10
Bentone
2.6 Recommended nozzles and pressures
Because of the different types of boiler in existence, with varying furnace
geometries and furnace loads, it is not possible to commit to any given spray
angle or spay pattern. Note that spray angles and spray patterns change
with pump pressures.
Nozzle
60° Solid/Hollow cone
80° Solid/Hollow conel
Pump pressure
10 bar (8–14 bar) Fuel oil 1
10 bar (7–12 bar) Kerosene
Nozzle table, 8-15 bar
Pump pressure, bar
Gph
8
9
10
11
12
13
14
15
kg/h
kW
kg/h
kW
kg/h
kW
kg/h
kW
kg/h
kW
kg/h
kW
kg/h
kW
kg/h
kW
0,40 1,33
16
1,41
17
1,49
18
1,56
18
1,63
19
1,70
20
1,76
21
1,82
21
0,50 1,66
20
1,76
21
1,86
22
1,95
23
2,04
24
2,12
25
2,20
26
2,28
27
0,60 2,00
24
2,12
25
2,23
26
2,34
28
2,45
29
2,55
30
2,64
31
2,73
32
0,65 2,16
26
2,29
27
2,42
29
2,54
30
2,65
31
2,75
33
2,86
34
2,96
35
0,75 2,49
29
2,65
31
2,79
33
2,93
35
3,08
36
3,18
38
3,30
39
3,42
40
0,85 2,83
33
3,00
36
3,16
37
3,32
39
3,47
41
3,61
43
3,74
44
3,87
46
1,00 3,33
39
3,53
42
3,72
44
3,90
46
4,08
48
4,24
50
4,40
52
4,56
54
1,10 3,66
43
3,88
46
4,09
48
4,29
51
4,48
53
4,67
55
4,84
57
5,01
59
1,20 3,99
47
4,24
50
4,47
53
4,68
55
4,89
58
5,09
60
5,29
63
5,47
65
1,25 4,16
49
4,40
52
4,65
55
4,88
58
5,10
60
5,30
63
5,51
65
5,70
68
1,35 4,49
53
4,76
56
5,02
59
5,27
62
5,50
65
5,73
68
5,95
70
6,15
73
1,50 4,98
59
5,29
63
5,58
66
5,85
69
6,11
72
6,36
75
6,60
78
6,83
81
1,65 5,49
65
5,82
69
6,14
73
6,44
76
6,73
80
7,00
83
7,27
86
7,52
89
1,75 5,82
69
6,18
73
6,51
77
6,83
81
7,14
85
7,42
88
7,71
91
7,97
94
2,00 6,65
79
7,06
84
7,45
88
7,81
93
8,18
97
8,49
101
8,81
104
9,12
108
2,25 7,49
89
7,94
94
8,38
99
8,78
104
9,18
109
9,55
113
9,91
117
10,26
122
The table applies to oils with a viscosity of 4.4 mm
2
/s (cSt) at a density of 830 kg/m
3
.
Burner with preheater
Allow for a reduction in oil quantity of 5–20% with preheating owing to:
• Temperature increases at the nozzle.
• Nozzle design.
• Capacity (the higher the capacity the lower the difference).
2.2 Recommended nozzles and pressures
Summary of Contents for BF 1 KSV RME
Page 12: ...12 Bentone 2 11 12 1 10 5 15 24 22 21 23 13 3 17 14 19 20 ...
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone com ...