48
Bentone BFG1
8.2.2 Function LME...
1.
Operating switch ON-Thermostat ON-Gas pressure switch ON
A check that the air pressure switch
does not
indicate fan pressure is
carried out.
2.
Burner motor starts
A check that the air pressure switch indicates sufficient fan pressure is
carried out.
3.
The ignition spark is created
4.
The gas solenoid valve is open
The gas is ignited. The ionisation electrode now indicates a flame.
5.
The safety time expires
The ignition spark ceases. The safety period ceases. If the spark is
missing or it disappears after this time limit, the gas burner control is
blocked.
6.
Operating position
7.
Stop
The operation of the burner can now be stopped with the control switch
or thermostat.
If the gas burner control is blocked
Red light in the gas burner control is lit. The burner is restarted by
pushing the reset button.
8.2.1 List of components
A1
Gas burner control
A3
Valve, leak tester, Dungs VPS504 (optional)
A7
RC circuit
B1
Ionisation electrode
U2
UV-sond QRC (LME23...)
F1
Fuse
H1
Lamp, operation
M1
Burner motor
P1
Timer total operating time
S3
Control thermostat
S4
Temperature limiter
S7
Main switch
S8
Air pressure switch
S9
Gas pressure switch
S30
External reset
T1
Ignition Transformer
Y1
Solenoid valve
X3
Plug-in contact, burner
X4
Plug-in contact, boiler
X17
Plug-in contact, burner external reset (optional)
X18
Plug-in contact, boiler external reset (optional)
Summary of Contents for BFG 1 H1
Page 13: ...13 Bentone BFG1 4 3 5 1 6 2 10 16 9 15 14 13 7 8 22 11 12 2 7 Description ...
Page 47: ...47 Bentone BFG1 Alt 1 Acc to DIN 4791 Alt 2 Alt 3 8 2 Wiring diagram ...
Page 54: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com ...