connect it to the connector M4 connect the other end of the same cable to th...

Page 36: ...REC IAT Remote control REC 07 08 HIGH temperature system M1C 31 30 REC IBT1 Remote control REC 07 08 LOW temperature system 1 M1A 25 24 REC IBT2 Remote contro REC 07 08 LOW temperature system 2 M1B 28...

Page 37: ...th a connected ex ternal sensor please refer to the chapters Trimmer and Tempera ture adjustment 3 COMMISSIONING 3 1 First start up Before starting up the CONNECT LE check that the plumbing and electr...

Page 38: ...int is the one selected by the trimmer from the lowest possible values see table in the section Trimmer adjustment under the heading WITHOUT external sen sor installed 3 3 2 Delivery temperature betwe...

Page 39: ...off for 2 hours after which time it will be reacti vated for 4 minutes If the temperature should fall below 6 C at any time a heat request is activated for a heat equal to the system s minimum tempera...

Page 40: ...e circulation unit operating modes Pressing the button A for more than 10 seconds enables disables the button lock function During this passage all LEDs C flash for 1 second 10 s Changing the operatin...

Page 41: ...board which are transmitted to the REC Alarm no Description 47 External sensor open or in short circuit 48 External sensor open or in short circuit in system ther moregulation mode 49 No communicatio...

Page 42: ...he shaft proceed as follows insert a screwdriver Phillips no 2 into the hole 1 of the circu lation unit press a and turn b the screwdriver until the motor shaft re leases 1 a b b b Take great care whe...

Page 43: ...se refer to the boiler installation manual Insert jumper on ST6 of the Connect board to configure the LINK MODE KEY 1 T A DIRECT CIRCUIT 2 T A MIX CIRCUIT 2 3 T A MIX CIRCUIT 1 4 REC DIRECT CIRCUIT 5...

Page 44: ...ONAL DIAGRAM for further information please refer to the instruction sheet for the boiler and the multizone board To terminals M1B 26 27 To terminals M1A 23 24 For ALL boilers connect to the boiler T...

Page 45: ...zasady bezpiecze stwa 46 1 3 Opis urz dzania 46 1 4 Budowa 47 1 5 Identyfikacja oznakowanie 47 1 6 Dane techniczne 48 1 7 Po czenia hydrauliczne 48 1 8 Pompy obiegowe 49 1 9 Schemat po cze elektryczn...

Page 46: ...nia b d c boso ani jakimikolwiek mokrymi cz ciami cia a a a Zabrania si przeprowadzania jakichkolwiek interwencji tech nicznych lub czyszczenia urz dzenia bez uprzedniego od cze nia go od zasilania el...

Page 47: ...Sprz g o hydrauliczne 3 Pompa obiegowa 1 strefy niskiej temperatury 4 Pompa obiegowa strefy wysokiej temperatury 5 Zaw r zwrotny wbudowany 6 Zaw r mieszaj cy 1 strefy niskiej temperatury 7 Zaw r odpo...

Page 48: ...kiej temperatury Mbt1 zasilanie 1 strefy niskiej temperatury 1 Mbt2 zasilanie 2 strefy niskiej temperatury 1 Rbt1 powr t 1 strefy niskiej tem peratury 1 Rbt2 powr t 2 strefy niskiej tem peratury 1 Rd...

Page 49: ...0 30 40 50 60 0 5 1 1 5 Portata m3 h Potenza assorbita circolatore W 2 2 5 3 3 5 4 CC4 CC3 CC2 CC1 CC1 CC2 CC3 CC4 PP3 PP3 CP3 PP2 PP2 PP1 P P 1 CP2 CP1 CP3 CP2 CP1 Wysoko podnoszenia m Pob r mocy prz...

Page 50: ...18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 3435 36 37 38 39 40 41 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 PT1B PT1C BL MA NE BL MA NE BL MA NE BL MA NE MA BL GI VE MA BL GI VE NE BL MA MA BL GI V...

Page 51: ...M8 M10 TR1 TR2 TR3 PT1A M6 1 2 3 4 5 6 7 8 9 10 11 12 1314 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 1 2 3 4 5 6 7 8 9 10 11 PT1B PT1C BL MA NE BL MA NE BL MA GI...

