43
Bentone
NO.
F
AUL
T
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
POSSIBLE SOLUTION
40
HARDW
ARE RESET
RED
Replace the control unit. Contact reseller/distributor if the fault
persists.
41
HARDW
ARE RESET
RED
Replace the control unit. Contact reseller/distributor if the fault
persists.
42
CONTROL
PROGRAM
FROZEN
RED
Replace the control unit. Contact the distributor/factory
.
43
CONTROL
PROGRAM
FROZEN
RED
Replace the control unit. Contact reseller/distributor
.
44
TIMER2 ERROR
RED
Replace the control unit. Contact reseller/distributor
.
45
LOW VOL
T
AGE ERROR
RED
Check mains power
. Contact reseller/distributor if the fault persists.
46
LOW VOL
T
AGE ERROR
RED
Check mains power
. Contact reseller/distributor if the fault persists.
47
UV DETECTION F
AUL
TY
RED
Replace the control unit. Contact reseller/distributor
.
48
INTERNAL
F
AUL
T
RED
Replace the control unit. Contact reseller/distributor
.
49
INTERNAL
F
AUL
T
RED
Replace the control unit. Contact reseller/distributor
.
50
IGNITION FEEDBACK
RED
The system detected voltage at terminal 16 at the incorrect time, or
no voltage. Check cabling and ensure sufficient earthing.
51
PILOT
FEEDBACK
RED
The system detected voltage at terminal 17 at the incorrect time, or
no voltage. Check cabling and ensure sufficient earthing.
52
MAINP
FEEDBACK
RED
The system detected voltage at terminal 19 at the incorrect time, or
no voltage. Check cabling and ensure sufficient earthing.
53
W
AITING
TIME
FEEDBACK
LIMIT
EXCEEDED
RED
Loss of feedback from the damper motor for more than 10 minutes.
Check the cabling. Check the damper motor
.
54
MAIND FEEDBACK
RED
The system detected voltage at terminal 18 at the incorrect time, or
no voltage. Check cabling and ensure sufficient earthing.
55
DIAGNOSTICS
INTERRUPTED
RED
Replace the control unit. Contact reseller/distributor
.
56
UV F
ALSE FLAME
RED
False flame detected prior to ignition. Check the cabling. Check the
flame detector
. Ensure sufficient earthing.
57
IONISA
TION F
ALSE FLAME
RED
False flame detected prior to ignition. Check the cabling. Check the
flame detector
. Ensure sufficient earthing.
58
OPEN FEEDBACK READING
RED
The system detected voltage at terminal 8 at the incorrect time, or no
voltage. Check cabling and ensure sufficient earthing.
59
ADJACENT
POLE SHOR
T
-
CIRCUIT
RED
Replace the control unit. Contact reseller/distributor
.
60
LOCAL
RESET
RED
The local reset button has been pressed in for more than 10
seconds, or the reset button is stuck.
61
FUEL
V
AL
VE OPEN
RED
Fuel valve open at incorrect time.
62
STRONG UV FLAME
RED
Flame detector too close to the flame. Increase the distance
between the flame detector and the flame.
63
INTERNAL
F
AUL
T
RED
Replace the control unit. Contact reseller/distributor
.
172 615 70
201022 /5
Summary of Contents for BG 700-2 Biogas
Page 17: ...17 Bentone 45 Natural gas Propan Biogas UV detektor 4 10 Gas nozzle...
Page 37: ...37 Bentone 10 2 Wiring diagram BP S2...
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com...