4.2.1
List of components
A1
Gas burner control
S4
Temperature limiter
A3
Leakage control VPS 504
S7
Main switch
B1
Ionisation electrode
S8
Air pressure switch
U2
UV-detector QRC
S9
Gas pressure switch, min
F1
Fuse
T1
Ignition Transformer
H1
Operating lamp
Y1
Solenoid valve
M1
Motor
X3
Plug-in contact, burner
P1
Timer total operating time
X4
Plug-in contact, boiler
S3
Control thermostat
4.3
Function LME...
1.
Operating switch ON-Thermostat ON-Gas pressure switch ON
A check that the air pressure switch does not indicate fan pressure is
carried out.
2.
Burner motor starts
A check that the air pressure switch indicates sufficient fan pressure is
carried out.
3.
The ignition spark is created
4.
The gas solenoid valve is open
The gas is ignited. The ionisation electrode now indicates a flame.
5.
The safety time expires
The ignition spark ceases. The safety period ceases. If the spark is missing
or it disappears after this time limit, the gas burner control is blocked.
6.
Operating position
7.
Stop
The operation of the burner can now be stopped with the control switch or
thermostat.
If the gas burner control is blocked
Red light in the gas burner control is lit. The burner is restarted by pushing
the reset button.
!
Mains connection and
fuse in accordance
with local regulations.
4.3.1
Technical data
LME23.331C2
3 s
30 s
2.5 s
< 3 s
< 1 s
< 1 s
5 µA
20 µA
160303-324
Preiginition time
Prepurge time
Postignition time
Safety lockout time
Reset time after lockout
Reaction time on fl ame failure
Min. ionisation current at fl ame
Max. ionisation current