Before obtaining access to electrical and fuel line components
all supply circuits must be disconnected.
5. Mounting
The burner is mounted on the boiler with bolts (A) according to the hole
pattern on the fixing flange.
1.
Install the fixing flange (B) and the enclosed gasket (C) on the boiler.
If new mounting holes need to be drilled, use the fixing flange as a
template and fasten with M8-M10 screws.
2.
Loosen the burner tube (D) and fit the enclosed gasket (E) around the
flame tube and check that the ignition electrodes are set correctly, see
chapter Gas nozzle.
3.
Mount the burner on the fixing flange and fasten with screws (F).
4.
Check/Mount the enclosed o-ring on the gas connection and mount
the gas fixture on the burner.
5.
Connect electrical connection for gas valve, gas pressure switch min,
gas pressure switch max and VPS/Tightness check.
6.
Connect gas line, connect supply cable, operating and safety circuits.
160303-510