Page 52: ...przepisami poniewa mo e stanowi potencjalne zagro enie 2 2 Wymiary i waga L P H CONNECT LE AT BT AT 2BT L mm 400 P mm 160 H mm 720 Waga netto obudowy kg 8 Waga netto urz dzenia kg 15 18 Obudowa jest d...

Page 53: ...si na rozdzielaczu hydraulicznym i za o y odpowiednie uszczelki Umie ci termometry T1 T2 w gniazdach 1 T2 6a 7a T1 6 7 Przy pomocy przeznaczonych do tego zacisk w zamocowa sondy termometr w przestrzeg...

Page 54: ...na 2 IAT zona 3 IBT1 zona 1 REC TA CT1 ch1 REC TA CT2 ch2 REC TA CT3 ch3 KOCIO REC TA Przy cze programatora REC termostatu REC TA CT1 Programator REC lub termostat pokojowy cza sowy strefy NISKIEJ tem...

Page 55: ...mocy 35kW W tym trybie urz dzenie nie przeniesie ustawie ustalonych dla ka dej ze stref na kocio Dlatego temperatura zasilania z kot a b dzie r wna zadanej na kotle a REC TA lub CT b dzie kontrolowa...

Page 56: ...b Programatory termostatyczne termostaty czasowe musz by pod czone beznapi ciowo 2 6 2 Tryb LINK MODE REC W trybie LINK CONNECT LE komunikuje si z kot em wykorzystuj c protok OPEN THERM W tym trybie u...

Page 57: ...ch domy lnych b b Programatory termostatyczne oraz termostaty czasowe musz by pod czone bez napi ciowo b b W przypadku korzystania ze r d a zasilania typu faza faza na le y u y testera do okre lenia k...

Page 58: ...pozna si z rozdzia em Regulacja trymerami i Temperatury Jest mo liwe po czenie ka dego kana u do wybranej strefy w celu zdefiniowania kt ra strefa 1 2 3 jest kontrolowana przez kt re z wy mienionych u...

Page 59: ...kotle Dla stref wysokiej temperatury wsp czynnik K 2 patrz wykres 20 20 30 40 50 60 70 80 15 Temperatura esterna C K 2 K 1 K 0 5 K 3 K 5 Temperatura di mandata C 10 5 0 5 10 15 20 K 4 Temperatura zewn...

Page 60: ...ie LINK MODE nale y ustawi programator REC na kanale 1 CH1 aby wybra dan funkcj kot a lato zima a ka dy dodatkowy programator tak eby dania grzania nie by y wysy ane Je eli CONNECT LE skonfigurowano z...

Page 61: ...nd Cykl pe nego zamkni cia zawor w mieszaj cych tylko w stre fach niskich temperatur trwaj cy 120 sekund Pompy obiegowe wszystkich stref s w czane na 10 sekund Pod koniec wykonania powy szej procedury...

Page 62: ...awie Konfiguracja Poprzez wci ni cie przycisku A mo liwe jest ponowne przej cie do bie cych ustawie i sprawdzenie czy diody LED B i C sygnalizuj przez 2 sekundy ostatnio wprowadzone usta wienia Je li...

Page 63: ...elno po cze hydraulicznych Czy w instalacji jest odpowiednie ci nienie Czy g wny wy cznik systemu dzia a Poprawno po cze elektrycznych W przypadku zapotrzebowania na ciep o z obiegu niskiej temperatu...

Page 64: ...mog zaburza jego swobodne obroty Zwalnianie wirnika pompy obiegowej w razie potrzeby W celu zwolnienia wirnika pompy nale y post powa w nast puj cy spos b Wsun rubokr t krzy akowy PH 2 do otworu 1 pom...

Page 65: ...ermostat pokojowy 1 strefy niskiej tempe ratury Programator lub ter mostat pokojowy strefy wysokiej temperatury Programator REC lub termostat pokojowy 2 strefy niskiej temp 2 strefa niskiej temperatur...

Page 66: ...tablicy zarz dzaj cej wieloma strefami P yta Wie lostr Obieg V1 Circ 1 Obieg TA2 Circ 1 Obieg V2 Circ 1 Obieg V2 Circ 2 Obieg TA2 Circ 2 Obieg TA1 Circ 2 Obieg V1 Circ 2 Do z czy M1A 23 24 Do z czy M1...

Page 67: ...67...

Page 68: ...63 info berettaboilers com www berettaboilers com In order to improve its products Beretta reserves the right to modify the characteristics and information contained in this manual at any time and wit...