33
Bentone
1
Switch on operating switch and twin thermostat
A spark is formed. The air damper motor opens the damper to low
load position. The burner motor starts, the prepurge goes on till the
prepurge period expires and the solenoid valve 1 opens (2).
2.
Solenoid valve 1 opens
Oil mist is formed and ignited. The photocell indicates a flame. The
ignition spark goes out after flame indication (See Technical data oil
burner control).
3.
a
b
The safety time expires
If no flame is established before this time limit the control cuts out.
If for some reasons the flame disappears after this time limit, the
burner will make an attempt to re-start.
4
High/Low thermostat ON
The burner is in operating position and can now change between
full load and low load.
4-5
Operating position
If the burner operation is interrupted by means of the main switch
or the thermostat, a new start takes place when the conditions in
accordance with point 1 are fulfilled.
The oil burner control cuts out
A red lamp in the control is lit. Press the reset button and the
burner re-starts.
8.1.1 List of components
A1
Oil burner control
U2 UV-cell QRC
E1
Preheater
S3
Control thermostat
E2
Burner without preheater
S4
Temperature limiter
F1
Fuse max. 10 A
S7
Main switch
H1 Lamp, low capacity
T1
Ignition transformer
M1 Burner motor
Y1
Solenoid valve
P1
Time meter, low capacity
(optinal)
X3
Plug-in contact, burner
R1 Flame detector QRB
X4
Plug-in contact, boiler
Preheater cable color:
A Blue
B Brown
C Black
8.2 Function LMO14/24
!
Mains connection and
fuse in accordance
with local regulations.
8.2.1
Technical data oil burner control
LMO14.113...
LMO24.255...
15 s
25 s
16 s
26 s
3 s
5 s
< 10 s
< 5 s
< 1 s
< 1 s
< 1 s
< 1 s
-5 - +60°C
-20 - +60°C
45 µA dc
45 µA dc
5.5 µA dc
5.5 µA dc
160303-333
Preiginition time
Prepurge time
Postignition time
Safety lockout time
Reset time after lockout
Reaction time on fl ame failure
Ambient temperature
Min detector current required (with fl ame)
Max perm. detector current (without fl ame)