24
Par.
Ref.
Desc.
Factory
set value
Type
Operation
08
Max set point
heating
85°C
(30°C ÷
85°C)
Type
rEc
Use the
button to decrease and the
button
to increase the temperature value. The value is
automatically memorized when moving to the next
parameter. This parameter put a high limit on the
maximum temperature value communicated to the
boiler.
09
Min set point
heating
30°C
(30°C ÷
85°C)
Type
rEc
Use the
button to decrease and the
button
to increase the temperature value. The value is
automatically memorized when moving to the next
parameter. This parameter put a low limit on the
minimum temperature value communicated to the
boiler.
10
Climatic curve
selection
1.2
(see
climatic
curves)
Type
rEc
Use the
button to decrease and the
button
to increase the climatic curve value (see below
the climatic curves). The value is automatically
memorized when moving to the next parameter.