29
Bentone
T =
Temperature of gas at the gas meter
[°C]
B =
Barometer reading
[mbar]
P =
Pressure of gas at the gas meter
[mbar]
f =
Factor calculated for multiplication with flow in Nm
3
/h to
arrive at actual flow in Nm
3
/h.
V =
Actual flow
[m
3
/h]
f =
273
·
B+P
273+T
1013.25
Example A
V
0A
=
Q
.
3600
=
160 · 3600
≈
18.8 Nm
3
/h
H
u
·
η
34020 · 0.90
Example B
V
0B
=
Q
≈
160
≈
19 Nm
3
/h
H
u
·
η
9.5 · 0.90
Example C
V
0C
=
Q
=
160
≈
19 Nm
3
/h
H
u
· 0,00116 ·
η
8126 · 0.00116 · 0.90
If the barometer reading (altitude), pressure and temperature of the gas
deviate significantly from normal values, this must be taken into account as
follows:
Calculation example:
Q =
160 kW
H
U
=
Example A: 34020 MJ/Nm
3
Example B: 9.5 kWh/Nm
3
Example C: 8126 kcal/Nm
3
η =
90%
V
0
=
Desired quantity of gas
[Nm
3
/h]
Q =
Boiler output
[kW]
H
U
=
Gas heat value
[kWh/Nm
3
] or [MJ/Nm
3
] or [kcal/
Nm3]
η
=
Boiler efficiency
[%]
7.3 Example of how to calculate the
gas quantity (natural gas G20):
Summary of Contents for BG 300 M-J/K-IP40
Page 17: ...17 Bentone 172 515 08 2018 01 02 4 8 Gas nozzle Natural gas Propan Biogas UV detector 2 5 8 0 ...
Page 36: ...36 Bentone 11 2 Wiring diagram BG300 BP JK IP 40 ...
Page 46: ...14 EU Declaration of conformity Bentone Gasburners ...
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com ...