background image

Function danfoss  BFP11

When the oil pump is started, oil is 

drawn from the suction connection 

(S) through the ilter (H) to the suction 

side of the gear wheel (C).

The gear wheel then pumps oil to the 
pressure side and the oil is put under 
pressure.
The pressure is controlled and kept 
constant at the set value by the 
regulating valve (P

1

) with the 

diaphragm (D). 
The regulating valve (P

1

) distributes 

the oil quantity supplied by the gear set 
(C) between the nozzle port (E) and 
the return side of the pump (R). 
The oil quantity utilized is determined 
by the set pressure on the regulating 
valve (P

1

) and the size of the oil nozzle 

in the nozzle line.
The valve (P

1

) functions in the following 

way:

-  When the opening pressure has  

  been reached, the passage to the  
  return side opens.
-  The diaphragm and the spring   
  keep the pump pressure constant  
  at set value.

171 505 29  07-01

INSTRUCTIONS PUMP TYPE DANFOSS BFP11

Replacement of cartridge ilter, mounting/dismounting return plug

In case of one-pipe operation the 
horse-shoe-shaped washer will be 
mounted under the screw head, and 
in case of two-pipe operation, the 
horse-shoe-shaped washer will be 
removed.

The horse-shoe-shaped washer will 
be introduced in all BFP 11-pumps .

To minimize the leak between cover 
plate and pump housing when running 
one-pipe operation, the changeover 
screw will be mounted generally. But 
in order for the return oil in the pump 

to be able to low freely to the suction 

side, a horse-shoe-shaped washer will 
be mounted under the screw.

R

S

E

NC

A

G

H

V

P

1

P

D

C

-  If the pump is overloaded, i.e. if
  you try to get out more oil than
  the gear set can supply under
  existing circum-stances, the oil  
  pressure falls below the set value  
  and the valve closes against the  
  return side (R) by means of the  
  diaphragm (D) and goes into    
  starting position.

This can be remedied by:
-  Reducing the pump pressure.
-  Reducing the oil quantity supplied  
  by using a smaller nozzle.
-  Using a pump with a larger capacity.

Summary of Contents for STERLING 40 ST108PL

Page 1: ...Providing sustainable energy solutions worldwide 178 016 13 Installation and maintenance instruction STERLING 40 ST108PL ...

Page 2: ......

Page 3: ...cables 5 Nozzle assembly 6 Nozzle 7 Brake plate 8 Blast tube 9 Ignition electrodes 10 Connecting pipe 11 Air damper 12 Solenoid valve 13 Pump 14 Drive coupling 15 Indication air damper 16 Fan wheel 17 Adjustment air damper 18 Photoresistor 19 Motor 171 205 32 07 01 Components ...

Page 4: ...with the pump pressure Output range and nozzles recommended The net caloriic value of 11 86 kWh kg for light oil has been used Burner tube Length of burner tube Incl lange A Measure B Incl lange B Measure B Incl lange C Measure B Incl lange D Measure B PL 80 45 58 66 65 2 5 3 1 7 0 8 0 0 5 0 5 B 188 275 145 ø89 56 239 162 Burner tube Oil capacity Outputy Recommended Nozzle Recommended Pump pressur...

Page 5: ...TECHNICAL DATA 171 215 76 07 01 Flange A 10 3 25 130 150 ø89 7 Flange C 10 125 ø90 4 Flange D 125 150 10 3 ø90 5 12 Flange B ø89 5 12 136 150 Dimensions ...

Page 6: ... soot occurs and increase again to reach a combustion free of soot By this procedure an optimum adjustment is obtained If larger nozzles are used the preadjustment of the air volume must be increased Condensation in chimney A modern burner works with less excess air and often also with smaller nozzles than older models This increasestheeficiencybutalsotherisk ofcondensationinthechimney Therisk inc...

Page 7: ...MAINTENANCE OF OIL BURNER Warning Before doing any service switch off power at the main switch and cut off the oil supply 171 305 68 07 01 Service of burner head and nozzle assembly ...

