12. Troubleshooting
Gas Burner
Conditions favourable to disruption-free operation of the system can only be
guaranteed through the interaction between three factors – electricity, gas flow and
combustion air. A change in any of these factors may cause disruptions.
It has been shown that a large proportion of disruptions can be attributed to
relatively small things. Therefore, before requesting servicing, you should ascertain
the following:
1.
Are the system’s gas taps open?
2.
Are the fuses intact and is the power on?
3.
Are control devices (room thermostat, boiler thermostat, etc.) correctly set?
4.
Is gas pressure to the burner sufficient?
5.
Are the burner controls on standby and not locked?
6.
Is air supply to the burner adequate?
Cause of fault
Action
Burner does not start:
No gas.
Make sure all gas taps are open.
No power.
Check the fuse, thermostat and electrical
connections.
Burner motor does not start.
Motor protection has tripped. Motor faulty.
Burner control faulty.
Replace.
Burner motor running, no ignition spark at the end of
pre-aeration:
No power in the terminals.
Check the connector. Replace faulty burner
controls.
Ignition electrodes in contact with each other or earth.
Adjust.
Ignition electrode porcelain damaged.
Replace the electrodes.
Poor connection to cable connectors.
Adjust connection.
Ignition cables damaged.
Replace.
Transformer damaged, no power to secondary winding.
Replace the transformer.
Ignition cable and ionisation cable swapped around.
Reconnect.
No flame propagation:
Gas solenoid valve faulty.
Replace.
Gas solenoid valve does not open despite having power.
Replace solenoid valve terminals, or entire valve.
No power to solenoid valve.
Check the connection.
No electrical connection through air pressure gauge.
Check the air pressure gauge’s settings and
functions.
Ignition load incorrectly set.
Increase/decrease gas supply Reduce airflow.
Burner control faulty
Replace
Air pressure gauge incorrectly set or faulty
Check the settings and reset, or replace
No acknowledgement signal due to incorrect adjustment or
misalignment of the control motor cams.
Check the settings and realign.
Summary of Contents for BG 700-2 Biogas
Page 17: ...17 Bentone 45 Natural gas Propan Biogas UV detektor 4 10 Gas nozzle...
Page 37: ...37 Bentone 10 2 Wiring diagram BP S2...
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com...