33
Bentone
!
When servicing/replacing components that aff ect combustion,
fl ue gas analysis and soot test shall be carried out on the
installation.
172 615 97
10.5 Air intake and suction cone
1.
Disconnect the main power and shut off the fuel supply.
2.
Remove gas line by loosening the electrical cabling and screws to the
gas valve and lift out.
3.
Loosen screws and lift burner out of fi xing fl ange.
4.
Remove air intake and fl ame tube.
5.
Disconnect ignition cable.
6.
Disassemble the burner by loosening the through screw (K) and
removing the front piece.
7.
Check function and appearance of the various components included
in the air control. Clean and replace components if necessary.
8.
Refi t the burner in reverse order. Be sure to fi t components in the
same position as when they were removed.
9.
Turn on the main power and open the fuel supply.
10. Start burner and check/adjust combustion.
!
Check for leaks in the gas line.
K
160303-514
160303-515
!
Before obtaining access to electrical and fuel line components
all supply circuits must be disconnected.