Page 8: ...IC EQUIPMENT 1 2 LMO14 113 LMO24 255 LOA24 171 Pre ignition time 15 s 25 s 13 s Pre purge time 16 s 26 s 13 s Post ignition time 3 s 5 s 15 s Safety lock out time 10 s 5 s 10 s Reset time after lockout 1 s 1 s 50 s Reaction time on lame failure 1 s 1 s 1 s Ambient temperature 5 60 C 20 60 C 20 60 C Min current with lame established 45 µA 45 µA 65 µA Max photo current at start 5 5 µA 5 5 µA 5 µA En...

Page 9: ...as provide indication if something ab normal is happening in accordance with the following table Preheater in operation Solid yellow Ignition switched on Flashing yellow Normal operation Solid green Operation poor lame signal Flashing green Undervoltage Flashing yellow red Fault alarm Solid red False light Flashing red green Communication mode Fluttering red Fault codes LMO14 24 When the red light...

Page 10: ...ndards On commissioning with an empty tube system the oil pump should not be run without oil for more than 5 min a condition is that the pump is being lubricated during operation The tables state the total suction line length in metres at a nozzle capacity of 2 5 kg h Max permissible pressure at the suction and pressure side is 2 0 bar Purging On 1 pipe systems it is necessary to purge the pump On...

Page 11: ...TYPE DANFOSS BFP11 Replacement of cartridge ilter mounting dismounting return plug In case of one pipe operation the horse shoe shaped washer will be mounted under the screw head and in case of two pipe operation the horse shoe shaped washer will be removed The horse shoe shaped washer will be introduced in all BFP 11 pumps To minimize the leak between cover plateandpumphousingwhenrunning one pipe...

Page 12: ... 93 9 71 115 99 10 24 121 104 10 73 127 109 3 00 9 98 118 102 10 59 126 108 11 16 132 114 11 71 139 119 3 50 11 65 138 119 12 35 146 126 13 03 154 133 13 66 162 139 4 00 13 31 158 136 14 12 167 144 14 89 176 152 15 62 185 159 4 50 14 97 177 153 15 88 188 162 16 75 198 171 17 57 208 179 5 00 16 64 197 170 17 65 209 180 18 62 221 190 19 52 231 199 5 50 18 30 217 187 19 42 230 198 20 48 243 209 21 47...

Page 13: ...11 21 133 114 11 67 138 119 12 11 144 123 12 53 148 128 3 00 12 23 145 125 12 73 151 130 13 21 157 135 13 67 162 139 3 50 14 27 169 145 14 85 176 151 15 42 183 157 15 95 189 163 4 00 16 31 193 166 16 97 201 173 17 62 209 180 18 23 216 186 4 50 18 35 217 187 19 10 226 195 19 82 235 202 20 51 243 209 5 00 20 39 242 208 21 22 251 216 22 03 261 225 22 79 270 232 5 50 22 43 266 229 23 34 277 238 24 23 ...

Page 14: ...of magnetic valve Burner fails to start Lamp not lit Motor runs Burner runs to lockout Fuse has blown Appliance thermostat has not reset Appliance overheat device has operated Control relay or photocell defective No oil being delivered Excessive lue draught is preventing lame establishment No spark Check or replace fuse if necessary Check reason for failure Adjust thermostat Reset overheat device ...

Page 15: ...ont conformes aux normes et aux documents normatifs suivants et satisfont aux critères applicables des directives CE suivantes Dokument EN 267 EN 60335 EU direktiv EU Directives EU Direktiven CE suivantes 2004 108 EC Elektromagnetisk kompatibilitet Electromagnetic compatibility EC Richtlinie Compatibilité électromagnétique 2006 95 EC Lågspänningsdirektivet Low voltage directive Niederspannungs Ric...

Page 16: ......

Page 17: ... the burner will not start Press the reset button on the relay Check that the thermostats are correctly adjusted Don t forget the room thermostat check that any fusesare intact and main switch is on If the burner starts but does not ignite Make an attempt to start the burner Never make close repeated start attempts Don t restart the burner until the boiler is free from oil gases If the burner stil...

Page 18: ......

Page 19: ......

Page 20: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com ...

Reviews: