32
Bentone
7.3 Replacement of damper motor, air
Removal and installation
1.
Break the main current and disconnect the Euro plugs from the burner.
2.
Note the connection position of the cables on the damper motor.
3.
Disconnect the damper motor cable from the damper motor.
4.
Loosen the screws (G) to the damper motor mounting plate.
5.
Lift up the damper motor.
6.
Remove the control arm from the motor shaft.
7.
Remove the screws (I) securing the damper motor to the mounting
plate.
8.
Remove the damper motor from the mounting plate.
9.
Install the new damper motor on the mounting plate.
10. Fit the control arm on the damper motor shaft. It is important that the
screw is perpendicular to the plane of the shaft.
11. Re-install the damper motor and mounting plate on the air intake.
Ensure that the damper shaft and control arm are connected correctly.
12. Connect the damper motor cable.
13. Fit the Euro plugs and turn on the mains power.
14. Check/adjust the combustion.
!
If the burner is directly connected, ensure that all
components on the burner are without power.
-
Releasing button
By pressing the button and snapping
it down, the motor will be released
and the damper can easily be
turned. This function facilitates an
exchange of damper motor.
G
G
G
I
I
H
Summary of Contents for BG 450-2
Page 2: ...2 Bentone...
Page 18: ...18 Bentone 4 11 Gas nozzle 45 Natural gas Propan Biogas UV detector...
Page 47: ...172 905 04 2018 02 15 12 EU Declaration of conformity Bentone Gasburners...
Page 50: ......
Page 51: ......
Page 52: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...