10.3 List of components
A1
Gas burner control
A3
Valve, leak tester, Dungs
VPS504
F1
Operating fuse
H1
Lamp, low capacity
H2
Lamp, high capacity
H3
Alarm signal 230 V
K1 Contactor
M1
Burner motor
M2
Damper Motor, L&S
SQN75.254.A21B
P1
Time meter, total operating
time
P2
Time meter, high capacity,
total operating time
S1
Operating switch
S2
Operating switch, stage 2
S3
Control thermostat
S4
Temperature limiter
S5
Micro switch for hinged door
S6
Control thermostat, stage 2
S7
Main switch
S8
Air pressure switch
S9
Gas pressure switch
Q1
Signal amplifier AGQ
R1 UV-Detector
T1
Ignition transformer
X1
Connection terminal board
X2
Earth terminal
X3
Plug-in contact, burner
X4
Plug-in contact, boiler
X5
Plug-in contact, stage 2,
burner
X6
Plug-in contact, stage 2,
boiler
Y1
Gas solenoid valve 1
Y2
Gas solenoid valve 2
Y3
Safety solenoid valve
10.3.1 Function LME...
1.
Operating switch ON-Thermostat ON-Gas pressure switch
ON
A check that the air pressure switch
does not
indicate fan pressure
is carried out
2.
Burner motor starts
A check that the air pressure switch indicates sufficient fan pressure
is carried out
3.
The ignition spark is created
4.
The gas solenoid valve is open
The gas is ignited. The ionisation electrode now indicates a flame
5.
The safety time expires
The ignition spark ceases. The safety period ceases. If the spark is
missing or it disappears after this time limit, the gas burner control is
blocked
6.
Operating position
7.
Stop
The operation of the burner can now be stopped with the control
switch or thermostat
If the gas burner control is blocked
Red light in the gas burner control is lit. The burner is restarted by
pushing the reset button
Summary of Contents for BG 450-2
Page 2: ...2 Bentone...
Page 18: ...18 Bentone 4 11 Gas nozzle 45 Natural gas Propan Biogas UV detector...
Page 47: ...172 905 04 2018 02 15 12 EU Declaration of conformity Bentone Gasburners...
Page 50: ......
Page 51: ......
Page 52: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com...